background image

Teikoku USA | Chempump

Instruction Manual HE-12270 (1219)

10

 

starved for liquid during operation. NPSH problems are a result of 
improper suction systems.

The suction pipe should be one or two sizes larger than pump 
suction port, depending on piping length. Use the largest pipe 
size practical on suction piping and keep piping short and free 
from elbows, tees or other sources of pressure drop.

If elbows, tees or valves must be used, locate them from 5 to 
10 pipe diameters upstream from the pump suction inlet. When 
reducing to pump suction port diameter, use eccentric reducers 
with flat side on top to avoid air pockets.

A vent line back to the suction vessel is required in the discharge 
pipe. The connection for the vent line in the discharge pipe must 
be between the pump discharge flange and the first block valve 
and/or check valve. Install a block valve in the vent line. When a 
solenoid valve is used for the start vent, program the solenoid 
valve to be open when the pump is off and closed when the 
pump is on. Refer to 

Appx. D

 piping layout for the Type-F (Plan 

1-SD) pressurized circulation ALP multi-stage pump. 

If discharge pipe length is normal, pipe diameter can be the same 
size as the pump discharge port diameter. If discharge piping is 
of considerable length, use one or two size larger diameter pipe.

If the pump is to discharge into a closed system, an elevated tank 
or if there are multiple pumps connected together, place a check 
valve in the discharge line close to the pump. 

NOTE: 

Install properly sized pressure gauges in suction and dis-

charge lines between the pump and the first block and/or check 
valve so that operation of the pump and system can be easily 
observed. Should cavitation, vapor lock, or unstable operation oc-
cur, widely fluctuating discharge pressures will be observed. Such 
gauges provide a positive means of determining actual system 
conditions and can be used to great advantage in evaluating sys-
tem problems.

2.3  Electrical and Instrumentation

2.3.1  TRG Bearing Wear Monitor

The TRG is an electrical meter that continuously monitors the con-
dition of the bearings. The TRG is mounted on the electrical junc-
tion box as standard.

The TRG meter operates on the principle of induced voltage. 
There are two TRG coils located inside the stator 180° apart. A 
magnetic field is created in the stator by current flowing through 
the stator windings. In addition, a magnetic field is created by 
induced currents in the rotor. When the rotor is perfectly centered 
in the stator, the two magnetic fields are essentially balanced. 
When bearing wear occurs and the gap between the rotor and 
stator decreases, an imbalance in the magnetic fields causes a dif-
ferential induced voltage in the TRG coils. This differential voltage 
is indicated on the TRG voltmeter.

The initial display of the TRG meter is adjusted in the Teikoku 
factory, but each meter will show subtle differences. To check  
bearing wear using the TRG meter, use the color change (Green, 
Yellow, Red) as a reference. If the increase of TRG readings is 0.3 
or more, stop the pump and check bearings.

The Teikoku Rotary Guardian (TRG) signal is affected by motor 
load. Changes in operating frequency or hydraulic load may in-
crease or decrease signal. 

Keeping records of the TRG meter reading in conjunction with 
motor amp readings will provide a good indication of when the 
pump will require maintenance.

Figure 2-1. Teikoku TRG Bearing Wear Monitor

Table 2-1. Conditions Indicated on the TRG Meter

The TRG meter has a colored scale which is divided into three zones: Green (0 to 0.5), Yellow (0.5 to 0.75), Red (0.75 to 1)

AT TRIAL OPERATION

DURING OPERATION

Indication

Condition

Solution

Indication

Diagnosis

User Actions

Full scale or 1-Volt

incorrect wiring

change power cable 
connection

Green

Good

No action

Yellow to Red

phase failure

check connection of 
cables

Yellow or voltage increase of  

> 0.3 V from initial indication

Bearings worn to 

caution level

Plan routine 

maintenance

Green

normal

connection is correct

Red or voltage increased of  

> 0.5 V from initial indication

Immediate 

maintenance required

Shutdown immediately 

and replace worn parts

Hazard! 

Do not operate if TRG meter condition is RED.

Summary of Contents for ALP 0104QM

Page 1: ...NSTRUCTION MANUAL for Installation Operation and Maintenance HE 12270 December 2019 ALPTM ADVANCED LOW PROBABILITY AMMONIA TRANSFER PUMP TYPE F Plan 1 SD 0104QM Multi Stage Pressurized Circulation Pum...

Page 2: ...F Plan 1 SD pressurized circulation ALP multi stage pump conforms to the following standards 1 Japanese Industrial Standard JIS 2 Japan Electrical Manufacturers Standard JEM 3 American Society of Mec...

Page 3: ...e or liquid is present You must take measures if the possibility exists that the gas or liquid is toxic or hazardous to personnel or the environment Hazard Do not remove any bolts on pump motor or dra...

Page 4: ...nel 35 Appx P Decontamination Form 36 Appx Q Teikoku Pump Repair Policy 39 Figures Figure 1 1 Type F Plan 1 SD Pressurized Circulation ALP Multi stage Pump 6 Figure 1 2 Flow Path 7 Figure 1 3 Typical...

Page 5: ...nonymous with all Teikoku pump solutions Driven by any commercially available variable frequency drive VFD Type F Plan 1 SD pressurized circulation ALP multi stage pumps feature advanced hydraulics fo...

Page 6: ...ed above its vapor pressure to assure required motor cooling and the estab lishment of the bearing liquid film for rotating element support The flow path of the Type F Plan 1 SD pressurized circulatio...

Page 7: ...ti stage pump are carbon graphite as standard and are machined with special helix grooves through the bore to assure adequate liquid circulation at the journal area Each liquid film journal bearing is...

Page 8: ...219 8 Figure 1 3 Typical NH3 Transfer System Requirements HIGH LEVEL LOW LEVEL ISOLATION VALVE ISOLATION VALVE CHECK VALVE CANNED MOTOR PUMP PLAN 1 SD PRESSURE GAUGES DISCHARGE VENT TO SAFETY START VE...

Page 9: ...insufficient NPSH The suction line must have as few pressure drops as possible and available NPSH MUST be greater than required NPSH Depending on job conditions available NPSH can sometimes be increa...

Page 10: ...TRG Bearing Wear Monitor The TRG is an electrical meter that continuously monitors the con dition of the bearings The TRG is mounted on the electrical junc tion box as standard The TRG meter operates...

Page 11: ...ds or less Upper Limited Frequency 120Hz 120Hz Lower Limited Frequency 60Hz or Start Hz 60Hz or Start Hz Starting Frequency See note See note V F Control Variable Torque Variable Torque PWM Carrier Fr...

Page 12: ...g current times 1 25 Attention Do not set the thermal overload protective device at more than the full load amps FLA listed on the name tag 3 2 2 Setting of Overload Relay Because of the rated electri...

Page 13: ...continuously cavitate the pump Attention The pump should not be allowed to run for more than one minute with the discharge valve fully closed Attention Wait a minimum of 10 minutes between starts Aft...

Page 14: ...ome cases the liquid supply may contain an excessive amount of air or gas which will tend to separate from the liquid and re main in the passages of the pump This results in the pump losing its prime...

Page 15: ...lation pipe bolting Remove circulation pipe ori fice plate and gaskets 9 Remove front support foot 10 Remove casing bolts and slide casing off Be careful not to al low the casing to bind to or drop on...

Page 16: ...neral ap pearance and uniform wear Excessive undercutting pitting or scoring is cause for replace ment Check the following points 1 Corrosion 2 Contact marks and wear 4 3 3 Rotor Assembly Inspection T...

Page 17: ...ng housing onto the rotor shaft and slide the rear bearing hous ing and rotor into the stator Tighten bolting evenly using a star or cross pattern Torque bolts per Table 4 5 14 Slide front bearing hou...

Page 18: ...2 Install pipe casing gasket Install pipe casing Install cap screws Tighten bolting evenly using a star or cross pattern Torque bolting per Table 4 5 33 Install o ring on diffuser plate 34 Install cas...

Page 19: ...Play Motor Frame Number End Play Inch mm 216 217 0 043 0 067 1 1 1 7 316 See Figure 4 5 4 5 Service Policy Any Teikoku USA product damaged or inoperative for any rea son can be repaired at the Teikok...

Page 20: ...Information Sheet 26 Appx G NH3 Reference Curve 20 F 27 Appx H NH3 Reference Curve 50 F 28 Appx I Type 217 120 Motor Data Sheet 29 Appx J 1 SD Temperature Pressure Profile 30 Appx K Optional Rotor Ca...

Page 21: ...ure NA UTILITIES REQUIRED Water Jacket Fluid NA Flow NA Pressure NA Temperature NA Heat Exchanger Fluid NA Flow NA Pressure NA Terminal Box Connection Diag DRAWINGS Perf Curve Cross Section Outline 46...

Page 22: ...Teikoku USA Chempump Instruction Manual HE 12270 0219 22 Containment Reliablity Safety by Design CHEMPUMP TEIKOKU USA INC Appx B Outline F 210P 0104Q 1 SD...

Page 23: ...Shaft Sleeve 18A Thrust Collar 18B Thrust Collar 19 Rotor Assembly 20 Stator Assembly 21 Rotor Can 22 Stator Can 24 Terminal Box Ass y 32 F B Housing 34 Circulation Pipe 39A Stand Asesmbly 40 Base 41...

Page 24: ...pe to the vapor zone in the suction tank c Never install a check valve in the vent pipe d The vent pipe must be continuously rising to the suction tank e This line must never be down slope at any poin...

Page 25: ...er Wrong direction of rotation Reverse any two motor leads Damaged impeller Impeller must be repaired or replaced Pump loses prime after starting Pump not properly primed at starting Reprime pump in a...

Page 26: ...e takes the guesswork out of confirming the correct rotation of the motor It is light compact and easy to use Not only can this be used on Teikoku canned motors but other three phase induction motors...

Page 27: ...0 A S G 0 65 Vis 0 18 cp Aqueous NH3 Estimated Performance Curve 20 F 120 Hz 100 Hz 80 Hz 60 Hz 0 2 4 6 8 10 12 Input Power kW 120 Hz 100 Hz 80 Hz 60 Hz 0 1 2 3 4 5 0 5 10 15 20 25 30 35 40 NPSHr ft...

Page 28: ...0 A S G 0 70 Vis 0 31 cp Estimated Performance Curve 50 F Aqueous NH3 REV Date Description APPROVED BY CHEKED BY DRAWN BY TEIKOKU USA INC 120 Hz 100 Hz 80 Hz 60 Hz 0 2 4 6 8 10 12 Input Power kW 120 H...

Page 29: ...150 kW 0 0 2 0 4 1 6 1 8 1 10 1 12 2 Current A 5 9 8 0 11 0 14 8 21 0 26 4 Input kW 1 64 3 72 5 90 8 24 10 83 14 04 Power Factor 42 4 71 0 81 5 84 9 84 8 80 8 Efficiency 0 0 54 5 68 6 73 7 74 8 72 1...

Page 30: ...ria 0 0 0 0 0 0 Judgement Good Good Good Good Good Good Higher flow and speeds and lower temperatures will increase NH3 Pressure Margins Maximum flow rate at minimum frequency for Anhydrous Ammonia 20...

Page 31: ...Teikoku USA Chempump Instruction Manual HE 12270 0219 31 Appx K Optional Rotor Cavity Thermowell Containment Reliablity Safety by Design CHEMPUMP TEIKOKU USA INC...

Page 32: ...Teikoku USA Chempump Instruction Manual HE 12270 0219 32 A B C Containment Reliablity Safety by Design CHEMPUMP TEIKOKU USA INC 5 of 13 Appx L Terminal Box Assembly...

Page 33: ...Teikoku USA Chempump Instruction Manual HE 12270 0219 33 Containment Reliablity Safety by Design CHEMPUMP TEIKOKU USA INC Appx M Allowable Piping Forces and Moments...

Page 34: ...Teikoku USA Chempump Instruction Manual HE 12270 0219 34 Appx N Optional TSG NH3 Speed Control Panel...

Page 35: ...POSITIVE VOLTAGE BLK BLACK WIRE VDC COMMON VOLTAGE ALL FIELD WIRING TO BE 14 AWG UNLESS OTHERWISE SPECIFIED CONSULT MANUFACTURER S WIRING RECOMMENDATION FOR TYPE SIZE AND TERMINATION REQUIREMENT AS R...

Page 36: ...p has been flushed by following steps A through Both the complete pump and the stator assembly have A3 of the Teikoku USA Flushing Procedure on page 2 of been flushed by following steps A through B3 o...

Page 37: ...REWOUND B1 REMOVE THE RELIEF VALVE INSERT A SCREWDRIVER INTO THE RELIEF VALVE ADAPTER AND PRY THE LISK FILTER TO ONE SIDE REMOVE THE CONNECTION BOX FROM THE LEAD NIPPLE AND CHIP AWAY THE POTTING COMPO...

Page 38: ...E COVER AND THE TERMINAL PLATE D2 WHEN PROCESS FLUID IS IN STATOR WINDING SUPPLY FLUSHING FLUID TO THE OPENING FOR SUFFICIENT TIME TO FULLY NEUTRALIZE THE PROCESS FLUID AFTER WASHING IS COMPLETED DRAI...

Page 39: ...RM BOTH THE CARRIER AND CUSTOMER OF THE REFUSAL These requirements are essential to Teikoku USA s safety practices and reviews that serve to protect all of Teikoku USA s associates visitors and custom...

Page 40: ...nsylvania 959 Mearns Road Warminster PA 18974 215 343 6000 Texas 5889 Bingle Road Houston TX 77092 713 983 9901 Ohio 27881 State Route 7 Marietta OH 45750 740 538 5332 www teikokupumps com HE 12270 02...

Reviews: