Attention! Do NOT connect the connector of the antenna directly or
indirectly to the protective ground, because this may damage the device!
-> Chapter 3.5 of the Installation and Application Manual.
DEVICE WIRING:
The
Gate Control PRO
has four inputs and two outputs, which can be configured
in the programming software for the task at hand.
Inputs:
The
NO
or
NC
dry contacts should be connected between the selected input and
the
V-
supply voltage negative terminal.
Inputs
IN1
and
IN2
can also be used as
Doorbell
,
Technical error
, or
Gate
opener
inputs. The wiring should be done accordingly for these functions
to work.
Outputs and control modes:
The outputs provide normally open
(NO)
dry contacts as the default state,
and closed contacts when controlled, except for control mode No. 3, where
output OUT2 is normally closed
(NC).
They can take a load of
1A
@24V AC/DC.
The device supports five different output control modes, each of them
controllable via phone call or through the mobile application. Choose the control
mode appropriate for your gate automation.
Control mode 1:
- For one or two gates, or one
gate with two opening options
(partial/ total opening).
- Both outputs are normally
open (NO).
- OUT1 is controlled by call with
caller identification.
- OUT2 is controlled by calls
from private (hidden) number.
- You can control both outputs
separately with the mobile
app.
- Gate position limit switches
can be connected to inputs
IN3 (for gate No. 1) and IN4
(for gate No. 2).