1. Product description

 

 
1.1. Manufacturer 
 

Teknoware Oy 
Ilmarisentie 8 
FI-15200 Lahti 
FINLAND 
 

1.2. Type 
 

TKT6506B Max.  6 circuits 230 V AC/DC 
TKT6512B Max. 12 circuits 230 V AC/DC 
TKT6518B Max. 18 circuits 230 V AC/DC 
TKT6524B Max. 24 circuits 230 V AC/DC 

 
1.3. General description 

 
TKT65XXB central battery unit is based on the Teknoware TKT series product family. This family is 
designed and manufactured according to the EN 50171 standard.   
 
In normal situations, the unit works from the 230 VAC mains supply, by maintaining the battery 
charging level, and by feeding a voltage of 230 VAC, to the maintained output circuits. When the mains 
voltage fails, or it drops below 180 V, the unit changes to battery use. This connects a voltage of 220 
VDC to the non-maintained circuits, and the voltage feed to the maintained circuits changes from 230 
VAC to 220 VDC. The battery feed works as long as the mains voltage remains unavailable, or the 
battery voltage is lowered to the deep discharge limit (173 V). 
 
The batteries (18 pcs) for the unit always require a separate battery cabinet. 
 
All the functions related to the use of the unit can be performed from the control panel that also 
includes display LEDs to indicate the operation status. The panel functions are presented in Appendix 
1. 
 

1.4. Technical specifications 

 
Mains connection: 

 

230 VAC 50 Hz 1~ 

Output voltage:   

 

normal mode: 230 VAC, emergency mode: 220 VDC 

Battery voltage:  

 

220 VDC 

Battery charging time:   

12 h 

Max input power TKT6506B:  

2,250 VA 

Max input power TKT6512B:  

2,250 VA 

Max input power TKT6518B:  

3,680 VA 

Max input power TKT6524B:  

3,680 VA 

Ambient temperature range:  

+10 … +30

Input fuse:  

 

 

Circuit breaker 10 AT (TKT6506B) 

Input fuse:  

 

 

Circuit breaker 16 AT (TKT6512B, TKT6524B, TKT6512B) 

Group fuses:  

 

 

5x20mm glass tube 4 AT 

Battery fuse TKT6506B:  

2 x 10 A plug cartridge S 10 A / 380 V Neozed 

Battery fuse TKT6512B:  

2 x 16 A plug cartridge S 16 A / 380 V Neozed 

Battery fuse TKT6518B:  

2 x 35 A plug cartridge S 35 A / 380 V Neozed 

Battery fuse TKT6524B:  

2 x 63 A plug cartridge S 63 A / 380 V Neozed 

Charging circuit fuses:    

5 x 20 mm glass tube 6,3 AT 

IP class of the casing:   

IP20 (basic models), IP34 (cabinet construction TKT65xxB

P

)  

 
 
 
 
 
 
 
 

Summary of Contents for TKT65 B Series

Page 1: ...1 VOT6506E CENTRAL BATTERY UNIT FOR EMERGENCY LIGHTING Installation and maintenance instructions TKT65XXB P KEEP IN A SAFE PLACE FOR LATER USE...

Page 2: ...Charging 5 2 4 Mains voltage limits 6 2 5 Battery voltage limits 6 2 6 Alarm relay outputs 6 2 7 Remote control 6 3 System installation 6 4 Implementation 6 4 1 Setting the charging current 7 5 Use 7...

Page 3: ...rge limit 173 V The batteries 18 pcs for the unit always require a separate battery cabinet All the functions related to the use of the unit can be performed from the control panel that also includes...

Page 4: ...t be suitable both for AC and DC supply 1 5 Directives and standards The following directives and standards were applied in designing and manufacturing the unit Quality ISO 9001 2000 certified quality...

Page 5: ...charge the batteries Main use LED is lit Charging LED is blinking or lit 2 5 Battery voltage limits If the battery voltage rises over 260 V in normal mode an over voltage alarm is given Main use LED i...

Page 6: ...and N After this connect the maintained and non maintained circuits to circuit boards TS10 TS13 CIRCUITS 1 6 The circuit fuses are located in fuse holders F1 F6 see Appendix 2 connections The outputs...

Page 7: ...be set checked in the following way Set the current from the charging card TS5 DIP switch as indicated in the instructions NOTE The charging current must ALWAYS be set checked according to the number...

Page 8: ...orded in the emergency lighting system maintenance manual which shall be shown to the authorities when requested 6 2 Replacing the batteries The batteries shall be changed in the following order take...

Page 9: ...OVER VOLTAGE The battery voltage is higher than normal over 260 V BATTERY UNDER VOLTAGE The battery voltage is lower than normal under 228 V DEEP DISCHARGE The deep discharge protection of the battery...

Page 10: ...10 APPENDIX 2 Connections...

Page 11: ...11 APPENDIX 3 Part placement TS5 CHARGING CURRENT SETTING DIP SWITCH...

Page 12: ...12 APPENDIX 4 Dimensions TKT65 B...

Page 13: ...13 APPENDIX 4 Dimensions TKT65xxBP cabinet construction...