nrgSMART
nrgSMART
™
™
Controller Confi guration Guide
Controller Confi guration Guide
POWER ::
POWER ::
User Guide
User Guide
Panels Tab :: Circuit Confi guration > Circuit Settings > Current Sensors Screen
Ref.
Field
Type
Value
Description
1
ID (column)
Read Only
Text
Indicates the fuse type and its location in the panel.
Circuit outputs can include:
Single-Pole Output, Dual-Pole Output,
Triple-Pole Output, GMT, TPS and TLS.
Refer to 6.2,
Fuse/Circuit Breaker Ratings for more information.
2
Precision (column)
Select
Drop down
Menu
Sets the Current Sensor precision value for the selected row. This value
determines the amount of fl uctuation before a sensor adjusts its reading.
Default is:
1.11
From the Precision drop down menu, select from:
1.xx
: This value can fl uctuate by one point before a sensor adjusts.
1.1x
: This value can fl uctuate by 1/10 of a point before a sensor adjusts.
1.11
: This value can fl uctuate by 1/100 of a point before a sensor adjusts.
3
Present (column)
Read Only
Text
Indicates if a sensor module is in the location indicated in the ID column.
Default is:
No
When the sensor module has been added, this fi eld defaults to
Yes
.
Figure 30 - Current Sensors Screen
10
4
5
7
9
11
12
13
15
14
2
3
6
1
8
16
NOTE: Field values in this screen default to specifi c settings. They do not require additional input, but can be customized if desired.
The fi elds in this table are column headings that defi ne data displayed in rows within the columns.
ALERT
ALERT! Global Threshold and light indicators for these fi elds will ONLY display in this screen.
For data to display in the
Current Sensors Screen, select
Enabled
in the
Panels Screen.
The
Current Sensors Screen is a tool to view how circuits are performing using sensors that indicate current status. Sensor precision values
can be adjusted to refl ect the degree of fl uctuation in current. When enabled, global threshold values indicate where current levels are among
one or both selected SNMP and Alarm sensors. The Alarm light displays the highest threshold value in the row depending on selection of one
or both selected SNMP and Alarm sensors.