IRIS/SIMPO Repeater TFT - Addressable Fire Alarm Repeater Panel
– Installation & Programming Manual
21
4.3.3.2. Colors Review
This is a menu for reviewing the color palette of the screen. Enter COLORS submenu to check the number and type of
the supported colors.
Press the screen anywhere to return to DISPLAY menu.
4.3.3.3. Setting the Screen Backlight
ATTENTION: “Power Safe Backlight” must be disabled for conformity with EN54-2 standard!
This is an option for switching off the backlight of the screen after 60 sec in case the TFT display is not used.
By default, the Power Safe Backlight option is Enabled.
Enter SYSTEM
– MAINTENANCE - POWER SAFE BACKLIGHT menu.
Every pressing of the button will change the state
Enabled/Disabled.
Confirm the new setting pressing the APPLY button on
the top of the screen. To reject press EXIT button and
return to DISPLAY menu.
4.3.4. Software Revision and Firmware Update
This is a menu for reviewing the current set software of the main CPU and the firmware revision of the panel.
To review the software version or the Repeater, enter SYSTEM - MAINTENANCE - SOFTWARE REVISION menu.
The screen displays the current set software revision of
the Repeater panel. Press EXIT button to return back to
Maintenance menus.