start. Measure the current for each 

phase feeding into the compressor’s.

Compare against the compressor amps 

specified on the unit’s wiring diagram. 

3. Compressors fitted are directional. Check 

for correct rotation. If rotation is incorrect 

the compressor will not pump, be noisy, 

and will draw minimal current. To correct 

motor rotation, change the phasing at 

the main power terminal. If changing the 

phasing, check the indoor air fan then 

runs in the correct direction also.

4.  Measure the current draw of each fan 

motor. Check all readings against the 

specified values in the wiring diagram.

5.  Use the UC6 Service Interface tool  to 

check operating pressures and status. 

If the UC6 Service Interface is not 

available, fit gauges and measure the 

suction and discharge pressures of both 

refrigeration circuits.

6.  Check that the outdoor air fan motors are 

running smoothly and drawing less than 

the full load amps specified.

7. Check the indoor unit's fan belt tension 

after 20 mins of operation and adjust if 

necessary (refer Commissioning Sheet).

8.  Test the operation of the reversing valve 

by running the unit in both the heating 

and cooling mode.

9.  Check the supply air flow at each outlet.

10. Touch up any outdoor unit paintwork 

damage to prevent corrosion.

OPA 1370RKTMG-PZ

DIMENSIONS (mm)

Not to Scale

OPA 1370RKTMG01-PZ – Horizontal Supply & Return Air

PROJECTION

Note :

  A 2 m clearance 

is required above the 

exhaust air fans

UNIT CONTROLLER (UC6)   

The Unit Controller provides system 

protection functions such as coil frost 

protection, de-icing, high head pressure 

and low suction pressure cut-out.  It 

also protects against rapid cycling of the 

compressor and loss of refrigerant. The UC 

regulates the superheat of the refrigeration 

system by controlling the position of an 

Electronic Expansion Valve (EEV). Various 

methods of head pressure control (or 

limiting) are employed in temperzone units 

including in this particular unit, variation 

of compressor speed. The particular 

method used varies from model to model, 

but is handled by the Unit Controller. 

In combination, these features deliver 

optimised performance across a wide 

operating temperature range.
Refer to UC6 Controller label on the unit for  

operation & fault diagnostics information. 

Many operating status conditions can be 

determined, without gauges, simply by using 

the UC6 Service Interface graphical display 

supplied with the unit

.

MAINTENANCE

Monthly

1. Check air filters, if fitted, and vacuum or 

wash clean as necessary.

2. Check condensate drain for free 

drainage.

3. Check compressor compartment for oil 

stains indicating refrigerant leaks.

Six Monthly

1. Check the tightness of electrical 

connections. 

2. Check the tightness of all fans and motor 

mountings.

3. Check suction and discharge operating 

pressures. (Using the UC6 Service 

Interface avoids fitting and removing 

gauges with consequential refrigerant loss.)

5. Check condensate drain for free drainage.

Yearly

1. Check all refrigerant piping for chafing 

and vibration.

2. Check the operation of electric heaters, 

if fitted.

3. Check air supply at all diffusers.

4. Check for excessive noise and vibration 

and correct as necessary.

5. Check for insulation and duct damage 

and repair as necessary.

6. Remove lint and dust accumulation from 

outdoor coil fins.

7. Touch up any paintwork damage to 

prevent corrosion.

NOTE

The manufacturer reserves the right to 

make changes in specifications at any time 

without notice or obligation. Certified data is 

available on request.

SUPPLY

AIR

RETURN

AIR

250

2320

OVERALL

1000 MIN. CLEARANCE

1000 MIN. CLEARANCE

DRAIN

1

1

/

2

" BSP

MALE

1000 MIN. CLEARANCE

2430 OA

FAN

ACCESS

DOOR

2260

MOUNTING

CENTRES

4668 OA

2150 CENTRES

184

2150 CENTRES

184

1710

380

617

617

225

FILTER

ACCESS PANEL

ECONOMISER

WEATHER

HOOD

2000 MIN. CLEARANCE

100

ELECTRICAL

ACCESS

DOOR

ELECTRICAL

ACCESS

DOOR

OUTDOOR

AIR FLOW

OUTDOOR

AIR FLOW

U

V

W

Z

Y

X

690

230

Net Weight 2297 kg

POINT LOADS (kg)

 

U  V  W  X  Y  Z

 430  347  262  406  419  433

Summary of Contents for OPA 1370RKTMG01-PZ

Page 1: ...se to the unit Note DO NOT USE REWIRABLE FUSES The OPA 1370 is provided with a 24V AC control circuit for a thermostat on off switch and or time clock Standard units are suitable for use with thermostats with either manual Heat Cool selection or automatic changeover subject to the contact ratings of the thermostats The system is set up for the compressors to be controlled variably by 1 TZT 100 Con...

Page 2: ...in temperzone units including in this particular unit variation of compressor speed The particular method used varies from model to model but is handled by the Unit Controller In combination these features deliver optimised performance across a wide operating temperature range Refer to UC6 Controller label on the unit for operation fault diagnostics information Many operating status conditions can...

Page 3: ...MC4 RV3 RV4 CMC4 CMC3 BB2 N CCH3 CCH4 CR1 CR2 CR3 CR4 HR1 HR2 N 8 C N 2 D O 8 D O 2 D S 8 D P 2 F P 8 E U 8 F Q 2 F Q 8 F U 3 F T 8 E T 3 F R 8 C R 3 D S 3 D C12ER C34ER TB17 DMR DMF COM HOT E TB16 DMR DMF COM HOT E CBL8 CBL9 CBL10 K 9 E K 5 F J 9 F J 5 F F 9 C F 5 D G 9 D G 5 D CBL13 CBL13 CBL14 CBL14 Return and Economiser Damper CP2W1 CP2W2 CP2W3 CP2W4 CBL15 CBL15 CBL16 CBL16 V 8 C V 0 C W 8 F W...

Page 4: ...TMG PZ UC6 A K B 27 12 2017 24V D1 10V E1 GND 11 14 IFM 1 CBL20 24V D1 10V E1 GND 11 14 IFM 2 CBL21 24V D1 10V E1 GND 11 14 IFM 3 CBL22 24V D1 10V E1 GND 11 14 IFM 4 CBL23 X 1 5 E TB18 FAULT IF1 FAULT IF2 FAULT NC7 1 TB19 FAULT NC7 2 FAN GND1 FAN GND2 FAN 1 2 E1 FAN 3 4 E1 Y 1 4 E A 1 2 D C 1 2 F B 1 3 D D 1 3 F APPROVED DATE ECN DESCRIPTION REV C 01 02 19 A W G Spec data updated N4188 ...

Page 5: ... S Transducers T Name Type Colour ST1 Suction Temp S BLUE ST2 Suction Temp S BLUE DT1 Discharge Temp S GREY DT2 Discharge Temp S GREY SP1 Suction Pressure T SP2 Suction Pressure T HP1 High Pressure T HP2 High Pressure T TS1 De ice Temp S BLUE TS2 De ice Temp S BLUE OAT Ambient Temp S YELLOW A Ph Compressor 2 3Ph run amps rating conditions 15 A Ph Compressor 3 3Ph run amps rating conditions 15 A Ph...

Reviews: