40
PLUS
TWP-4AI4DI1UT
INSTALLATION GUIDE
07
step
GATEWAY ANALOG OUTPUTS
01
Follow steps 06 and 07 of the PLUS Wireless
Gateway
Configuration.
02
In
Tekon Configurator Software
select
PLUS
>>
Gateway
>>
Analog Outputs
menu
2
1
3
NOTE:
Transmitter analog input 1 data is received and stored at the Gateway Modbus address [9].
03
Considering the transmitter configuration with GTW Modbus Index=1, there is a Gateway Modbus Address
Window corresponding to Modbus address window [0-19].
MB Add
0
19
HOLDING REGISTERS - TRANSMITTERS DATA
Description
Address
Serial Number
(Transmitter Modbus Index-1) x 20+0
Transmitter Model
(Transmitter Modbus Index-1)x20+2
RSSI
(Transmitter Modbus Index-1)x20+3
Communication Period
(Transmitter Modbus Index-1)x20+4
Elapsed Time
(Transmitter Modbus Index-1)x20+5
Power Voltage
(Transmitter Modbus Index-1)x20+6
Data 0
(Transmitter Modbus Index-1)x20+7
Data 1
(Transmitter Modbus Index-1)x20+9
Data 2
(Transmitter Modbus Index-1)x20+11
Data 3
(Transmitter Modbus Index-1)x20+13
Data 4
(Transmitter Modbus Index-1)x20+15
FW Version Major Minor
(Transmitter Modbus Index-1)x20+17
FW Version Revision
(Transmitter Modbus Index-1)x20+18
HW Version Major Minor
(Transmitter Modbus Index-1)x20+19
9
Summary of Contents for PLUS TWP-4AI4DI1UT
Page 20: ...03 step TWP 4AI4DI1UT TRANSMITTER ANALOG INPUT CONFIGURATION...
Page 24: ...04 step TWP 4AI4DI1UT TRANSMITTER DIGITAL INPUTS CONFIGURATION...
Page 30: ...05 step TWP 4AI4DI1UT TRANSM UNIV TEMPERATURE INPUT CONFIGURATION...
Page 33: ...06 step TWP 4AI4DI1UT TRANSMITTER DIGITAL OUTPUTS CONFIGURATION...
Page 39: ...07 step WGW420 GATEWAY ANALOG OUTPUTS CONFIGURATION...
Page 42: ...08 step WRP001 PLUS WIRELESS REPEATER CONFIGURATION...
Page 48: ...09 step SITE SURVEY MODE...