3.2 Installation
3.2.1 Programming of the device address
Burn the address of the horn/strobe horn to the device's card. Use the wire supplied with
the software
PROG-4000 or the technician kit TFC-7000 and connect the gator clips to
lug 1 (positive) and 2 (negative).
i
Note
Burning an address to the base sets the address of the horn/strobe horn only.
The detector installed on the base uses its own address and the setting of the
device on the panel.
3.2.2 Device settings on the panel
Set the assembly on the panel to "Silenced Horn". When this option is selected, the horn
will be off.
On the
TFB-180BSA, setting the panel to Silenced Horns will disable the horn, but the
strobe light will continue to be on, until Respond is pressed in the panel.
Set the operating matrix of the device in the panel. Read the technical instructions of the
panel for additional instructions about setting the devices and operating matrix.
3.2.3 Configuration switches
–
TFB-180BA
i
Note
The switch is set to 1 when the selector is close to 1, and to 0 when the
switch is away from 1 (OPEN state).
Switch
3
Switch
2
Switch
3
Sound
1
1
1
Constant -
910Hz
1
1
0
Goes up from 500Hz to 1,200Hz for 3.5 sec; stops for
0.5 seconds
1
0
1
Switches between 910Hz and 685Hz at a rate of 2Hz
1
0
0
Intermittent sound, half a second at 910Hz, half a
second off
0
1
1
Goes down from 1,200Hz to 500Hz every second
0
1
0
Sounds three pulses of 500mS at
910Hz and then
goes off for 1.5 seconds
0
0
1
Goes up and down every 0.5 second in the range of
800Hz
– 1,000Hz
0
0
0
Goes up from 800Hz to 970Hz every second