Controller Tab :: Measurement Settings Screen
Ref.
Field
Type
Value
Description
11
Upper Critical
Select
Drop down
menu
Upper Critical is a user defi ned threshold that is a percentage of the Global
Fuse Rating and indicates a higher than expected measurement, defi ned
as a critical alarm.
Default is:
80%
From the Upper Critical drop down menu, select from:
0% to 100% in
5% increments
.
12
Alarm
Read Only
Light
This light indicates the threshold level of current to the circuit on the row.
Green
: Normal current.
Yellow
: Warning threshold reached.
Orange
: Critical threshold reached.
Red
: A blown fuse or tripped breaker.
Gray
: Not connected.