Quick Start Guide

•  For Liquid and Steam

Tek-DP 1610D Integral Orifice Assemblies should be mounted below the pipe to ensure that that gases do 

not collect on the transmitter sensing diaphragms.

If the fluid is flowing down, a direct mount Tek-DP 1610D should not be used in vertical liquid or steam 

applications. Vertical installation for steam should be remote mount.

Where,  

A is 90° Recommended Zone

 

 

B is Vertical Plane

 

 

C is Horizontal Plane

Where , 

A is 360° Recommended Zone.

Fig 12: Direct Mount Gas in Vertical Pipes

Fig 11: Direct Mount Liquid or Steam in Horizontal Pipes

A

B

C

A

C

B

A

FLOW

A

Summary of Contents for TEK-DP 1610D

Page 1: ...Quick Start Guide TEK DP 1610D 796 Tek Drive Crystal Lake IL 60014 USA 1 847 857 6076 1 847 655 6147 www tek trol com Integral Orifice Assembly...

Page 2: ...ational and international standards codes and practices Review the approvals section of the 3800E Multivariable Pressure Transmitter reference manual for any restrictions associated with a safe instal...

Page 3: ...Technology Solutions Fig 5 Two or More 90 Bends in Same Planes 4 Installations Straight Length Requirements Fig 3 Reducer U D Fig 4 Single 90 Bend Flow from One Branch U D 2d to d over a length of 1...

Page 4: ...L 60014 USA 1 847 857 6076 1 847 655 6147 www tek trol com Quick Start Guide Fig 6 Two or More 90 Bends in Different Planes Fig 7 Expander Fig 8 Ball Valve or Gate Valve Fully Open U D 0 5d to d over...

Page 5: ...ymmetrical reduction having a diameter ratio 0 5 Thermo meter pocket or well of diameter 0 03D Thermo meter pocket or well of diameter between 0 03D and 0 13D Fitting All mentioned in Upstream Side of...

Page 6: ...5 4 0 50 1 5 0 5 2 5 1 5 8 5 5 5 0 5 2 5 1 5 3 5 1 5 4 0 55 2 5 0 5 2 5 1 5 12 5 6 5 0 5 3 5 1 5 4 5 2 5 4 0 60 3 1 3 5 2 5 17 5 8 5 0 5 3 5 1 5 4 5 2 5 4 0 65 4 1 5 4 5 2 5 23 5 9 5 1 5 4 5 2 5 4 5...

Page 7: ...pipe to ensure that condensate does not collect on the transmitter sensing diaphragms If the fluid is flowing up a direct mount Tek DP 1610D should not be used in vertical gas applications because of...

Page 8: ...ect on the transmitter sensing diaphragms If the fluid is flowing down a direct mount Tek DP 1610D should not be used in vertical liquid or steam applications Vertical installation for steam should be...

Page 9: ...Vent B is High Valve C is Equalizer D is Equalizer Valve Where A is Low Valve B is Vent C is High Valve D is Equalizer Valve E is Block Valves Fig 13 Direct Mount Gas Measurement Fig 14 Remote Mount G...

Page 10: ...Guide Liquid Measurement Fig 15 Direct Mount Liquid Measurement Fig 16 Remote Mount Liquid Measurement Where A is Vent B is Low Valve C is Equalizer Valve D is High Valve Where A is Vent B is High Val...

Page 11: ...ect Mount Steam Measurement Fig 18 Remote Mount Steam Measurement Where A is Vent B is Low Valve C is Equalizer Valve D is High Valve Where A is Vent B is High Valve C is Equalizer Valve D is Vent Val...

Page 12: ...transmitter o Remove the temperature terminal housing cover o Disconnect the RTD lead wires from the terminal block o Separate the wires so that the un insulated ends are not affecting o Check that th...

Page 13: ...parameters for accuracy Cross check pipe inside diameter for proper sizing Raising flow signal Two phase flow The flow meter is a head measurement device and will not measure a two phase flow accurate...

Page 14: ...utions BV Tek Trol Middle East FZE PO Box 121 Windsor Colorado 80550 USA Sales 1 847 857 6076 796 Tek Drive Crystal Lake IL 60014 USA Sales 1 847 857 6076 Florijnstraat 18 4879 AH Etten Leur Netherlan...

Reviews: