![Tekmar D 262 Data Brochure Download Page 9](http://html1.mh-extra.com/html/tekmar/d-262/d-262_data-brochure_1076392009.webp)
9 of 36
Copyright © D 262 -
12/08
Boosting
(BOOST)
When the control changes from the
UnOccupied to the Occupied mode,
it enters into a
Boosting mode. In this mode, the supply water tempera-
ture to the system is raised above its normal values for a period of time
to provide a faster recovery from the setback temperature of the building.
The maximum length of the
Boost
is selected in the user interface. This
setting is only available if a
Characterized Heating Curve is selected; It
is not available for a
Reset Ratio or if a tekmar Zone Control is used.
Typical settings for the
Boost function vary between 30 minutes and two
hours for a building that has a fast responding heating system. For a
building that has a slow responding heating system, a setting between
four hours and eight hours is typical. After a
Boost time is selected, the
setback timer must be adjusted to come out of setback some time in
advance of the desired
Occupied time. This time in advance is normally
the same as the
Boost setting.
If the building is not up to temperature at the correct time, the
Boost setting should be lengthened and the setback timer should be
adjusted accordingly. If the building is up to temperature before the required time, the
Boost setting should be shortened and the
setback timer should be adjusted accordingly. If the system is operating near its design conditions or if the supply water temperatures
are being limited by settings made in the control, the time required to bring the building up to temperature may be longer than expected.
Section B2 —Alternate Boiler Demands
(Mode = —1—)
In addition to using conventional thermostats to provide a boiler demand as described in Section B1, the 262 can use a number of other
methods to provide a
Boiler Demand.
10K INDOOR SENSOR
(10K = INDR)
Set the
10K
item to
INDR
to add an indoor sensor for temperature control of a single zone boiler
system. The indoor sensor is connected to the
Com and 10K terminals (16 and 17). In addition,
power must be applied to the
Boiler Demand terminals (1 and 2) as described in Section B1.
With the indoor sensor connected, the 262 is able to sense the actual room temperature. With
this information, the 262 provides a more constant water flow through the system. At the same
time, indoor feedback fine tunes the supply water temperature in the system to prevent over
heating or under heating. To adjust the room temperature for the zone, use the
ROOM
Occupied or UnOccupied setting in the Adjust menu at the control.
10K BOILER ZONE CONTROL
(10K = ZoIn)
Set the
10K
item to
ZoIn
to add indoor temperature feedback control of multiple zones. Control
of the zones is provided by connecting a tekmar Zone Control to the
Com and 10K terminals
(16 and 17) of the 262. The zone control provides its own internal
Boiler Demand to the 262.
In this case, there is no need to provide an external
Boiler Demand as described earlier in
Section B1. The zone control is capable of automatically adjusting the
Boil TRG
temperature
to improve building occupant comfort and system performance.
10K SLAB SENSOR
(10K = SLAB)
Set the
10K
item to
SLAB
to add a slab sensor for temperature control of a single zone system.
The 262 can use a slab sensor to control the actual slab temperature. A slab sensor is placed
in the slab and connected to the
Com and the 10K terminals (16 and 17). Power must be
applied to the
Boiler Demand terminals (1 and 2) as described in Section B1. With the slab
sensor connected, the 262 will limit the supply temperature in order to maintain the slab sensor
between the
SLAB MIN
and
SLAB MAX
settings. This application is available only when
Boil MIN
is set to
OFF
.
Slab Min
(SLAB MIN)
The
SLAB MIN
sets the minimum allowed core temperature of the slab as long as the control is not in a
WWSD
. Caution should be
used when adjusting the
SLAB MIN
setting as this may lead to overheating of the zone during mild conditions. If the
AWAY
setting
is selected in the
Schedule menu, the 262 ignores the
SLAB MIN
setting.
Slab Max
(SLAB MAX)
The
SLAB MAX
sets the maximum allowed core temperature of the slab. If the slab is to be maintained at a fixed core temperature,
set
SLAB MAX
and
SLAB MIN
items to the same setting.
ROOM TEMPERATURE UNIT (RTU)
(10K = NONE)
If the system consists of a single zone, temperature control of that zone can be provided by using an RTU. The RTU is connected to
the
Com and tekmar Net
TM
tN1 / tN2 terminals (15 and 16). In addition, power must be applied to the Boiler Demand terminals (1 and
LR 58233
E150539
tekmar
Zone Control
Zone Control 367
One & Two Stage / One Stage & Floating
Power
Heat Required
Zone 2 / Hi stage /
Close / Ventilation
System Pump
24 hr. Timer
• Dial the desired duration
of the UnOccupied period.
• Press start button at the time of day
you want the UnOcc. period to begin.
Timer Active light turns on.
Start
UnOccupied
Duration
0 = always Occupied
24 = always UnOccupied
Zone 1 / Lo stage /
Open / Cooling
2
3
4
1
Zone 4 / Hi stage
Close
Zone 3 / Lo stage
Open
5
6
Zone 6 / Hi stage
Close
Zone 5 / Lo stage
Open
70
°
F
(21
°
C)
40
(4)
100
(38)
UnOccupied
Occupied
Optimum Start / Stop
UnOccupied
Timer Active
0
12 hrs.
24
6
18
tekmar
262 Control
Menu
Item
R
Boiler Control 262
Two Stage Boiler & DHW / Two Stage DHW
LR 58223
N R T L / C
Boiler Demand
DHW Demand
Setpoint Demand
WWSD
Minimum
Maximum
2
1
°
F
Vie
1
Occ
tekmar
262 Control
tekmar
Slab Sensor
Menu
Item
R
Boiler Control 262
Two Stage Boiler & DHW / Two Stage DHW
LR 58223
N R T L / C
Boiler Demand
DHW Demand
Setpoint Demand
WWSD
Minimum
Maximum
2
1
°
F
Vie
1
Occ
UnOcc to Occ
Boost
Boil TRG
(Occupied)
W
ater T
emperature
Time
Boost setting - 20 minutes to 8 hours
Boil TRG
(UnOccupied)
Self Adjusting
Water Temperature
tekmar
Indoor Sensor
tekmar
262 Control
Menu
Item
R
Boiler Control 262
Two Stage Boiler & DHW / Two Stage DHW
LR 58223
N R T L / C
Boiler Demand
DHW Demand
Setpoint Demand
WWSD
Minimum
Maximum
2
1
°
F
Vie
1
Occ