TG-7 Cellular Series Installation & Operating Guide
4
56053501 Rev A © 2022 Telguard
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, OTHER INVOLVED PARTIES
FIRE SYSTEM INSTALLATIONS IN CANADA: This product incorporates field-programmable software. In
order to comply with the requirements in the Standard for Equipment for Fire Signal Receiving Centres and
Systems, ULC-S559, certain programming features or options must be limited to specific values or not used
at all as indicated below.
Program feature or option
Permitted in
ULC-S559
(Y/N)
Possible settings
Settings permitted in
ULC-S559
Link Supervision
Y
Disabled, 180 seconds
180 seconds
End-to-End Acknowledgment
Y
Disabled, Enabled
Enabled
No Service Condition (NSC)
delay
Y
30 seconds, 60 seconds,
3-, 5- 10-, 20-, 30-, 45-,
60-, 1440- minutes
No more than 60 seconds
AC Failure Condition (ACFC)/
Low Power Failure (LPF)
Y
Disabled, any number of
hours up to 24
1 hour, 2 hours, 3 hours