background image

484 01 3905 04

7

Specifications subject to change without notice.

3” (76mm)

A13067

Figure 10 

 

Condensate Trap

NOTE

: If unit is located in or above a living space, where

damage may result from condensate overflow, a field

supplied,

external condensate pan should be installed underneath the

entire unit, and a secondary condensate line (with appropriate

trap) should be run from the unit into the pan. Any condensate

in this external condensate pan should be drained to a

noticeable place. As an alternative to using an external

condensate pan, some localities may allow the running of a

separate 3/4 inch (19 mm) condensate line (with appropriate

trap) per local code to a place where the condensate will be

noticeable. The owner of the structure must be informed that

when condensate flows from secondary drain or external

condensate pan, the unit requires servicing or water damage

will occur. To further protect against water damage, install a

float switch to shut the unit off if the water in the secondary pan

gets too high.

Condensate
Line

Trap

Sewer Line

Air Gap Above
Liquid Level

A10216

Figure 11 

 

Condensate Drain to Waste Line

WASTE LINE CONNECTION

If the condensate line is to be connected to a waste (sewer)

line, an open trap must be installed ahead of the waste line to

prevent escape of sewer gases (See 

Figure 11

)

CARE AND MAINTENANCE

To continue high performance and minimize possible equipment

failure, it is essential that periodic maintenance be performed on this

equipment. Consult your local dealer as to the proper frequency of

maintenance, but it should be done at least annually.
The ability to properly perform maintenance on this equipment

requires certain mechanical skills and tools. If you do not possess

these, contact your dealer for maintenance. The only consumer service

recommended or required is  filter replacement or cleaning on a

monthly basis.

ENVIRONMENTAL HAZARD

Failure to follow this caution may result in environmental

damage.
Remove and recycle all components or materials (i.e., oil,

refrigerant, etc.) before unit final disposal.

CAUTION

!

Copyright 2019 International Comfort Products

Lewisburg, TN  37091 USA

Summary of Contents for EAM4X Series

Page 1: ...personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and pro...

Page 2: ... EAM4X36L21A 3 21 533 3 8 3 4 EAM4X37L17A 3 17 1 2 445 3 8 3 4 EAM4X37L21A 3 21 533 3 8 7 8 EAM4X42L21A 3 1 2 21 533 3 8 7 8 EAM4X42L24A 3 1 2 24 1 2 622 3 8 7 8 EAM4X43L21A 3 1 2 21 533 3 8 7 8 EAM4X48L17A 4 17 1 2 445 3 8 7 8 EAM4X48L21A 4 21 533 3 8 7 8 EAM4X48L24A 4 24 1 2 622 3 8 7 8 EAM4X60L21A 5 21 533 3 8 7 8 EAM4X61L21A 5 21 533 3 8 7 8 EAM4X60L24A 5 24 1 2 622 3 8 7 8 EAM4X61L24A 5 24 1 ...

Page 3: ...rapped around the outside of coil casing and supply duct contact point NOTE Consult the furnace installation instructions for any special requirements when installing the coil to the furnace Horizontal Right Left Installation A170281 Vertical Upflow Downflow Installation A170280 Figure 2 Adapter s Installation When Coil Overhangs Furnace Downflow Coil Installation IMPORTANT Installing A coils rota...

Page 4: ... and depth of coil cabinet in the direction of drain pan connection Horizontal Right Installation 1 Use field fabricated attachment plates to secure coil to furnace See Figure 4 2 Use self tapping screws to mount attachment plates to coil casing Self Tapping Screws A13065 Figure 4 Horizontal Right Installation 3 Connect furnace snugly against coil casing 4 Use self tapping screws to attach furnace...

Page 5: ...ing could result in personal injury Wear eye protection Coil is factory charged with 15 psi nitrogen The coil is under pressure and TXV screen is in place behind liquid line plug DO NOT remove liquid line plug first always remove the suction line plug first to depressurize the coil NOTE Factory nitrogen charge may escape past rubber plugs during storage This does not indicate a leaking coil nor wa...

Page 6: ... a factory installed hard shut off TXV designed only for use with R 410A refrigerant Use only with outdoor units designed for R 410A NOTE ALL TXV S HAVE PRESET SUPERHEAT SETTINGS AND ARE FIELD NON ADJUSTABLE UNIT DAMAGE HAZARD Failure to follow this caution may result in product damage DO NOT BURY MORE THAN 36 IN OF REFRIGERANT TUBING IN GROUND If any section of tubing is buried there must be a 6 ...

Page 7: ... off if the water in the secondary pan gets too high Condensate Line Trap Sewer Line Air Gap Above Liquid Level A10216 Figure 11 Condensate Drain to Waste Line WASTE LINE CONNECTION If the condensate line is to be connected to a waste sewer line an open trap must be installed ahead of the waste line to prevent escape of sewer gases See Figure 11 CARE AND MAINTENANCE To continue high performance an...

Reviews: