POWER SUPPLY

 

 

The VRT200 control unit must be supplied with 230Vac 

±

10% 50/60Hz, check the connection diagrams on pages 9 

and 10. 

A variation in the network voltage of over 10% might cause alarms because of the current variation in the load. 

 

If the electrical system is affected by harmonic frequencies, alarm warnings might be triggered because of the 
consequent variation in the current absorbed by the motors. 

 

It is good practice to make sure that the level of system harmonics is not such as to cause malfunction or damages to 
all the connected electrical and electronic instruments, in compliance with the regulations in force for the type of 
system. 

 
 

OPERATION

 

 

When switched on, the device carries out a LAMP TEST and is set either in REMOTE or LOCAL mode, according to 
how it was set before being switched off. 

 

In REMOTE mode the fans are activated when contact 52-53 closes, which must be connected to the FAN contact of 
the temperature control unit. 

 

In LOCAL mode the fans are activated by pressing the <START-STOP> button. The status of operation is stored in 

case of power failure. 

 

HOW TO CHECK THE ALARM STATUS

 

 

 

Running LED OFF: 

no ventilation activation control 

 

Running LED ON: 

REMOTE or LOCAL ventilation activation 

 

Over- and under-current LEDs OFF: 

motor operating correctly 

 

Over-current LED ON: 

motor stopped due to over-current 

 

Under-current LED ON: 

motor w under-current alarm signal 

 

Over- and under-current LEDs ON + overtemp aux stop: 

overtemperature alarm  

 

Under-current LED flashing: 

motor disconnected while auto-tuning 

 

Over-current LED ON: 

motor consumption >5.5A (immediate trip without any delay) 

 

All LEDs flashing: 

corrupted memory error (ech); press reset and repeat the programming procedure 

 

 

N.B.: 

A motor in a state of alarm or the interruption of supply to the device make contacts 8-9 of the FAULT relay close. 

 

 

HOW TO RESET A MOTOR IN ALARM

 

 

To reset an alarm due to under-current, over-current, overtemp-aux, press the RESET button after carrying out the 
necessary checks and any repairs might be required. 

 

             OPERATION WITH BAR 400 OR 600 

 

 

The 400 and 600 bars are fitted with low current variation motors in case of a motor block. 

To optimise the operation 

of the VRT200 control unit with these bars, we recommend the alarm threshold is programmed at 5%. 
 
 

             OPERATION WITH FANS NOT TECSYSTEM 

  

           The proper functioning of the VRT unit is guaranteed only for: fans with current absorption between 250mA  
           (IN MAX 20%) or 300mA (IN MAX 30%) and 5A , single phase, single speed and power variation is not  
           greater than ± 10%. 

 
 
 

                           IMPORTANT NOTE: if an existing control unit must be replaced with a new one, to guarantee  
           its correct and safe operation, all the connecting terminals must be replaced with the new terminals supplied, 
          on condition the brand of the new terminals is different from the one of the previously installed ones. 

10

 

Summary of Contents for VRT200

Page 1: ...es with ISO9001 certified quality system http www tecsystem it R 1 4 07 11 16 Translations of the original instructions TECSYSTEM S r l 20094 Corsico MI Tel 39 024581861 Fax 39 0248600783 VRT200 INSTRUCTION MANUAL ENGLISH ...

Page 2: ... IS VALID AND COMPLETE FOR THE UNIT VRT200 PAGE 1 SAFETY REQUIREMENTS 3 2 ACCESSORIES 4 3 TECHNICAL SPECIFICATIONS 5 4 FRONT PANEL 7 5 INSTALLATION 8 6 ELECTRICAL CONNECTIONS 9 VRT200 BACK POWER SUPPLY 10 OPERATION HOW TO CHECK THE ALARM STATUS HOW TO RESET A MOTOR IN ALARM OPERATION WITH BAR 400 or 600 OPERATION WITH FANS NOT TECSYSTEM 7 PROGRAMMING 11 8 WARRANTY CONDITIONS 12 9 TROUBLESHOOTING 1...

Page 3: ...humid hands during storms If any liquid penetrates the control unit disconnect it immediately and contact technical service CLEANING Disconnect the power cable before cleaning the control unit use a dry cloth to dust it without any solvent or detergents and compressed air OBJECTS Never insert any objects into the cracks of the control unit If this happens disconnect the control unit and contact an...

Page 4: ... 2 Supply and relay terminal 3 poles pitch 5 Code 2PL0367 Screws tightening torque 0 5Nm 1 PTC line connection terminal 3 poles 1 motor line terminal 4 poles pitch 5 Code 2PL0369 Screws tightening torque 0 5Nm 1MN0030 REV 2 ATTENTION always install the device using the terminals included in the pack The use of terminals other than those included with the control unit might cause malfunctions ACCES...

Page 5: ...0Vac max 10 A max 50 60 Hz NO Connections on removable terminal strips OUTPUTS 1 fault sensor or operating failure FAULT relay SPDT Output relay with 5A 250Vac res COSФ 1 contacts 2 M1 M2 outputs 250Vac max 10 5A max 50 60Hz SPST DIMENSIONS 100x100 mm din43700 depth 131mm terminal block included Hole 92 x 92 mm TEST AND PERFORMANCE Construction in compliance with CE regulations Protection from ele...

Page 6: ...ng NORYL 94 _V0 Absorption 5VA max Protection treatment of the electronic part Option Front polycarbonate IP65 DISPLAY AND DATA MANAGEMENT LED s alarm undercurrent overcurrent overtemp aux stop only on VRT200 LED s running remote local LED s prg setting cal Initial AUTO TUNING to set up motors operation Front button to START STOP motors locally Front alarm RESET button Access to programming throug...

Page 7: ...r in over current LED red 5 M2 motor in under current LED yellow 15 Current variation LED yellow 6 Fixing block 16 Fans local management LED red 7 Fans local START STOP button 17 Fans remote control LED green 8 Fans control mode REM LOC button REMOTE or LOCAL 18 Programming selection LED yellow In d start d trip 9 ENT RESET button alarm reset and programming data selection 19 Monitoring delay LED ...

Page 8: ...2 1 3 1MN0063 REV 0 1 Control unit 2 Panel hole dimensions 0 8mm tolerance 3 Identification label Fix the unit securely with the blocks supplied 1 2 3 4 1MN0008 REV 0 1 Control unit 3 Fixing screw 2 Fixing block 4 Crosshead screwdriver 1X100mm MOUNTING 8 ...

Page 9: ... line supply 230V 10 50 60 Hz 10 Amp max 2 Remote enabling contact ENABLE 5 FAULT relay fault signal 3 M1 M2 motor line connection 5A max Note with the power to the unit ON the FAULT relay switches contacts 8 9 open NO and 7 9 closed NC FAULT 8 9 NC ALARM FAULT OR POWER OFF FAULT 7 9 NC POWER ON ELECTRICAL CONNECTIONS 7 8 9 7 8 9 9 ...

Page 10: ...r stopped due to over current Under current LED ON motor working under current alarm signal Over and under current LEDs ON overtemp aux stop overtemperature alarm Under current LED flashing motor disconnected while auto tuning Over current LED ON motor consumption 5 5A immediate trip without any delay All LEDs flashing corrupted memory error ech press reset and repeat the programming procedure N B...

Page 11: ......

Page 12: ... the M2 line 8 VRT200 Enabling or disabling PTC inputs LEDS ON PTCs enabled LEDs ON PTC disabled N B if the PTC sensors are not connected the function must be disabled Default disabled 9 Motor start for automatic calibration CAL LED ON To perform the automatic calibration all motors must be connected as per final configuration At the START the motors are switched ON for 60 seconds the CAL LED flas...

Page 13: ...evice M1 or M2 under current yellow LED ON Check the condition of the fans the cables and the supply Re program the device All the LEDs are flashing Memory error press RESET and repeat the programming procedure All the LEDs are ON Likely microcontroller fault return the device to Tecsystem for repair Contact TECSYSTEM Technical Department if the problem persists European directives 2012 19 EC WEEE...

Page 14: ...VRT200 USEFUL CONTACTS TECHNICAL INFORMATION ufficiotecnico tecsystem it SALES INFORMATION info tecsystem it 13 ...

Reviews: