Telefire TFB-180BSA Technical Instructions Download Page 4

 

 2019  – 2020 ©  

A

LL RIGHTS RESERVED TO 

T

ELEFIRE 

G

AS AND 

F

IRE DETECTORS 

L

TD

.

  

  Rev  1.01   Date  4.2.2020 

        Page 

2  of 7   

Cable type 

 

Maximum cable length (for a given size) as input 

to:

 

Cable 

(AWG)  

Diameter 

(mm) 

Section 

(mm

2

ADR-7000

  ,SAVER-7000  ,GUARD-7 ו ,

- ADR-3000 

19 

0.912 

0.653 

710 

18 

1.024 

0.823 

900 

17 

1.15 

1.04 

1,125 

16 

1.291 

1.31 

1,425 

15 

1.45 

1.65 

1,800 

14 

1.628 

2.08 

2,275 

13 

1.828 

2.62 

2,875 

12 

2.053 

3.31 

3,625 

Table 1: selection of communication loop cables for addressable devices (SLC)  

Note 

    

IS 1220 part 3 (2014) states in section 12.1.4 that "When using cables that 
are composed of two strands and up, the section area of each conductor in 
the cable strand will be 0.5 mm

2

, as a minimum". 

The cable lengths stated in table 1 are brought as an estimate, assuming the 
cables are single-stranded. 

In any case, the cable resistance, as measured in the field, has to be taken 
into account.  

In communication lines for addressable devices (SLC), the loop resistance 
and capacitance 

– the stricter of the two, has to be considered. The 

capacitance of the SLC loop will not exceed 1 

μF . 

 

3.1.3 

Wiring planning 

– 24VDC supply  

The assembly is fed by +24Vdc supply from the panel or local addressable power 
supply, like TPS-74A or TPS-34A

. The resistance of the power supply line between the 

power source 24Vdc and an addressable assembly will be calculated such that the 
maximum voltage drop at the end of line, under full load, will not exceed 2V, or a 
voltage level that supplies the last device with the minimum operating voltage, 
according to the manufacturer's data 

– the stricter of the two. 

Use TPS-74A or TPS-34A

 when the assembly is installed far from the panel, or when 

the sum of consumer currents in regular operating mode or in alarm state exceeds the 
maximum permissible current on the main power supply (the panel).   

 

Summary of Contents for TFB-180BSA

Page 1: ...d with a addressable horn strobe horn Technical instructions TELEFIRE GAS AND FIRE DETECTORS LTD P O Box 7036 Petach Tikwa 49250 Tel 03 970 0400 Fax 03 921 1816 Email info telefire com www telefire co...

Page 2: ...i Note The equipment must not be installed operated or maintained before reading this manual and understanding its content 2020 2019 ALL RIGHTS RESERVED TO TELEFIRE GAS AND FIRE DETECTORS LTD...

Page 3: ...the following panels ADR 7000 SAVER 7000 GUARD 7 ADR 3000 ADR SAVER 2 2 Detectors The addressable strobe horn and horn serve as a basis for the following detectors TFO 480A TFH 280A TPH 482A 3 Install...

Page 4: ...he cable resistance as measured in the field has to be taken into account In communication lines for addressable devices SLC the loop resistance and capacitance the stricter of the two has to be consi...

Page 5: ...to the grounding by the grounding clamps on the panel 3 1 5 Location The device has to be installed indoors Exposure to outdoor and weather conditions must be prevented to avoid high humidity or dust...

Page 6: ...Horns will disable the horn but the strobe light will continue to be on until Respond is pressed in the panel Set the operating matrix of the device in the panel Read the technical instructions of th...

Page 7: ...TO TELEFIRE GAS AND FIRE DETECTORS LTD Rev 1 01 Date 4 2 2020 Page 5 of 7 3 2 4 Configuration switches TFB 180BSA i Note The switch is off when the selector is close to the digit and on when the swit...

Page 8: ...vice to the communication line of addressable devices and 24Vdc input i Note Measure the wiring to ensure there is no short circuit or connection or leakage to the ground before connecting the device...

Page 9: ...ation panel or addressable output assembly 24 Vdc 4 1 TFB 180SA Maximum current consumption device line 180 A quiescent state 2 mA alarm state Maximum current consumption from 24Vdc power source 10 mA...

Reviews: