4

484 01 3905 04

Specifications subject to change without notice.

NOTE

: In downflow installation with a 4

way multipoise

furnace, break off perforated duct flanges on furnace. See
furnace installation instructions.

4"

A170284

Figure 3 

 

Downflow Installation with Coil Rotated 90

5

Horizontal Coil Installation

The unit can be installed on a work platform, secured to roof

truss in attic, suspended from hangers on floor joists in crawl

space, or installed on blocks. It is designed to allow airflow in

either direction, to mate with horizontal

left or horizontal

right

furnace installations. Ensure coil cabinet is level side to side

and front to back. It is allowable to add up to 1/2

in. additional

slope over length and depth of coil cabinet in the direction of

drain pan connection.

Horizontal Right Installation

1. Use field fabricated attachment plates to secure coil to

furnace. (See 

Figure 4

)

2. Use self

tapping screws to mount attachment plates to

coil casing.

Self-Tapping Screws

A13065

Figure 4 

 

Horizontal Right Installation

3. Connect furnace snugly against coil casing.
4. Use self

tapping screws to attach furnace. (See

Figure 5

)

5. Seal joint between coil casing and furnace to create an

air tight seal using locally approved materials.

6. Use cork tape to create air seal between the undersides

of the pan extension and front of the vertical drain pan as

shown in 

Figure 6

.

7. Install included condensate pan extension and two

corner screws as shown in 

Figure 7

.

8. If coil is wider than furnace, use 4

in minimum transition

and self tapping screws to attach furnace. (See 

Figure 2

)

A13063

Figure 5 

 

Horizontal Right Installation

Summary of Contents for EAM4X Series

Page 1: ...personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and pro...

Page 2: ... EAM4X36L21A 3 21 533 3 8 3 4 EAM4X37L17A 3 17 1 2 445 3 8 3 4 EAM4X37L21A 3 21 533 3 8 7 8 EAM4X42L21A 3 1 2 21 533 3 8 7 8 EAM4X42L24A 3 1 2 24 1 2 622 3 8 7 8 EAM4X43L21A 3 1 2 21 533 3 8 7 8 EAM4X48L17A 4 17 1 2 445 3 8 7 8 EAM4X48L21A 4 21 533 3 8 7 8 EAM4X48L24A 4 24 1 2 622 3 8 7 8 EAM4X60L21A 5 21 533 3 8 7 8 EAM4X61L21A 5 21 533 3 8 7 8 EAM4X60L24A 5 24 1 2 622 3 8 7 8 EAM4X61L24A 5 24 1 ...

Page 3: ...rapped around the outside of coil casing and supply duct contact point NOTE Consult the furnace installation instructions for any special requirements when installing the coil to the furnace Horizontal Right Left Installation A170281 Vertical Upflow Downflow Installation A170280 Figure 2 Adapter s Installation When Coil Overhangs Furnace Downflow Coil Installation IMPORTANT Installing A coils rota...

Page 4: ... and depth of coil cabinet in the direction of drain pan connection Horizontal Right Installation 1 Use field fabricated attachment plates to secure coil to furnace See Figure 4 2 Use self tapping screws to mount attachment plates to coil casing Self Tapping Screws A13065 Figure 4 Horizontal Right Installation 3 Connect furnace snugly against coil casing 4 Use self tapping screws to attach furnace...

Page 5: ...ing could result in personal injury Wear eye protection Coil is factory charged with 15 psi nitrogen The coil is under pressure and TXV screen is in place behind liquid line plug DO NOT remove liquid line plug first always remove the suction line plug first to depressurize the coil NOTE Factory nitrogen charge may escape past rubber plugs during storage This does not indicate a leaking coil nor wa...

Page 6: ... a factory installed hard shut off TXV designed only for use with R 410A refrigerant Use only with outdoor units designed for R 410A NOTE ALL TXV S HAVE PRESET SUPERHEAT SETTINGS AND ARE FIELD NON ADJUSTABLE UNIT DAMAGE HAZARD Failure to follow this caution may result in product damage DO NOT BURY MORE THAN 36 IN OF REFRIGERANT TUBING IN GROUND If any section of tubing is buried there must be a 6 ...

Page 7: ... off if the water in the secondary pan gets too high Condensate Line Trap Sewer Line Air Gap Above Liquid Level A10216 Figure 11 Condensate Drain to Waste Line WASTE LINE CONNECTION If the condensate line is to be connected to a waste sewer line an open trap must be installed ahead of the waste line to prevent escape of sewer gases See Figure 11 CARE AND MAINTENANCE To continue high performance an...

Reviews: