background image

2    A19 Product Bulletin

A built-in high cutout stop is an integral part of these
controls and may be adjusted quickly and easily in the
field.  Product Number A19BAG-1 is especially
designed for portable heaters.  It is supplied with a
6 ft cord, 120 V.A.C. polarized plug, and a chain hanger
kit.

Optional Constructions

Note:  For most prompt service, select controls listed
under “Specifications,” below.  If these are not entirely
suitable for your application, then the following
variations are available.

Adjustable Differential:  Available at extra cost.

Armored Capillary:  Single braided copper armor may
be supplied at extra cost.

Capillary Tube:  Additional length of capillary over
6 ft available at extra cost.  Extra length in 2 ft
increments from 6 ft to 10 ft; over 10 ft in 5 ft
increments.

Contact Unit:  Close differential or special close
differential may be supplied.

Mounting Bracket:  Optional at extra cost.

Types A19AAB, A19AAC, A19BAB, A19BAC

Volts AC

120

208

240

Full Load Amps.

16.0

9.2

8.0

Locked Rotor Amps.

96.0

55.2

48.0

Non-inductive or

Resistance Load Amps.

(Not Lamp Load)

* 22 Amps. 120 to 277 VAC

Pilot Duty - 125 VA @ 24 to 600 VAC

* SPST Rating

Types A19AAE

Volts AC

120

208

240

Full Load Amps.

6.0

3.4

3.0

Locked Rotor Amps.

36.0

20.4

18.0

Non-inductive or

Resistance Load Amps.

(Not Lamp Load)

10 Amps. 120 to 277 VAC

Pilot Duty - 125 VA @ 24 to 277 VAC

Types A19AAB, A19AAC, A19ADB (Hot Water Models)

Volts AC

120

240

Full Load Amps.

10.0

6.0

Locked Rotor Amps.

60.0

36.0

Non-inductive or

Resistance Load Amps.

10.0

6.0

Pilot Duty - 125 VA @ 24 to 600 VAC

Specifications

Product

Range

Diff.

*Max. Bulb

Bulb

Bulb

Bulb

Cap.

Bulb

Cover

Range Adjuster

Number

Appl.

Action

°F (°C)

°F (°C)

Temp. °F

(°C)

Style

Size

(in.)

Well

Length

(ft.)

Suppor

t (in.)

Plain

Scale

Screw-

driver

Knob

A19AAB-4

Fluid

Cutout

Opens
on rise

30 to 110

(-1 to 43)

3 (1.7)

140 (60)

1

3/8 x

4-15/16

WEL14A-

602R

6

3

X

X

A19AAB-7

Industrial

Oven

Opens
on rise

100 to 300
(38 to 149)

7 (3.9)

350 (177)

1

3/16 x

10-1/8

6

X

X

A19AAB-

10

Industrial

Oven

Opens
on rise

200 to 550
(93 to 288)

10 (5.6)

620 (327)

1

3/16 x

5-5/8

6

X

X

A19AAC-1

Dual Fuel

Change-

over

SPDT

-30 to 50

(-34 to 10)

5 (2.8)

140 (60)

1

3/8 x

4-1/16

Outdoor

Shield

Supplied

6

3

X

X

A19AAC-9

Fluid

Cutout

SPDT

100 to 240
(38 to 121)

6 (3.3)

290 (143)

1

3/8 x

3-9/16

WEL14A-

602R

6

3

X

X

A19AAE-3

Crop

Drying

Opens
on rise

80 to 180
(27 to 82)

2 (1.1)

200 (93)

7

1-1/8 x

1-1/4

Copper

Coil

10

X

X

A19ADB-2

Hot

Water

Cutout;
Manual

Reset

Opens
on rise

100 to 240
(38 to 121)

Lockout

290 (143)

2

0.290 x

2-11/16

Direct

Immersion

1/2 in. NPT

Conn.

None

X

X

A19ADN-1

Warm

Air;

Manual

Reset

Opens
on rise

100 to 240
(38 to 121)

Lockout

290 (143)

1

3/8 x 3

WEL14A-

602R

6

3

X

X

A19ADP-1

Warm

Air;

Manual

Reset

SPDT

100 to 240
(38 to 121)

Lockout

290 (143)

1

3/8 x 3

WEL14A-

602R

6

3

X

X

A19BAB-3

Heating

Opens
on rise

30 to 95
(0 to 35)

3 (1.7)

140 (60)

3

Coil

None

X

X

A19BAC-1

Farm

Thermost
at Heat or

Ventilate

SPDT

30 to 110

(0 to 43)

3 (1.7)

140 (60)

3

Coil

None

X

X

A19BAG-1

Portable

Heater

Opens
on rise

35 to 95
(0 to 35)

3 (1.7)

140 (60)

3

Coil

None

X

X

* Maximum bulb temperature which the element can withstand at infrequent intervals during life of control, such as shipping conditions.  This is not the
temperature at which the control can withstand on repeat cycles.

Summary of Contents for A19 Series

Page 1: ...ions a separate back up control with alarm contacts should be wired to indicate when the back up control operates Fig 2 Space thermostat with Style 3 coiled bulb and finger tip adjusting knob Fig 1 Left Control with external range scale knob adjustment Right Interior of model with adjustable differential Features Dependability precision snap acting dusttight contacts Dependability low volume respo...

Page 2: ...s 10 0 6 0 Pilot Duty 125 VA 24 to 600 VAC Specifications Product Range Diff Max Bulb Bulb Bulb Bulb Cap Bulb Cover Range Adjuster Number Appl Action F C F C Temp F C Style Size in Well Length ft Suppor t in Plain Scale Screw driver Knob A19AAB 4 Fluid Cutout Opens on rise 30 to 110 1 to 43 3 1 7 140 60 1 3 8 x 4 15 16 WEL14A 602R 6 3 X X A19AAB 7 Industrial Oven Opens on rise 100 to 300 38 to 149...

Page 3: ...steel Gray baked enamel finish Contact Unit Precision Pennswitch Snap acting dust tight contacts Shipping Weights Shipping weights shown below are approximate Weights vary depending upon construction Generally overpack will contain 25 individually packed controls Individual pack 1 0 lb Overpack containing 25 individually packed units 26 0 lbs Ordering Information 1 Specify Product Number only if a...

Page 4: ...4 A19 Product Bulletin Bulb and Bulb Accessories ...

Page 5: ...A19 Product Bulletin 5 ...

Page 6: ...6 A19 Product Bulletin Notes ...

Page 7: ...A19 Product Bulletin 7 Notes ...

Page 8: ...8 A19 Product Bulletin Notes Controls Group 507 E Michigan Street P O Box 423 Printed in U S A Milwaukee WI 53202 ...