background image

 

 

 

 

 

 

                                                                                                                     

6

 

If the batteries are disconnected, the charger does not charge, the battery fuse is blown, or the 
batteries do not accept charging current, the following alarms are displayed on the screen:    

  

Main use LED is lit 
Under-voltage or over-voltage LED is lit 
Battery fault LED is lit

 

Internal fault LED is lit

 

 

2.6. Alarm relay outputs 
 

Fault alarm: 

 

 

- Alarms, when a fault is detected. 

Emergency mode alarm:

 

- Alarms when the unit is in battery mode. 

 

 

2.7. Remote control 
 

Remote control on: 

 

- network use LED is blinking, and the battery use LED is lit 

 
 

3. System installation 

 
Only a qualified electrical worker may perform system installation and implementation.  
No connections in the unit shall be made with voltage on!

 

 

System installation takes place according to the electrical design plan, or the electrical work 
explanation.  

 

In the starting phase, the main switch must be in position 0 and the battery fuse must not be 
connected. The batteries are always placed in a separate battery cabinet. The batteries are connected 
in series 18 x 12 V to the + (red) and 

– (black) cables reserved for them. The battery 

temperature 

sensor shall be placed between the batteries

. Check the battery polarity.  

 
Bring the mains supply cable to the connectors L, PE and N. After this, connect the maintained and 
non-maintained circuits to circuit boards TS10-TS13/ CIRCUITS 1-6. The circuit fuses are located in 
fuse holders F1-F6 (see Appendix 2, connections). The outputs a

re connected by the “Mode” wire 

loops (see connections, Appendix 2), either as maintained or non-maintained:  
 
”Mode” loop connected: 

maintained circuit  

”Mode” loop not connected:  non-maintained circuit 

 

 
”Mode” loop affects always two circuit outputs. 
 
Mode AB circuits 1-2 
Mode CD circuits 5-6 
Mode EF circuits 3-4 
 

At the factory, all the circuits in the unit are set as maintained circuits. The circuits that are required for 
non-

maintained use, must have the corresponding “Mode” wire loop removed.  

 
The alarms and the remote control switch are connected to the connectors presented in Appendix 2.  
 
 

4. Implementation 

 
Only a qualified electrical worker may perform system installation and implementation. 
 
The type label located inside the unit shall be marked with the total load connected to the unit, 
and the battery mode duration, with rated load, shall be marked in the two empty columns. 
 

At the factory, the central battery unit and the luminaires are subjected to voltage withstand test, 
insulation resistance test and grounding connectivity tests, according to the Low Voltage Directive. 
During the final insulation resistance testing of the installed system, the mains input and circuit outputs 
of the unit must be short-circuited. 

Summary of Contents for TKT65 B Series

Page 1: ...1 VOT6506E CENTRAL BATTERY UNIT FOR EMERGENCY LIGHTING Installation and maintenance instructions TKT65XXB P KEEP IN A SAFE PLACE FOR LATER USE...

Page 2: ...Charging 5 2 4 Mains voltage limits 6 2 5 Battery voltage limits 6 2 6 Alarm relay outputs 6 2 7 Remote control 6 3 System installation 6 4 Implementation 6 4 1 Setting the charging current 7 5 Use 7...

Page 3: ...rge limit 173 V The batteries 18 pcs for the unit always require a separate battery cabinet All the functions related to the use of the unit can be performed from the control panel that also includes...

Page 4: ...t be suitable both for AC and DC supply 1 5 Directives and standards The following directives and standards were applied in designing and manufacturing the unit Quality ISO 9001 2000 certified quality...

Page 5: ...charge the batteries Main use LED is lit Charging LED is blinking or lit 2 5 Battery voltage limits If the battery voltage rises over 260 V in normal mode an over voltage alarm is given Main use LED i...

Page 6: ...and N After this connect the maintained and non maintained circuits to circuit boards TS10 TS13 CIRCUITS 1 6 The circuit fuses are located in fuse holders F1 F6 see Appendix 2 connections The outputs...

Page 7: ...be set checked in the following way Set the current from the charging card TS5 DIP switch as indicated in the instructions NOTE The charging current must ALWAYS be set checked according to the number...

Page 8: ...orded in the emergency lighting system maintenance manual which shall be shown to the authorities when requested 6 2 Replacing the batteries The batteries shall be changed in the following order take...

Page 9: ...OVER VOLTAGE The battery voltage is higher than normal over 260 V BATTERY UNDER VOLTAGE The battery voltage is lower than normal under 228 V DEEP DISCHARGE The deep discharge protection of the battery...

Page 10: ...10 APPENDIX 2 Connections...

Page 11: ...11 APPENDIX 3 Part placement TS5 CHARGING CURRENT SETTING DIP SWITCH...

Page 12: ...12 APPENDIX 4 Dimensions TKT65 B...

Page 13: ...13 APPENDIX 4 Dimensions TKT65xxBP cabinet construction...

Reviews: