20 of 36
Copyright © D 262 -
12/08
Minimum boiler supply temperature during a setpoint
demand.
MODE = —1—
262
View
Menu (1 of 1)
-31 to 266˚F
(-35 to 130˚C)
- - -, OFF, 70 to 220˚F
(OFF, 21 to 104˚C)
Current DHW tank temperature.
DHW SENS = DHW
DHW THRU
≠
NONE
Section
•
•
•
•
•
•
Current outdoor air temperature as measured by the outdoor
sensor. This is the default display for the control.
MODE = —1—
-67 to 149˚F
(-55 to 65˚C)
•
•
•
•
Target room air temperature. “– – –” denotes no heat is
required.
10K = INDR
MODE = —1—
- - -, 35 to 100˚F
(2 to 38˚C)
•
•
•
Measured room air temperature at the indoor sensor.
10K = INDR
MODE = —1—
-58 to 167˚F
(-50 to 75˚C)
•
•
•
•
This is the signal that is being received from a tekmar Zone
Control.
10K = ZoIn
MODE = —1—
- - -, 35 to 110˚F
(2 to 43˚C)
•
Current slab sensor temperature.
10K = SLAB
MODE = —1—
Boil MIN = OFF
-58 to 167˚F
(-50 to 75˚C)
•
•
Target boiler supply is the temperature the control is currently
trying to maintain at the boiler /- 1/2 of the
differential.
- - -, 35 to 248˚F
(2 to 120˚C)
•
•
Current boiler supply water temperature as measured by
the boiler sensor.
-31 to 266˚F
(-35 to 130˚C)
•
•
•
Minimum boiler supply temperature during a DHW demand.
DHW SENS = NONE
DHW THRU
≠
NONE
- - -, OFF, 100 to 220˚F
(OFF, 38 to 104˚C)
•
•
Target DHW tank temperature.
DHW SENS = DHW
DHW THRU
≠
NONE
- - -, OFF, 70 to 190˚F
(OFF, 21 to 88˚C)
•
•
•
LT
D
USER
INST
ADV
Range
Access
Level
Description
Item Field
B2
B2
B2
B2
B1
B1
C1
C1
C1
D1