background image

Tek-DP 1610D

Technology Solutions

7. Troubleshooting

This section provides troubleshooting techniques for most common operating problems shown in 

table 3.

Table 3: Troubleshooting Techniques

Symptom 

Possible Cause 

Corrective Actions

Questionable accuracy

or erroneous flow signal

Improper Installation

•  Check flow arrow pointed in the direction of the flow.

•  Verify that the cross reservoirs are correctly in level with one another.

•  Check the sufficient straight runs upstream and downstream of the flow meter. 

System Leaks

•  Check instrument piping leaks.

•  Repair and seal all leaks.

Contamination or Plugging

• Remove the flow meter and check for contamination.

Closed Valve

• Verify both High and Low manifold valves are open.

• Verify vent, equalizer and line valves are properly positioned per start-up procedure.

Connections

(remote mount only)

•  Verify the high side of the transmitter is connected to the high side of the flow meter. 

•  Check the same for the low side.

Entrapped Air (liquid and 

steam applications)

•  Check uneven water legs caused by air entrapment in the instrument connections, if so, bleed 

air.

Questionable accuracy

or erroneous flow signal

Operating Conditions

•  Check the operating conditions in compliance with those given at the time the flow meter 

was purchased.

•  Check the flow calculation and the fluid parameters for accuracy.

•  Cross check pipe inside diameter for proper sizing.

Raising flow signal

Two-phase flow

•  The flow meter is a head measurement device and will not measure a two-phase flow 

accurately.

Raising flow signal (Stream 

Service)

Improper insulation (vertical 

pipes only), Excessive 

vibration

•  Additional insulation may be required to ensure a phase change occurs at the cross reservoirs.

•  Check the impulse piping for vibration.

mA reading is zero

•  Check if the power terminals are reversed.

•  Verify voltage across terminals (should be 10 to 55VDC).

•  Check for bad diode in terminal block.

•  Replace the transmitter terminal block.

Transmitter is not 

communicating

•  Check power supply voltage of the transmitter (10.5VDC minimum).

•  Check load resistance (250Ω minimum).

•  Check if the unit is addressed properly.

•  Replace the Transmitter.

mA reading is high or low

•  Check pressure variable reading for saturation.

•  Check if output is in alarm condition.

•  Perform 4–20mA output trim.

•  Replace Transmitter.

No response to changes in 

applied flow

•  Check test equipment.

•  Check impulse piping for blockage.

•  Check for disabled span adjustment.

•  Check transmitter security switch.

•  Verify calibration settings (4 and 20mA points).

•  Contact factory for replacement.

Low or High reading

•  Check impulse piping for blockage.

•  Check test equipment.

•  Perform full sensor trim.  

•  Contact factory for replacement.

Unpredictable reading for 

pressure variable

•  Check impulse piping for blockage.

•  Check damping.

•  Check for EMF interference.

•  Contact factory for replacement.

Summary of Contents for TEK-DP 1610D

Page 1: ...Quick Start Guide TEK DP 1610D 796 Tek Drive Crystal Lake IL 60014 USA 1 847 857 6076 1 847 655 6147 www tek trol com Integral Orifice Assembly...

Page 2: ...ational and international standards codes and practices Review the approvals section of the 3800E Multivariable Pressure Transmitter reference manual for any restrictions associated with a safe instal...

Page 3: ...Technology Solutions Fig 5 Two or More 90 Bends in Same Planes 4 Installations Straight Length Requirements Fig 3 Reducer U D Fig 4 Single 90 Bend Flow from One Branch U D 2d to d over a length of 1...

Page 4: ...L 60014 USA 1 847 857 6076 1 847 655 6147 www tek trol com Quick Start Guide Fig 6 Two or More 90 Bends in Different Planes Fig 7 Expander Fig 8 Ball Valve or Gate Valve Fully Open U D 0 5d to d over...

Page 5: ...ymmetrical reduction having a diameter ratio 0 5 Thermo meter pocket or well of diameter 0 03D Thermo meter pocket or well of diameter between 0 03D and 0 13D Fitting All mentioned in Upstream Side of...

Page 6: ...5 4 0 50 1 5 0 5 2 5 1 5 8 5 5 5 0 5 2 5 1 5 3 5 1 5 4 0 55 2 5 0 5 2 5 1 5 12 5 6 5 0 5 3 5 1 5 4 5 2 5 4 0 60 3 1 3 5 2 5 17 5 8 5 0 5 3 5 1 5 4 5 2 5 4 0 65 4 1 5 4 5 2 5 23 5 9 5 1 5 4 5 2 5 4 5...

Page 7: ...pipe to ensure that condensate does not collect on the transmitter sensing diaphragms If the fluid is flowing up a direct mount Tek DP 1610D should not be used in vertical gas applications because of...

Page 8: ...ect on the transmitter sensing diaphragms If the fluid is flowing down a direct mount Tek DP 1610D should not be used in vertical liquid or steam applications Vertical installation for steam should be...

Page 9: ...Vent B is High Valve C is Equalizer D is Equalizer Valve Where A is Low Valve B is Vent C is High Valve D is Equalizer Valve E is Block Valves Fig 13 Direct Mount Gas Measurement Fig 14 Remote Mount G...

Page 10: ...Guide Liquid Measurement Fig 15 Direct Mount Liquid Measurement Fig 16 Remote Mount Liquid Measurement Where A is Vent B is Low Valve C is Equalizer Valve D is High Valve Where A is Vent B is High Val...

Page 11: ...ect Mount Steam Measurement Fig 18 Remote Mount Steam Measurement Where A is Vent B is Low Valve C is Equalizer Valve D is High Valve Where A is Vent B is High Valve C is Equalizer Valve D is Vent Val...

Page 12: ...transmitter o Remove the temperature terminal housing cover o Disconnect the RTD lead wires from the terminal block o Separate the wires so that the un insulated ends are not affecting o Check that th...

Page 13: ...parameters for accuracy Cross check pipe inside diameter for proper sizing Raising flow signal Two phase flow The flow meter is a head measurement device and will not measure a two phase flow accurate...

Page 14: ...utions BV Tek Trol Middle East FZE PO Box 121 Windsor Colorado 80550 USA Sales 1 847 857 6076 796 Tek Drive Crystal Lake IL 60014 USA Sales 1 847 857 6076 Florijnstraat 18 4879 AH Etten Leur Netherlan...

Reviews: