User Guide
PAGE 84
Example of Entry/Exit Zone
WITHOUT
Security Switch Usage
For Entry Zone:
The entry delay is the period of time between entering the surveillance zone and
reachingthe digital video recorder. In order to disarm the system for maintenance or repair,
user / installer enters the surveillance zone. The delay timer starts from the 1st trigger by
the 1st alarm sensor (i.e. Alarm 4). Note that if user enables recording action, recording
action is automatically activated during entry delay.
The detail description is shown as follows:
1. The alarm is set at entry delay
2. The 1st trigger is made by Alarm 4 (i.e. user enters the surveillance zone and the entry
delay time begins)
3. 2nd, 3rd and 4th trigger are made and each entry delay starts respectively
4. User disarms the system for maintenance
For example: If the time for going from security switch to digital video recorder is about 8
minutes, Delay 4 should be around 8 minutes, while Delay 3 should be longer than the
time for going from security switch to Alarm 3, and so on.