Telguard TG-7 Series 

QUICK INSTALLATION GUIDE [SOLE PATH] 

Installation Summary 

There are seven steps in installing Telguard properly.  

IF YOU DO NOT 

PROCEED IN THE ORDER AND MANNER PRESCRIBED, YOU MAY NOT 
COMPLETE THE INSTALLATION IN THE TIME ALLOCATED.

   

S

TEP 

1:

 

R

EGISTER FOR 

C

ELLULAR 

S

ERVICE

 

Register the unit online through 

www.telguardonline.com

, by completing the 

Online Registration Form at 

www.Telguard.com

.  Telular requires this information 

to register and activate the unit. 

S

TEP 

2:

 

L

OCATE 

U

NIT AND 

M

EASURE 

S

IGNAL 

S

TRENGTH 

(RSSI) 

First, you will be confirming that Telguard has adequate cellular signal strength. Press the LED/RSSI 
Mode Toggle button one time, LEDs will now indicate signal strength. Minimum recommended is 3 (3 
on solid). Press the LED/RSSI Mode Toggle button a second time to exit RSSI mode.  

S

TEP 

3:

 

C

ONFIGURE 

A

LARM 

P

ANEL FOR 

S

OLE 

P

ATH 

C

ONNECTION

 

Fire panels are typically provided with two Telco connections. Because the TG-7 provides a single 
connection, the panel must be set up accordingly. The first method of installation is to configure the 
panel to disable the second Telco connection.  If this is not an option due to panel limitations, it is 
possible to splice both TIP and RING connections from the panel into the single jack of the 
Telguard.  The TG-7 is capable of providing dial tone to both Telco connections. 

S

TEP 

4:

 

P

ROGRAM

,

 

A

CTIVATE 

&

 

T

RANSMIT 

P

ANEL 

A

LARMS OVER THE 

C

ELLULAR 

R

ADIO 

N

ETWORK 

 

Program the TG-7 for Sole Path communication. You may do this by setting Memory Location 831 
to a value of 3, using a butt-set. (See programming guide on reverse).  LED 3 will be off when idle, 
if successful. Next, connect the alarm panel's digital dialer output to Telguard and verify that alarm 
signals can be reliably sent through Telguard over cellular to the central station digital receiver.  A 
minimum of two alarm signals must be transmitted.

 

Activation is confirmed when LED 1 is 

illuminated. 

(NOTE:

 THE FIRST ALARM WILL ACTIVATE THE UNIT AT THE 

T

ELULAR 

C

OMMUNICATION 

C

ENTER

,

 IT WILL NOT GO TO THE 

C

ENTRAL 

S

TATION

,

 ALL SIGNALS AFTER THE FIRST ARE 

SENT TO THE 

C

ENTRAL 

S

TATION

S

TEP 

5:

 

C

ONNECT 

S

UPERVISORY 

T

RIP 

O

UTPUTS

 

Next, you will wire Telguard's supervisory trip outputs to the alarm panel and then test. 

S

TEP 

6:

 

C

ONNECT 

T

RIP 

I

NPUT 

(

OPTIONAL

Optionally, you can wire an external relay input to the trip input lead and ground, and test. 

S

TEP 

7:

 

C

OMPLETE THE 

I

NSTALLATION

 

Your last step will be to attach earth ground, and permanently mount the unit. 