Heating Operation

Section A

Sequence of Operation

When using only a room temperature sensor, the thermostat operates the heating 
system to maintain the Set Room Heat temperature. 
When using only a floor temperature sensor, the thermostat operates the heating 
system to maintain the Set Floor Heat temperature. In this case, the thermostat 
does not try to control the air temperature. This is ideal for bathrooms and some 
kitchen applications where the customer wants their feet to feel warm on the floor. 
This is also ideal for garages so that the heating system is not affected by the 
opening of the garage door in cold outdoor weather.
When using both a room temperature sensor and a floor temperature sensor, the 
thermostat always maintains the Floor Minimum temperature, even when the air 
temperature is satisfied. When the air temperature is below the Set Room Heat 
temperature, the thermostat operates the heating system to maintain the Set Room 
Heat temperature. The floor is never heated above the Floor Maximum setting in 
order to protect the floor covering.
The H1 symbol indicates that the thermostat is heating with stage 1. The H2 symbol 
indicates that the thermostat is heating with stage 2. The heat can cycle on and off 
/- 1.5°F (1°C) of the Set Room Heat temperature.

Second Stage Differential

 --------------------------------------------

 --------------------------------------------

The Heat 2 Differential setting allows for a reduction in second stage operation by 
applying a temperature differential for second stage below the room target. The 
Heat 2 relay is turned on once the air temperature reaches the Set Room Heat 
temperature minus the Differential setting. The Heat 2 relay is shut off once the air 
temperature reaches the Set Room Heat temperature minus 1.5°F (1.0°C). The 
automatic differential (AU) setting operates the second stage to provide optimum 
comfort level. When the Differential is set to Off, the second stage is disabled.

Second Stage Heat Source

 -------------------------------------------

 -------------------------------------------

The Heat 2 Source setting determines which water temperature the second stage 
will draw its heat from. Select boiler temperature, mix 1, mix 2, mix 3, or other 
(non-hydronic). If “other” is selected, a heat demand will not be sent from second 
stage to the tekmarNet

®

 reset control.

Freeze Protection

 

----------------------------------------------------

 

----------------------------------------------------

The thermostat operates the heat whenever the room or floor temperature falls 
below 40°F (4.5°C).

Summary of Contents for tekmarNet 2 Thermostat 529

Page 1: ...ch overrides User Switch Auto Heating Cycle tekmarNet 2 Communication compatible Requires 2 wires Two stage heat Pulse Width Modulation CSA C US Approved for use in USA and Canada Outdoor Temperature...

Page 2: ...ng the Thermostat Wiring 6 Mounting the Thermostat 6 Cleaning the Thermostat 7 Switch Settings 7 User Interface 8 Display 8 Button Operation 8 Symbols Description 8 Settings 9 16 Sequence of Operation...

Page 3: ...f wire is 1000 feet 300 m Strip wire to 3 8 10 mm for all terminal connections Use standard 18 AWG wire for the tN2 connections Installation Location Removing The Thermostat Base Push tab 1 Remove the...

Page 4: ...ermostat by connecting the tN2 terminals on the thermostat to the tN2 terminals on a tN2 Wiring Center House Control Zone Manager or Zone Expansion Module tN2 terminals are not polarity sensitive Conn...

Page 5: ...the 529 thermostat s second stage relay must be used This relay will close when the thermostat calls for 2nd stage heat Rh W2 and can be used to bring on the heating equipment Note This 2nd stage wiri...

Page 6: ...g Center or Zone Manager If the thermostat display remains permanently on there may be a fault with the previously tried zone on the House Control Wiring Center or Zone Manager If the thermostat displ...

Page 7: ...rammable setback schedule 2 ON SCENE The thermostat responds to changes in the scene system wide manual overrides Requires the installation of a User Switch 479 to use this feature OFF OFF The thermos...

Page 8: ...temperature AIR GROUP The air group is cooling Heating can start once the cooling is finished LOCK Locked to User access level CLOCK Operating on a programmable schedule tekmarNet Communication is pr...

Page 9: ...ler SET ROOM HEAT AWAY Set the room heating temperature while in the Away scene Continued on next page Press and hold down both the and buttons for 2 seconds to change from one step to the next Releas...

Page 10: ...ing in the Adjust menu is set to Off 40 to 122 F 4 5 to 50 0 C Default 65 F 18 5 C Installer User SET FLOOR HEAT Set the floor heating temperature while in the event Available when A slab sensor is in...

Page 11: ...rge number with Software Version upper right corner and the thermostat address 40 to 95 F 4 5 to 35 0 C Default 85 F 29 5 C Installer MAXIMUM SET ROOM HEAT Set the maximum room heating limit while in...

Page 12: ...n AND A slab sensor is installed on the auxiliary sensor input AND Sensor setting in the Adjust menu is set to Floor Off 40 to 122 F Off 4 5 to 50 0 C Default Off Installer User SET FLOOR MINIMUM Set...

Page 13: ...D Sensor setting in the Adjust menu is set to Floor 1 2 3 4 Default 1 Installer SCHEDULE Thermostat can follow schedule master 1 2 3 or 4 Available when Switch setting 1 is set to Setback On Position...

Page 14: ...n Synchronize Default Sychronize Installer HEAT CYCLES PER HOUR Select either Auto cycle or Synchronize with other thermostats on the tekmarNet system Choose Synchronize when zone heated using a boile...

Page 15: ...hen A reset control is present on the tekmarNet system There is an active room sensor OFF On Default On Installer HEAT 2 SUPPLY PUMP Select whether the system supply pump should turn on during a call...

Page 16: ...t control mixing Installer tekmarNet ADDRESS The address is shown in the large number field Auto is shown in the upper number field when using automatic addressing Press the or the button to manually...

Page 17: ...n order to protect the floor covering The H1 symbol indicates that the thermostat is heating with stage 1 The H2 symbol indicates that the thermostat is heating with stage 2 The heat can cycle on and...

Page 18: ...On to operate the primary pump and or the mix system pump when there is a call for heat from the thermostat In special applications with multiple zoning manifolds the Heat 1 Supply Pump setting can b...

Page 19: ...while the air group is cooling the snowflake icon is flashed to alert the user that the cooling is presently on Once the cooling shuts off the heating can start operation Air Group Master Member Membe...

Page 20: ...e Display Room Temperature Setting 1 or or Follows programmable schedule or operates at the occupied temperature 2 Away Away temperature 3 Unoccupied temperature Scenes System Override Section E When...

Page 21: ...nue until all settings have been reviewed BUS ERROR The tekmarNet 4 communication bus has either an open or a short circuit The result is that there are no communications Check for loose wires Check f...

Page 22: ...h the auxiliary room sensor short circuit error This error cannot be field repaired Contact your wholesaler or tekmar sales representative for details on repair procedures ROOM SENSOR OPEN CIRCUIT The...

Page 23: ...described in the Data Brochure D072 or D 079 Error clears once the floor sensor fault is corrected FLOOR SENSOR OPEN CIRCUIT The auxiliary floor sensor has an open circuit Check for loose or damaged w...

Page 24: ...rochure D 070 Error clears once the outdoor sensor fault is corrected If the outdoor sensor was intentionally removed power the thermostat down and up to clear the error AIR GROUP MEMBER ERROR The the...

Page 25: ...arly so that the room is comfortable at the scheduled time Pressing button does not increase temperature Flashing Max Installer can increase the Maximum Set Room Heat Flashing Floor Max Floor temperat...

Page 26: ...eat 1 Supply Pump Backlight Heat 1 Pump Delay Units Heat 2 Source Max Set Room Heat Heat 2 Supply Pump Max Set Room Heat Heat 2 Differential Min Set Room Heat Air Group Set Floor Min tekmarNet Address...

Page 27: ...SA C US meets Class B ICES and FCC Part 15 Ambient conditions Indoor use only 32 to 122 F 0 to 50 C RH max 80 up to 88 F 31 C decreasing linearly to 50 RH at 104 F 40 C Altitude 0 6560 feet 2000 m Ins...

Page 28: ...s not cover the cost of the parts or labor to remove or transport the defec tive Product or to reinstall the repaired or replacement Product all such costs and expenses being subject to Purchaser s ag...

Reviews: