OPA 1370RKTMG01-PZ  

(Digital c/w Plug fan and Economiser)

Packaged Reverse Cycle R410A

Air Cooled Air Conditioner

GENERAL

This OPA 1370RKTMG Outdoor Unit must 

be installed in accordance with all national 

and local safety codes.

OPTION

1. TZT-100 Room Temperature Controller 

(field fitted).

2. Viking Controller for Economiser with 

enthalpy control (factory fitted).

REFRIGERATION SYSTEM

General

The OPA 1370 has four independent 

refrigeration circuits and four compressors 

to provide the flexibility and economy of 

four stage operation, i.e. utilising one to 

four circuits as conditions vary, plus the 

advantage of staggered starting.
Each refrigeration system has been 

charged with HFC-410A (R410A) 

refrigerant; refer wiring diagram 

specification table for amount. Tapping 

points are provided to measure discharge 

and suction operating pressures.  

Compressors

The compressors are directional scroll 

type. One of the four compressors is digital 

scroll type. This has a variable capacity 

ability that enables closer control of room 

temperature. 
The compressor lubricant is polyol ester 

oil (POE). Note, this oil absorbs moisture 

quickly if exposed to open air. On 

commissioning, the compressors must be 

checked for correct rotation (refer Start 

Up Procedure). A time delay prevents 

simultaneous starting of the compressors.

ECONOMISER

The economiser fresh air intake cowl with 

water separator is supplied separately and 

is best fitted after the OPA is mounted on 

it's platform. Fitting instructions are supplied 

with the cowl. 
Controls may be supplied by others. If the 

outdoor air temperature or heat content 

preferably, is below that of the return air 

the fresh air damper opens and the return 

air damper closes to provide the first stage 

of cooling. A spill air facility in the building 

may be necessary for when the return air 

damper is closed. The fresh air damper 

should return to minimum setting and the 

return air damper open before compressors 

are allowed to operate to provide further 

cooling.  

INSTALLATION
Positioning

Refer to dimension diagrams for minimum 

clearances. If multiple units are to be 

placed side-by-side then allow at least 2 m 

between coil faces.

Installation & 

Maintenance

Mounting

The unit should be fastened to a firm flat 

horizontal base using the holes supplied in 

the mounting channels.
When the unit is being installed on a roof 

it is recommended that the unit is installed 

on a substantial structure with anti-vibration 

mounts or pads.
Flexible duct connections are recommended 

between the supply and return ducts and 

the unit.

Condensate Drain

The condensate drain should be 'U' trapped 

outside the unit. The trap should have a 

vertical height of at least 100 mm. The drain 

should have a slope of at least 1 in 50 and 

must not be piped to a level above the unit 

drain pipe.

Electrical Requirements

Electrical work must be done by a qualified 

electrician.  The outdoor unit must be wired 

directly from a distribution board by means 

of a circuit breaker or H.R.C. fuse, and a 

mains isolator provided - preferably close to 

the unit.

Note

:  DO NOT USE REWIRABLE FUSES.

The OPA 1370 is provided with a 24V AC 

control circuit for a thermostat, on/off switch 

and/or time clock.
Standard units are suitable for use with 

thermostats with either manual Heat/Cool 

selection or automatic changeover subject to 

the contact ratings of the thermostats. 
The system is set up for the compressors to 

be controlled variably by:

1.  TZT-100 Controller (via RS485 modbus),

2.  0-10V dc command via BMS modbus, or

3.  0-10V dc command via a client supplied 

external controller. 

If option 1 is chosen, then disconnect or 

remove the Signal Input for Controller 0-10V.
If a TZT-100 Controller is used then variable 

capacity control is automatically included 

and no additional wiring is required.
A 24 hour power supply to the control circuit 

is required, otherwise the warranty is void.

SETTING SUPPLY AIR FLOW

Consult OPA 1370 Technical Data pamphlet 

at www.temperzone.biz for details of airflow/

duct static pressure, if required. 

If the indoor air returning to the unit is 

regularly expected to be above 50%RH, 

then the coil face velocity should be limited 

to be 2.5 m/s or less (refer Air Handling 

graph in Technical Data pamphlet). 
High humidity levels can occur in tropical or 

subtropical conditions, and/or when heavily 

moisture laden fresh air is introduced. 

Select a fan speed that avoids water carry-

over problems.

INDOOR FAN SPEED

The fan speed is continuously variable 

via the 0-10V DC  control signal applied 

between terminals 'FAN GND' and '0–10V'.
Once the maximum design air flow has 

been set, a variable fan speed can be 

controlled as follows by applying an external 

variable 0–10V DC control voltage to 

'0–10V' terminal. Connect 0V reference to 

'FAN GND'.

CHECK TESTS

1.  Check that all the shipping bolts on the 

back of the compressor frame have been 

removed and that the compressor is 

secure on its mounts.

2.  Check by hand that all fan motors can 

turn freely. 

3.  Check that the air filters have been 

correctly installed, if fitted.

4.  Check air diffuser dampers are open if 

appropriate.

5.  Check that the thermostat, or external 

24V controller, is correctly wired to 

the unit and is set at the desired 

temperature.

6.  Check the tightness of all electrical 

connections.

7.  Leave the thermostat, or external 24V 

controller, in the off position and close 

the mains isolating switch. (A four hour 

delay period is required to allow the 

crankcase heater to drive any liquid 

refrigerant out of the compressor oil.)

8.  Check the supply voltage between each 

phase and neutral.

START UP PROCEDURE

After the four hour delay for the crankcase 

heater has expired, use the supplied 

Commissioning Sheet (Form NS 228) to 

record results when completing the following 

‘Start-up’ procedure. A UC6 Service 

Interface tool is supplied to read, pressures, 

superheat and its set-point, compressor 

amps etc.

1.  Select a sensible Fan speed (or Auto 

Fan mode), operating cycle (cool or 

heat), and room temperature set point, 

depending on the time of year, such that 

the compressor will start and run at a 

high capacity.

2.  Turn ON the thermostat / external 

controller. Wait for the compressor to 

OPEN

DRAIN

MINIMUM

SLOPE

20 mm PER m

(1 IN 50)

100 mm

MINIMUM

200 mm

APPROX.

'U' TRAP

100 mm

APPROX.

VENT PIPE

FOR LONG

CONDENSATE

DRAIN RUNS

Summary of Contents for OPA 1370RKTMG01-PZ

Page 1: ...se to the unit Note DO NOT USE REWIRABLE FUSES The OPA 1370 is provided with a 24V AC control circuit for a thermostat on off switch and or time clock Standard units are suitable for use with thermostats with either manual Heat Cool selection or automatic changeover subject to the contact ratings of the thermostats The system is set up for the compressors to be controlled variably by 1 TZT 100 Con...

Page 2: ...in temperzone units including in this particular unit variation of compressor speed The particular method used varies from model to model but is handled by the Unit Controller In combination these features deliver optimised performance across a wide operating temperature range Refer to UC6 Controller label on the unit for operation fault diagnostics information Many operating status conditions can...

Page 3: ...MC4 RV3 RV4 CMC4 CMC3 BB2 N CCH3 CCH4 CR1 CR2 CR3 CR4 HR1 HR2 N 8 C N 2 D O 8 D O 2 D S 8 D P 2 F P 8 E U 8 F Q 2 F Q 8 F U 3 F T 8 E T 3 F R 8 C R 3 D S 3 D C12ER C34ER TB17 DMR DMF COM HOT E TB16 DMR DMF COM HOT E CBL8 CBL9 CBL10 K 9 E K 5 F J 9 F J 5 F F 9 C F 5 D G 9 D G 5 D CBL13 CBL13 CBL14 CBL14 Return and Economiser Damper CP2W1 CP2W2 CP2W3 CP2W4 CBL15 CBL15 CBL16 CBL16 V 8 C V 0 C W 8 F W...

Page 4: ...TMG PZ UC6 A K B 27 12 2017 24V D1 10V E1 GND 11 14 IFM 1 CBL20 24V D1 10V E1 GND 11 14 IFM 2 CBL21 24V D1 10V E1 GND 11 14 IFM 3 CBL22 24V D1 10V E1 GND 11 14 IFM 4 CBL23 X 1 5 E TB18 FAULT IF1 FAULT IF2 FAULT NC7 1 TB19 FAULT NC7 2 FAN GND1 FAN GND2 FAN 1 2 E1 FAN 3 4 E1 Y 1 4 E A 1 2 D C 1 2 F B 1 3 D D 1 3 F APPROVED DATE ECN DESCRIPTION REV C 01 02 19 A W G Spec data updated N4188 ...

Page 5: ... S Transducers T Name Type Colour ST1 Suction Temp S BLUE ST2 Suction Temp S BLUE DT1 Discharge Temp S GREY DT2 Discharge Temp S GREY SP1 Suction Pressure T SP2 Suction Pressure T HP1 High Pressure T HP2 High Pressure T TS1 De ice Temp S BLUE TS2 De ice Temp S BLUE OAT Ambient Temp S YELLOW A Ph Compressor 2 3Ph run amps rating conditions 15 A Ph Compressor 3 3Ph run amps rating conditions 15 A Ph...

Reviews: