3  of 7   

Note  

24V lines that feed several loops will be split only on the panel output. It is 
forbidden to connect in the field 24V lines to different loops. 

TPS-74A or TPS-34A

 power supply will feed  24V to devices that belong to 

one loop only. It is forbidden to bridge 24V between devices in the field that 
belong to different loops.  

 

 

 

3.1.4  Wiring planning 

– shielding  

It is recommended not to conduct wiring outside of a building, because of the potential 
risk of lightning strike. If necessary, shielded cables must be used. The shield must be 
connected to the grounding by the grounding clamps on the panel.   

3.1.5  Location  

The device has to be installed indoors. Exposure to outdoor and weather conditions 
must be prevented to avoid high humidity or dust and air contamination from external 
sources. 

3.1.6  Connection of 24V power input and communication line to addressable 

devices  

Connect to the assembly the communication line for addressable devices (SLC) from 
the panel, and 24VDC input from the panel or external power source, like TPS-74A or 
TPS-34A

 . 

Note 

    

Check the wiring before making the connection, to ensure that is no short-
circuit in the wires. 

The addition or removal of assemblies from the panel will be done when the 
power sources to the panel (AC input voltage and batteries) are 
disconnected.  

 

 

 

 

 

 

 

 

 

 

 

 

 

Drawing 1: wiring of TFB-180BSA or 

 TFB-180SA 

To the next device

 

From the panel or 
previous device 

 

Summary of Contents for TFB-180BSA

Page 1: ...d with a addressable horn strobe horn Technical instructions TELEFIRE GAS AND FIRE DETECTORS LTD P O Box 7036 Petach Tikwa 49250 Tel 03 970 0400 Fax 03 921 1816 Email info telefire com www telefire co...

Page 2: ...i Note The equipment must not be installed operated or maintained before reading this manual and understanding its content 2020 2019 ALL RIGHTS RESERVED TO TELEFIRE GAS AND FIRE DETECTORS LTD...

Page 3: ...the following panels ADR 7000 SAVER 7000 GUARD 7 ADR 3000 ADR SAVER 2 2 Detectors The addressable strobe horn and horn serve as a basis for the following detectors TFO 480A TFH 280A TPH 482A 3 Install...

Page 4: ...he cable resistance as measured in the field has to be taken into account In communication lines for addressable devices SLC the loop resistance and capacitance the stricter of the two has to be consi...

Page 5: ...to the grounding by the grounding clamps on the panel 3 1 5 Location The device has to be installed indoors Exposure to outdoor and weather conditions must be prevented to avoid high humidity or dust...

Page 6: ...Horns will disable the horn but the strobe light will continue to be on until Respond is pressed in the panel Set the operating matrix of the device in the panel Read the technical instructions of th...

Page 7: ...TO TELEFIRE GAS AND FIRE DETECTORS LTD Rev 1 01 Date 4 2 2020 Page 5 of 7 3 2 4 Configuration switches TFB 180BSA i Note The switch is off when the selector is close to the digit and on when the swit...

Page 8: ...vice to the communication line of addressable devices and 24Vdc input i Note Measure the wiring to ensure there is no short circuit or connection or leakage to the ground before connecting the device...

Page 9: ...ation panel or addressable output assembly 24 Vdc 4 1 TFB 180SA Maximum current consumption device line 180 A quiescent state 2 mA alarm state Maximum current consumption from 24Vdc power source 10 mA...

Reviews: