Tekmar D 262 Data Brochure Download Page 9

9 of 36

Copyright © D 262 -

12/08

Boosting 

(BOOST) 

When the control changes from the 

UnOccupied to the Occupied mode,

it enters into a 

Boosting mode. In this mode, the supply water tempera-

ture to the system is raised above its normal values for a period of time
to provide a faster recovery from the setback temperature of the building.
The maximum length of the 

Boost 

is selected in the user interface. This

setting is only available if a

 Characterized Heating Curve is selected; It

is not available for a 

Reset Ratio or if a tekmar Zone Control is used.

Typical settings for the 

Boost function vary between 30 minutes and two

hours for a building that has a fast responding heating system. For a
building that has a slow responding heating system, a setting between
four hours and eight hours is typical. After a 

Boost time is selected, the

setback timer must be adjusted to come out of setback some time in
advance of the desired 

Occupied time. This time in advance is normally

the same as the 

Boost setting.

If the building is not up to temperature at the correct time, the 

Boost setting should be lengthened and the setback timer should be

adjusted accordingly. If the building is up to temperature before the required time, the 

Boost setting should be shortened and the

setback timer should be adjusted accordingly. If the system is operating near its design conditions or if the supply water temperatures
are being limited by settings made in the control, the time required to bring the building up to temperature may be longer than expected.

Section B2 —Alternate Boiler Demands 

(Mode = —1—)

In addition to using conventional thermostats to provide a boiler demand as described in Section B1, the 262 can use a number of other
methods to provide a 

Boiler Demand.

10K INDOOR SENSOR 

(10K = INDR) 

Set the 

10K 

 item to 

INDR

  to add an indoor sensor for temperature control of a single zone boiler

system. The indoor sensor is connected to the 

Com and 10K  terminals (16 and 17). In addition,

power must be applied to the 

Boiler Demand terminals (1 and 2) as described in Section B1.

With the indoor sensor connected, the 262 is able to sense the actual room temperature. With
this information, the 262 provides a more constant water flow through the system. At the same
time, indoor feedback fine tunes the supply water temperature in the system to prevent over
heating or under heating. To adjust the room temperature for the zone, use the 

ROOM

Occupied or UnOccupied setting in the Adjust menu at the control.

10K BOILER ZONE CONTROL 

(10K = ZoIn) 

Set the 

10K 

 item to 

ZoIn

 to add indoor temperature feedback control of multiple zones. Control

of the zones is provided by connecting a tekmar Zone Control to the 

Com and 10K terminals

(16 and 17) of the 262. The zone control provides its own internal 

Boiler Demand to the 262.

In this case, there is no need to provide an external 

Boiler Demand as described earlier in

Section B1. The zone control is capable of automatically adjusting the 

Boil TRG

 temperature

to improve building occupant comfort and system performance.

10K SLAB SENSOR 

(10K = SLAB) 

Set the 

10K 

 item to 

SLAB

 to add a slab sensor for temperature control of a single zone system.

The 262 can use a slab sensor to control the actual slab temperature. A slab sensor is placed
in the slab and connected to the 

Com and the 10K terminals (16 and 17). Power must be

applied to the 

Boiler Demand terminals (1 and 2) as described in Section B1. With the slab

sensor connected, the 262 will limit the supply temperature in order to maintain the slab sensor
between the 

SLAB MIN

 and 

SLAB MAX

 settings. This application is available only when

Boil MIN 

is set to 

OFF

.

Slab Min 

(SLAB MIN) 

The 

SLAB MIN

 sets the minimum allowed core temperature of the slab as long as the control is not in a 

WWSD

. Caution should be

used when adjusting the 

SLAB MIN

 setting as this may lead to overheating of the zone during mild conditions. If the 

AWAY

 setting

is selected in the 

Schedule menu, the 262 ignores the 

SLAB MIN

 setting.

Slab Max 

(SLAB MAX) 

The 

SLAB MAX

 sets the maximum allowed core temperature of the slab. If the slab is to be maintained at a fixed core temperature,

set 

SLAB MAX 

and 

SLAB MIN

 items to the same setting.

ROOM TEMPERATURE UNIT (RTU) 

(10K = NONE) 

If the system consists of a single zone, temperature control of that zone can be provided by using an RTU. The RTU is connected to
the 

Com and tekmar Net

TM

 

tN1 / tN2 terminals (15 and 16). In addition, power must be applied to the Boiler Demand terminals (1 and

LR 58233

E150539

tekmar

Zone Control

Zone Control 367

One & Two Stage / One Stage & Floating

Power

Heat Required

Zone 2 / Hi stage /
Close / Ventilation

System Pump

24 hr. Timer

• Dial the desired duration
of the UnOccupied period.
• Press start button at the time of day
you want the UnOcc. period to begin.
Timer Active light turns on.

Start

UnOccupied

Duration

0 = always Occupied
24 = always UnOccupied

Zone 1 / Lo stage /
Open / Cooling

2

3

4

1

Zone 4 / Hi stage
Close

Zone 3 / Lo stage
Open

5

6

Zone 6 / Hi stage
Close

Zone 5  / Lo stage
Open

70

°

F

(21

°

C)

40
(4)

100
(38)

UnOccupied

Occupied

Optimum Start / Stop

UnOccupied

Timer Active

0

12 hrs.

24

6

18

tekmar

262 Control

Menu

Item

R

Boiler Control 262

Two Stage Boiler & DHW / Two Stage DHW

LR 58223

N R T L / C

Boiler Demand

DHW Demand

Setpoint Demand

WWSD

Minimum

Maximum

2

1

°

F

Vie

1

Occ

tekmar

262 Control

tekmar

Slab Sensor

Menu

Item

R

Boiler Control 262

Two Stage Boiler & DHW / Two Stage DHW

LR 58223

N R T L / C

Boiler Demand

DHW Demand

Setpoint Demand

WWSD

Minimum

Maximum

2

1

°

F

Vie

1

Occ

UnOcc to Occ

Boost

Boil TRG

 (Occupied)

W

ater T

emperature

Time

Boost setting - 20 minutes to 8 hours

Boil TRG

 (UnOccupied)

Self Adjusting

Water Temperature

tekmar

Indoor Sensor

tekmar

262 Control

Menu

Item

R

Boiler Control 262

Two Stage Boiler & DHW / Two Stage DHW

LR 58223

N R T L / C

Boiler Demand

DHW Demand

Setpoint Demand

WWSD

Minimum

Maximum

2

1

°

F

Vie

1

Occ

Summary of Contents for D 262

Page 1: ...ral energy saving features have been incorporated into the 262 such as Warm Weather Shut Down WWSD DHW post purge system setback DHW priority and an automatic differential for boiler operation LR 5823...

Page 2: ...available menu Once a menu is selected there will be a group of items that can be viewed within that menu Item The abbreviated name of the selected item will be displayed in the item field of the disp...

Page 3: ...in sec DHW 12 1 DHW Burner Displays when the stage 1 and or stage 2 relay is turned on Pump Displays when the boiler pump is operating DHW Pump Displays when the DHW pump is on Warning Displays when a...

Page 4: ...trolerrorisdeterminedusingProportional Integral and Derivative PID logic Proportional compares the actual supply temperature to the boiler target Boil TRG temperature The colder the supply water tempe...

Page 5: ...2 automatically determines the best differential as the load changes This reduces potential short cycling during light loads STAGE 1 2 STAGE The stage 1 and 2 setting may be selected to AUTO or OFF Wh...

Page 6: ...General Boiler Operation BOILER DEMAND A boiler demand is generated by applying a voltage between 24 and 240 V ac across the Boil Dem 1 2 terminals Once voltage is applied the Boiler Demand pointer i...

Page 7: ...viewed Atnotimedoesthecontroloperatetheboiler s above248 F 120 C WARM WEATHER SHUT DOWN WWSD OCC UNOCC RESET RATIO CHARACTERIZED HEATING CURVE When the outdoor air temperature rises above the WWSD se...

Page 8: ...encased in fins This type of terminal unit relies on the natural convection of air across the heating element to deliver heated air into the space The amount of natural convection is dependant on the...

Page 9: ...d to provide an external Boiler Demand as described earlier in Section B1 The zone control is capable of automatically adjusting the Boil TRG temperature to improve building occupant comfort and syste...

Page 10: ...TANK temperature and record the highest and lowest DHW TANK temperatures Also the 262 can control the DHW temperature with more accuracy than when using an aquastat DHW DEVICE DHW THRU Once the 262 re...

Page 11: ...s will be the only pump providing flow through the boiler s DHW PRIORITY OVERRIDE To prevent the building from cooling off too much or the possibility of a potential freeze up during DHW priority the...

Page 12: ...he 262 turns off the boiler pump P1 flow to the heating system must stop If flow is not stopped the temperature in the heating system can exceed the maximum desired temperature and can result in damag...

Page 13: ...rmally If a system override of AWAY is selected the 262 operates the SETPOINT load at the Occupied setting SETPOINT PRIORITY SETP PRI BOIL For setpoint loads to have priority over the boiler zone s se...

Page 14: ...l the Outdoor Sensor 070 and Boiler Sensor 071 according to the instructions in the Data Brochure D 070 and run the wiring back to the control If a DHW Sensor 071 is used install the DHW Sensor accord...

Page 15: ...ontrol These terminals are to be used as a switch to either make or break power to the DHW pump or the DHW valve Since this is an isolated contact it may switch a voltage between 24 V ac and 240 V ac...

Page 16: ...ernal timer tekmar Timer 032 or switch is used connect the two wires from the external switch to the Com and UnO Sw terminals 16 and 18 When these two terminals are shorted together the control regist...

Page 17: ...Power N and Power L terminals 6 and 7 the boiler pump should start If the pump does not turn on check the wiring between the terminal block and pump and refer to any installation or troubleshooting in...

Page 18: ...levels To lock the access level select the appropriate access level in the Miscellaneous Misc menu and move the DIP switch from the Unlocked position to the Locked position As long as the DIP switch...

Page 19: ...us Misc menu when the Lock Unlock DIP switch is set to the Unlocked position In the Advanced access level all of the control settings are available to the user In the User access level only a few of t...

Page 20: ...F 50 to 75 C This is the signal that is being received from a tekmar Zone Control 10K ZoIn MODE 1 35 to 110 F 2 to 43 C Current slab sensor temperature 10K SLAB MODE 1 Boil MIN OFF 58 to 167 F 50 to...

Page 21: ...8 00 hr Default OFF The maximum temperature at the slab sensor DIP switch Characterized Heating Curve No RTU connected 10K SLAB Boil MIN OFF MODE 1 The amount of morning boost DIP switch Characterized...

Page 22: ...eating system DIP switch Reset Ratio MODE 1 The time delay the control can expect between the time the boiler contact closes and the burner fires 0 00 to 3 00 min in 1 sec increments Default 0 10 min...

Page 23: ...hether or not DHW will be generated during the UnOccupied period DIP switch Setback DHW SENS NONE DHW THRU NONE OFF 100 to 220 F OFF 38 to 104 C Default 180 F 82 C OFF DHW XCHG Occ setting Default OFF...

Page 24: ...by the control S e c t i o n 262 Adjust Menu 4 of 4 The system s warm weather shut down during the UnOccupied period DIP switch Setback MODE 1 The maximum length of time that the boiler pump will con...

Page 25: ...0 sec ON Default ON ADV INST USER LTD Default INST The units of measure that all of the temperatures are to be displayed in by the control The operating mode for the back lighting on the LCD as well a...

Page 26: ...air temperature during an UnOccupied period for the heating zone Note There is only a 3 F adjustment in the LTD access level DIP switch Setback 35 to 100 F 2 to 38 C Default 65 F 18 C OFF 0 20 to 8 00...

Page 27: ...in the display turn on Step 1 The boiler pump Boil P1 is turned on for 10 seconds NOTE Only if there is a boiler demand can the control be paused in step 1 Step 2 The zccontact is turned on for 10 se...

Page 28: ...Boil P1 contacts are shut off NOTE Only if there is a boiler demand can the control be paused in step 3 Step 4 MODE 1 If a DHW Pump is selected as the DHW device the DHW Pmp Vlv contact is turned on...

Page 29: ...al contacts on the control are opening and closing correctly Follow the instructions in the Testing the Wiring section to simulate closed contacts on the terminal blocks as required Test the sensors a...

Page 30: ...that Stage 1 has had since this item was last cleared This item can be used in conjunction with the B1 FIRE item to determine the average cycle length of Stage 1 If the cycle length is too short a lo...

Page 31: ...he control and the RTU or RDM are run in a noisy electrical environment this can cause interference in communication between the control and the RTU or RDM MODE 1 3 to 40 min OFF Default OFF 0 255 0 2...

Page 32: ...st be ADV in order to clear the error The RTU was unable to read a piece of information stored in the Schedule menu Because of this the control was required to load the factory settings into all of th...

Page 33: ...is error message can be cleared once the sensor has been repaired To clear the error message from the control press either the Menu or Item button The air sensor in the RTU is being read as an open ci...

Page 34: ...ot connected to the control This error message can be cleared once the sensor has been repaired Locate and repair the problem as described in the Data Brochure D 070 To clear the error message from th...

Page 35: ...35 of 36 Copyright D 262 12 08 Notes...

Page 36: ...sub sequent to purchase which have not been authorized by tekmar or if the product was not installed in compliance with tekmar s instructions and the local codes and ordinances or if due to defective...

Reviews: