TECSYSTEM VRT200 Instruction Manual Download Page 3

VRT200

 

 
 

 

 

 

 

 

 

 

                     ATTENTION:

 

 

Read the manual carefully before starting to use the control unit. Keep the instructions for future reference. 
 
 

                      Do not open the device, touching any internal components can cause electric shock. Contact with 230 Volts  
            AC  can be fatal. To reduce the risk of electric shock, do not dismantle the back of the device for any reason. Moreover  
           its opening would void the warranty. 
 

Before connecting the device to the power supply, make sure that all the connections are correct. 

Always         

disconnect the unit from the supply before any cabling modification.

 

                Any intervention on the equipment must be entrusted to a qualified repair engineer.

 

         Failure to comply with these instructions can cause damages, fires or electric shock, and possible serious injuries! 

 

POWER SUPPLY

 

 

The VRT200 series can be supplied by 230Vac 50/60Hz . 
Before using it, make sure the power cable is not damaged, kinked or pinched. Do not tamper with the power cable. Never 
disconnect the unit by pulling the cable, avoid touching the pins. Do not carry out any connecting/disconnecting with wet 
hands. To disconnect the device, do not use objects such as levers. Immediately disconnect the device if you smell burning 
or see any smoke: contact technical service.  

 

LIQUIDS

 

Do not expose the equipment to splashes or drops, do not position it in places with humidity exceeding 90% and never touch 
with wet or humid hands during storms. If any liquid penetrates the control unit, disconnect it immediately and contact 
technical service. 

 
CLEANING 

Disconnect the power cable before cleaning the control unit, use a dry cloth to dust it, without any solvent or detergents, and 
compressed air. 

 
OBJECTS 

Never insert any objects into the cracks of the control unit. If this happens, disconnect the control unit and  
contact an engineer. 

 
USE RESERVED TO QUALIFIED PERSONNEL 

The purchased goods are a sophisticated electronic device that is totally unsuitable to be used by non-qualified personnel. 
Any intervention must be carried out by a specialist engineer. 

 
ACCESSORIES 

The use of non-original accessories or spare parts might damage the unit and endanger users' safety.  In the event of faults, 
contact technical service. 

 
LOCATION 

Install the control unit indoors, in a place protected from water splashes and sun rays. Do not place near heat sources 
exceeding the parameters stated in this manual. Position on a stable surface, far from any possible vibrations. Position the 
unit as far as possible from any intense magnetic fields. 

 
REPAIRS 

Do not open the control unit. For any fault, always use qualified personnel. The opening of the control unit and/or the removal 
of the series identifying label entails the automatic forfeiture of the warranty. The Warranty seal is applied to all devices, any 
attempt to open the unit would break the seal and cause the consequent automatic forfeiture of the warranty. 

 
 

TECHNICAL INFORMATION  

 

Mail: [email protected] — tel: 02/4581861

 

 SAFETY REQUIREMENTS 

3

 

Summary of Contents for VRT200

Page 1: ...es with ISO9001 certified quality system http www tecsystem it R 1 4 07 11 16 Translations of the original instructions TECSYSTEM S r l 20094 Corsico MI Tel 39 024581861 Fax 39 0248600783 VRT200 INSTRUCTION MANUAL ENGLISH ...

Page 2: ... IS VALID AND COMPLETE FOR THE UNIT VRT200 PAGE 1 SAFETY REQUIREMENTS 3 2 ACCESSORIES 4 3 TECHNICAL SPECIFICATIONS 5 4 FRONT PANEL 7 5 INSTALLATION 8 6 ELECTRICAL CONNECTIONS 9 VRT200 BACK POWER SUPPLY 10 OPERATION HOW TO CHECK THE ALARM STATUS HOW TO RESET A MOTOR IN ALARM OPERATION WITH BAR 400 or 600 OPERATION WITH FANS NOT TECSYSTEM 7 PROGRAMMING 11 8 WARRANTY CONDITIONS 12 9 TROUBLESHOOTING 1...

Page 3: ...humid hands during storms If any liquid penetrates the control unit disconnect it immediately and contact technical service CLEANING Disconnect the power cable before cleaning the control unit use a dry cloth to dust it without any solvent or detergents and compressed air OBJECTS Never insert any objects into the cracks of the control unit If this happens disconnect the control unit and contact an...

Page 4: ... 2 Supply and relay terminal 3 poles pitch 5 Code 2PL0367 Screws tightening torque 0 5Nm 1 PTC line connection terminal 3 poles 1 motor line terminal 4 poles pitch 5 Code 2PL0369 Screws tightening torque 0 5Nm 1MN0030 REV 2 ATTENTION always install the device using the terminals included in the pack The use of terminals other than those included with the control unit might cause malfunctions ACCES...

Page 5: ...0Vac max 10 A max 50 60 Hz NO Connections on removable terminal strips OUTPUTS 1 fault sensor or operating failure FAULT relay SPDT Output relay with 5A 250Vac res COSФ 1 contacts 2 M1 M2 outputs 250Vac max 10 5A max 50 60Hz SPST DIMENSIONS 100x100 mm din43700 depth 131mm terminal block included Hole 92 x 92 mm TEST AND PERFORMANCE Construction in compliance with CE regulations Protection from ele...

Page 6: ...ng NORYL 94 _V0 Absorption 5VA max Protection treatment of the electronic part Option Front polycarbonate IP65 DISPLAY AND DATA MANAGEMENT LED s alarm undercurrent overcurrent overtemp aux stop only on VRT200 LED s running remote local LED s prg setting cal Initial AUTO TUNING to set up motors operation Front button to START STOP motors locally Front alarm RESET button Access to programming throug...

Page 7: ...r in over current LED red 5 M2 motor in under current LED yellow 15 Current variation LED yellow 6 Fixing block 16 Fans local management LED red 7 Fans local START STOP button 17 Fans remote control LED green 8 Fans control mode REM LOC button REMOTE or LOCAL 18 Programming selection LED yellow In d start d trip 9 ENT RESET button alarm reset and programming data selection 19 Monitoring delay LED ...

Page 8: ...2 1 3 1MN0063 REV 0 1 Control unit 2 Panel hole dimensions 0 8mm tolerance 3 Identification label Fix the unit securely with the blocks supplied 1 2 3 4 1MN0008 REV 0 1 Control unit 3 Fixing screw 2 Fixing block 4 Crosshead screwdriver 1X100mm MOUNTING 8 ...

Page 9: ... line supply 230V 10 50 60 Hz 10 Amp max 2 Remote enabling contact ENABLE 5 FAULT relay fault signal 3 M1 M2 motor line connection 5A max Note with the power to the unit ON the FAULT relay switches contacts 8 9 open NO and 7 9 closed NC FAULT 8 9 NC ALARM FAULT OR POWER OFF FAULT 7 9 NC POWER ON ELECTRICAL CONNECTIONS 7 8 9 7 8 9 9 ...

Page 10: ...r stopped due to over current Under current LED ON motor working under current alarm signal Over and under current LEDs ON overtemp aux stop overtemperature alarm Under current LED flashing motor disconnected while auto tuning Over current LED ON motor consumption 5 5A immediate trip without any delay All LEDs flashing corrupted memory error ech press reset and repeat the programming procedure N B...

Page 11: ......

Page 12: ... the M2 line 8 VRT200 Enabling or disabling PTC inputs LEDS ON PTCs enabled LEDs ON PTC disabled N B if the PTC sensors are not connected the function must be disabled Default disabled 9 Motor start for automatic calibration CAL LED ON To perform the automatic calibration all motors must be connected as per final configuration At the START the motors are switched ON for 60 seconds the CAL LED flas...

Page 13: ...evice M1 or M2 under current yellow LED ON Check the condition of the fans the cables and the supply Re program the device All the LEDs are flashing Memory error press RESET and repeat the programming procedure All the LEDs are ON Likely microcontroller fault return the device to Tecsystem for repair Contact TECSYSTEM Technical Department if the problem persists European directives 2012 19 EC WEEE...

Page 14: ...VRT200 USEFUL CONTACTS TECHNICAL INFORMATION ufficiotecnico tecsystem it SALES INFORMATION info tecsystem it 13 ...