3–5 Configuring User Menu

Most conventional controllers are designed with a fixed order in

which the parameters scroll. The x100 series have the flexibility

to allow you to select those parameters which are most significant

to you and put these parameters at the front of the display se-

quence.

SEL1~SEL8:

Selects the parameter for view and change in the

user menu.

Range: LOCK, INPT, UNIT, DP, SHIF, PB, TI, TD, O1HY,

CYC1, OFST, RR, O2HY, CYC2, CPB, DB, ADDR, ALHY

When using the up and down keys to select the parameters, you

may not see all of the above parameters. The number of visible pa-

rameters is dependent on the setup condition. The hidden param-

eters for the specific application are also blocked from the SEL

selection.

Example:

  OUT2 set for DE.LO     PB= 100.0              SEL1 set for INPT

  SEL2 set for UNIT        SEL3 set for PB     SEL4 set for TI

  SEL5~SEL8 set for NONE

  

Now, the upper display scrolling becomes:

3–6 Ramp

Ramp

The ramping function is performed during power up as well as any

time the set point is changed. If MINR or HRR is chosen for

RAMP, the unit will perform the ramping function. The ramp rate

is programmed by adjusting RR. The ramping function is disabled

as soon as failure mode, manual control mode, auto-tuning mode

or calibration mode is entered.

Example without dwell timer

Select MINR for RAMP, select °C for UNIT, select 1-DP for DP,

set RR=10.0. SV is set to 200°C initially, and changed to 100°C

30 minutes after power-up. The starting temperature is 30°C. After

power-up, the process runs like the curve shown below:

Note:

When the ramp function is used, the lower display will show

the current ramping value. The ramping value is an artificially de-

termined setpoint created and updated by the control to match the

ramp rate set by the user. However, it will revert to show the set

point value as soon as the up or down key is touched for adjust-

ment. The ramping value is initiated to process value either on

power-up or when RR and/or the set point are changed. Setting

RR to zero means no ramp function.

3–7 Dwell Timer

The alarm output can be configured as a dwell timer by selecting

TIMR for ALFN (alarm function). As the dwell timer is config-

ured, the parameter SP3 is used for dwell time adjustment. The

dwell time is measured in minutes ranging from 0.1 to 4553 min-

utes. Once the process reaches the set point the dwell timer starts

to count down to zero (time out). The timer relay will remain un-

changed until time out. For the dwell timer to control the heater,

the heater circuit (or contactor) must be wired in series with the

alarm relay. Note the following diagram located below and also

Figure 2.20.1 on page 11. When the dwell timer times out, the

heater will be turned off. The dwell timer operation is shown in

the following diagram.

After time out, the dwell timer can be restarted by pressing the

RESET key.

The timer stops counting during manual control mode, failure

mode, the calibration period and the auto-tuning period.

If the alarm is configured as a dwell timer, ALHY and ALMD are

hidden.

Dwell Timer Function Wiring Diagram

Figure 3.6  Dwell Timer Function

Figure 3.5  RAMP Function

Summary of Contents for PCM10005

Page 1: ...48 60amps 11 520 19 930W 14 75H x 8W PCM10008 480VAC 48 60amps 23 000 39 900W 14 75H x 8W There is no disconnect or heater fusing in this enclosure Heater fusing and disconnect must be supplied by the...

Page 2: ...g instructions for the TEC 9100 temperature controller 2 Close and secure the door Switch on the enclosure Using the up down pushbuttons on the TEC 9100 controller start out with the temperature set l...

Page 3: ...Page 3 of 16 1 5 Menu Overview...

Page 4: ...Page 4 of 16 1 6 Parameter Descriptions page 1 of 2 Indicates Controller Parameter Settings that are not applicable...

Page 5: ...Page 5 of 16 Parameter Descriptions page 2 of 2...

Page 6: ...Page 6 of 16 Alarm Wiring...

Page 7: ...s selected for LOCK then all setup data as well as user data refer to section 1 5 except the set point are locked to prevent them from being changed If ALL is selected for LOCK then all parameters are...

Page 8: ...quick response to the process if it is properly tuned Control Outputs continued Heat only ON OFF control Select REVR for OUT1 Set PB proportional band to 0 O1HY is used to adjust dead band for ON OFF...

Page 9: ...The two trigger levels are SV SP3 and SV SP3 for alarm When the process is higher than SV SP3 or lower than SV SP3 a deviation band high alarm DB HI occurs When the process is within the trigger leve...

Page 10: ...ature is 30 C After power up the process runs like the curve shown below Note When the ramp function is used the lower display will show the current ramping value The ramping value is an artificially...

Page 11: ...used for control may produce an unstable process The controller will enter failure mode if one of the following conditions occurs 1 SBER occurs due to input sensor break or input current below 1mA if...

Page 12: ...on as either failure mode or manual control mode is entered Procedures Auto tuning can be applied either as the process is warming up cold start or when the process has been in a steady state warm sta...

Page 13: ...ower display will show The controller is now in manual control mode indicates output control variable for out put 1 and indicates control variable for output 2 Now you can use the up and down keys to...

Page 14: ...Page 14 of 16 Table A 1 Error Codes and Corrective Actions...

Page 15: ...fect com pliance with any applicable specification TEC Temperature Con trollers are warranted to be free from defects in material and workmanship for two 2 years after delivery to the first purchaser...

Page 16: ...es of our Diverse and Innovative Products Copyright 2015 All Rights Reserved Electric Heating Elements Thermocouples and RTD Assemblies SCR Power Controls Solid State Relays Mechanical Relays Videogra...

Reviews: