1. DCF-77 output pulse simulation
2. IRIG-B NRZI (B000/B001 or B002/B003)
3. IRIG-B Modified Manchester Encoded (B220/B223 or B221/B222)
4. User Defined Pulse Sequence (separate definition stored for each output)
In the case of the User-Defined Pulse option being selected for any outputs, further
parameters are entered to define the pulse sequence. The parameters are as follows:-
A drop-down menu allows the user to choose to have pulses output “Every” “second”,
“minute”, “hour”, or “day”.
The “Pulses” field defines the number of pulses that will be produced in the selected
time interval. Selection is constrained to even divisors of the time interval.
The “Offset” data entry boxes specify how much time elapses into the defined time
interval before pulsing starts. Data validation rules ensure that only sensible entries can
be made.
The “Duration” data entry boxes specify the length of individual pulses.