F97CMN and G97CMN: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
22
(SW1-5 and SW4-3 set to OFF, except as indicated. See notes 1 and 2.)
Unit Size: 0802120
Clg/CF Switch settings
External Static Pressure (ESP)
Clg Switches
SW2-3 SW2-2 SW2-1
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
Clg Default:
OFF
OFF
OFF
1745
1755
1755
1760
1755
1750
1745
1725
1705
1685
CF Switches
SW3-3 SW3-2 SW3-1
Low-Clg Default:
OFF
OFF
OFF
700
710
750
725
750
See note 4
Cooling Airflow
(SW2)
Low-Cooling
Airflow (SW3)
OFF
OFF
ON
700
710
750
725
750
See note 4
OFF
ON
OFF
830
860
870
890
960
See note 4
OFF
ON
ON
1045
1045
1060
1070
1070
1070
1095
1090
1080
1070
ON
OFF
OFF
1215
1220
1245
1240
1235
1235
1225
1220
1235
1235
ON
OFF
ON
1370
1370
1390
1390
1400
1395
1400
1390
1390
1385
ON
ON
OFF
1745
1755
1755
1760
1755
1750
1745
1725
1705
1685
ON
ON
ON
1745
1755
1755
1760
1755
1750
1745
1725
1705
1685
Maximum Clg Airflow
2
1920
1920
1945
1945
1945
1960
1950
1940
1915
1900
CF Switches
SW3-3 SW3-2 SW3-1
Cont. Fan Default:
OFF
OFF
OFF
700
710
750
725
750
See note 4
Continuous Fan
Airflow (SW3)
OFF
OFF
ON
700
710
750
725
750
See note 4
OFF
ON
OFF
830
860
870
890
960
See note 4
OFF
ON
ON
1045
1045
1060
1070
1070
1070
1095
1090
1080
1070
ON
OFF
OFF
1215
1220
1245
1240
1235
1235
1225
1220
1235
1235
ON
OFF
ON
1370
1370
1390
1390
1400
1395
1400
1390
1390
1385
ON
ON
OFF
1370
1370
1390
1390
1400
1395
1400
1390
1390
1385
ON
ON
ON
1370
1370
1390
1390
1400
1395
1400
1390
1390
1385
Heating (SW1)
Maximum Heat Airflow
3
1340
1355
1370
1385
1380
1385
1400
1400
1385
1380
Intermediate Heat Airflow
3
780
810
835
840
845
See note 4
Minimum Heat Airflow
3
595
595
600
595
605
See note 4
Unit Size: 1002122
Clg/CF Switch settings
External Static Pressure (ESP)
Clg Switches
SW2-3 SW2-2 SW2-1
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
Clg Default:
OFF
OFF
OFF
1820
1825
1840
1845
1840
1835
1825
1805
1780
1770
CF Switches
SW3-3 SW3-2 SW3-1
Low-Clg Default:
OFF
OFF
OFF
750
740
745
730
715
See note 4
Cooling Airflow
(SW2)
Low-Cooling
Airflow (SW3)
OFF
OFF
ON
750
740
745
730
715
See note 4
OFF
ON
OFF
900
900
915
910
905
See note 4
OFF
ON
ON
1070
1075
1095
1095
1090
1085
1095
1080
1065
1070
ON
OFF
OFF
1280
1285
1305
1305
1310
1305
1295
1300
1290
1285
ON
OFF
ON
1440
1445
1465
1465
1470
1485
1480
1485
1475
1460
ON
ON
OFF
1820
1825
1840
1845
1840
1835
1825
1805
1780
1770
ON
ON
ON
2135
2140
2140
2135
2140
2130
2115
2100
2070
2015
Maximum Clg Airflow
2
2160
2165
2175
2170
2160
2150
2135
2120
2065
2020
CF Switches
SW3-3 SW3-2 SW3-1
Cont. Fan Default:
OFF
OFF
OFF
750
740
745
730
715
See note 4
Continuous Fan
Airflow (SW3)
OFF
OFF
ON
750
740
745
730
715
See note 4
OFF
ON
OFF
900
900
915
910
905
See note 4
OFF
ON
ON
1070
1075
1095
1095
1090
1085
1095
1080
1065
1070
ON
OFF
OFF
1280
1285
1305
1305
1310
1305
1295
1300
1290
1285
ON
OFF
ON
1440
1445
1465
1465
1470
1485
1480
1485
1475
1460
ON
ON
OFF
1440
1445
1465
1465
1470
1485
1480
1485
1475
1460
ON
ON
ON
1440
1445
1465
1465
1470
1485
1480
1485
1475
1460
Heating (SW1)
Maximum Heat Airflow
3
1570
1575
1595
1595
1600
1605
1600
1600
1590
1575
Intermediate Heat Airflow
3
950
955
965
975
970
See note 4
Minimum Heat Airflow
3
755
745
750
735
720
See note 4
Table 7 – Cooling
4
and Heating Air Delivery - CFM (Bottom Return
5
With Filter) (Continued)