nrgSMART
nrgSMART
™
™
Controller Confi guration Guide
Controller Confi guration Guide
POWER ::
POWER ::
User Guide
User Guide
Panels Tab :: Circuit Confi guration > Circuit Settings > Voltage Sensors and Temperature Sensors Screens
Ref.
Field
Type
Value
Description
1
ID (column)
Read Only
Text
The row for the sensor settings being defi ned.
2
Precision (column)
Select
Drop down
Menu
Sets the current sensor precision value for the selected row. This value
determines the amount of fl uctuation before a sensor adjusts its reading.
Default is:
1.11
From the Precision drop down menu, select from:
1.xx
: This value can fl uctuate by one point before a sensor adjusts.
1.1x
: This value can fl uctuate by 1/10 of a point before a sensor adjusts.
1.11
: This value can fl uctuate by 1/100 of a point before a sensor adjusts.
3
SNMP (column)
Select
Checkbox
When SNMP is enabled (in the
Controller Tab), this checkbox allows the
voltage or temperature sensor data to be sent over SNMP.
Default is:
Checked
To enable sensor settings for SNMP,
select
(to check) the
SNMP
Checkbox. To disable,
deselect
the Checkbox.
NOTE: Threshold settings enabled during controller confi guration remain
operational even when this fi eld is unchecked, but sensor settings are
not set.
4
Data Server (column)
Select
Checkbox
This feature has been removed.
ALERT
ALERT! Unless otherwise noted, fi eld settings are defi ned in the same manner for the
Voltage Sensors Screen and the Temperature
Sensors Screen. Indicators for these fi elds ONLY display in this screen as notifi cation of sensor settings.
Figure 29 - Voltage Sensors Screen and Temperature Sensors Screen
1
2
10
3
4
5
6
7
8
9
NOTE: Field values in these screens default to specifi c settings. They do not require additional input, but can be customized if desired.
The fi elds in these tables are column headings that defi ne data displayed in rows within the columns.
For data to display in the
Voltage Sensors and the Temperature Sensors Screens, select
Enabled
in the
Panels Screen.