background image

Master Catalog

125

Temperature Controls Section

A

Product Bulletin

A19

Issue Date

0579

© 1979 Johnson Controls, Inc.

1

Code No. LIT-125030

A19 Series Utility Thermostats for Farm,

Industrial and Commercial Use

Application

These temperature controls are designed to cover a
broad range of uses for heating and general purpose
requirements.  See “Application” column,
“Specifications” Page 2, for typical uses.  Controls
have SPST contacts which open on temperature
increase or they may be supplied in single-pole,
double-throw contact action.

Various control ranges are available to cover working
temperatures from -30 to 550

°

 F (-34 to 288

°

 C).

Closed tank fittings and bulb wells are available for
immersion applications.

These controls are designed for open low and open
high applications.  Where critical or high value
products are to be maintained within a specific
temperature differential, a single control should not
be applied to function as both an open low and open
high control.  In these applications, a separate back-
up control with alarm contacts should be wired to
indicate when the back-up control operates.

Fig. 2:  Space thermostat

with Style 3 coiled bulb

and finger-tip adjusting knob.

Fig. 1:  (Left) Control with external range scale,

knob adjustment.  (Right) Interior of model with

adjustable differential.

Features

Dependability -- precision snap-acting dusttight

contacts.

Dependability -- low volume, responsive liquid

filled sensing elements.

Wide choice of temperature control functions with

a minimum number of models.

Precision “repeat” accuracy which is unaffected by

barometric pressure and cross ambient problems.

Special close differential models available.

General Description

The Series A19 is a small, compact control with
adjustable or fixed differential.  Controls supplied with
adjustable differential have an internal scale plate
indicating increments of differential.  The controls are
supplied with adjusting lever at minimum differential
stamped on the control.  To adjust move the lever to
the differential required.  Models are available with or
without external range adjustment and visible scale.
External range adjustment may be by screwdriver slot
or range adjusting knob (Fig. 2).

Summary of Contents for A19 Series

Page 1: ...ions a separate back up control with alarm contacts should be wired to indicate when the back up control operates Fig 2 Space thermostat with Style 3 coiled bulb and finger tip adjusting knob Fig 1 Left Control with external range scale knob adjustment Right Interior of model with adjustable differential Features Dependability precision snap acting dusttight contacts Dependability low volume respo...

Page 2: ...s 10 0 6 0 Pilot Duty 125 VA 24 to 600 VAC Specifications Product Range Diff Max Bulb Bulb Bulb Bulb Cap Bulb Cover Range Adjuster Number Appl Action F C F C Temp F C Style Size in Well Length ft Suppor t in Plain Scale Screw driver Knob A19AAB 4 Fluid Cutout Opens on rise 30 to 110 1 to 43 3 1 7 140 60 1 3 8 x 4 15 16 WEL14A 602R 6 3 X X A19AAB 7 Industrial Oven Opens on rise 100 to 300 38 to 149...

Page 3: ...steel Gray baked enamel finish Contact Unit Precision Pennswitch Snap acting dust tight contacts Shipping Weights Shipping weights shown below are approximate Weights vary depending upon construction Generally overpack will contain 25 individually packed controls Individual pack 1 0 lb Overpack containing 25 individually packed units 26 0 lbs Ordering Information 1 Specify Product Number only if a...