TECSYSTEM VRT200 Instruction Manual Download Page 12

VRT200

 

 

 

 

VRT200 

 

 

 

STEP

 

 

PRESS

 

 

EFFECT

 

 

PRESS

 

 

NOTES

 

 

 

 
 

 

 

 
 

Programming start

 

 

 
 

Keep pressing for 5 seconds until the ON PRG 

LED switches ON. 

 

 

 
 

 

 

 
 

Programming 

“%In”

 

 

 

Set the maximum current variation allowed as a 

percentage (5-10-20-30%) of the In. rated value. 

 

Default 5% 

 

 

 

 

Going to the 

"d.start"

 programming 

step 

 

          Start delay: fan start time during which no  

alarm is generated 

 

 

 
 

 

 

 

Selection of the time in 
seconds 

"d.start"

 

 

 

Select the desired time (5-10-20-

30 sec.) 

 

Default 5 

 

 

 

 

 

 

Going to the 

"d.trip"

 programming 

step 

 

 

Trip delay: time during which the 

alarm persists, necessary for signalling 

 

 

 
 

 

 

 

Selection of the time in seconds  

“d.trip”

 

 

 

Select the desired time (5-10-20-

30 sec.) 

 

Default 5 

 

 

 
 
 

 

 

VRT200

 

Going to the 

“OVERTEMP-AUX 

STOP”

 programming step 

 

 

 

By enabling this function it is possible to connect 

a PTC (or series of PTCs) to control the motor 

temperature. AUX1 for the M1 line 

and AUX2 for the M2 line 

 

 

 
 
 

 

 

 

VRT200

 

Enabling or disabling 

PTC

 inputs. 

 

 

LEDS 

 ON: PTCs enabled 

LEDs 

 ON: PTC disabled 

N.B.: if the PTC sensors are not 

connected, the function must be disabled. 

 

Default disabled 

 

 

 
 
 
 

 

 

 
 
 

 

Motor start 

for automatic calibration CAL LED 

ON 

 

 

To perform the "automatic calibration" all motors 

must be connected as per final configuration. 

At the START the motors are 

switched ON for 60 seconds, the 

CAL LED flashes and LEDs 0-5-10-

20-30 light up in sequence. 

When the calibration is completed, the 

control unit resets and goes  

into REMOTE mode 

 

 

N.B.: any connection or programming errors might cause fan malfunctions. 

 

 
                ATTENTION:  
 

We recommend you check the control unit before starting the device. 
  
The default parameters set by TECSYSTEM might not suit your requirements.    
  
Programming the device is the end user’s responsibility: the set alarm thresholds and the enabled 
functions described in this manual must be checked (by a specialized technician) referring them to the 
application and system characteristics on which the control unit is installed. 

PROGRAMMING  

11

 

Summary of Contents for VRT200

Page 1: ...es with ISO9001 certified quality system http www tecsystem it R 1 4 07 11 16 Translations of the original instructions TECSYSTEM S r l 20094 Corsico MI Tel 39 024581861 Fax 39 0248600783 VRT200 INSTRUCTION MANUAL ENGLISH ...

Page 2: ... IS VALID AND COMPLETE FOR THE UNIT VRT200 PAGE 1 SAFETY REQUIREMENTS 3 2 ACCESSORIES 4 3 TECHNICAL SPECIFICATIONS 5 4 FRONT PANEL 7 5 INSTALLATION 8 6 ELECTRICAL CONNECTIONS 9 VRT200 BACK POWER SUPPLY 10 OPERATION HOW TO CHECK THE ALARM STATUS HOW TO RESET A MOTOR IN ALARM OPERATION WITH BAR 400 or 600 OPERATION WITH FANS NOT TECSYSTEM 7 PROGRAMMING 11 8 WARRANTY CONDITIONS 12 9 TROUBLESHOOTING 1...

Page 3: ...humid hands during storms If any liquid penetrates the control unit disconnect it immediately and contact technical service CLEANING Disconnect the power cable before cleaning the control unit use a dry cloth to dust it without any solvent or detergents and compressed air OBJECTS Never insert any objects into the cracks of the control unit If this happens disconnect the control unit and contact an...

Page 4: ... 2 Supply and relay terminal 3 poles pitch 5 Code 2PL0367 Screws tightening torque 0 5Nm 1 PTC line connection terminal 3 poles 1 motor line terminal 4 poles pitch 5 Code 2PL0369 Screws tightening torque 0 5Nm 1MN0030 REV 2 ATTENTION always install the device using the terminals included in the pack The use of terminals other than those included with the control unit might cause malfunctions ACCES...

Page 5: ...0Vac max 10 A max 50 60 Hz NO Connections on removable terminal strips OUTPUTS 1 fault sensor or operating failure FAULT relay SPDT Output relay with 5A 250Vac res COSФ 1 contacts 2 M1 M2 outputs 250Vac max 10 5A max 50 60Hz SPST DIMENSIONS 100x100 mm din43700 depth 131mm terminal block included Hole 92 x 92 mm TEST AND PERFORMANCE Construction in compliance with CE regulations Protection from ele...

Page 6: ...ng NORYL 94 _V0 Absorption 5VA max Protection treatment of the electronic part Option Front polycarbonate IP65 DISPLAY AND DATA MANAGEMENT LED s alarm undercurrent overcurrent overtemp aux stop only on VRT200 LED s running remote local LED s prg setting cal Initial AUTO TUNING to set up motors operation Front button to START STOP motors locally Front alarm RESET button Access to programming throug...

Page 7: ...r in over current LED red 5 M2 motor in under current LED yellow 15 Current variation LED yellow 6 Fixing block 16 Fans local management LED red 7 Fans local START STOP button 17 Fans remote control LED green 8 Fans control mode REM LOC button REMOTE or LOCAL 18 Programming selection LED yellow In d start d trip 9 ENT RESET button alarm reset and programming data selection 19 Monitoring delay LED ...

Page 8: ...2 1 3 1MN0063 REV 0 1 Control unit 2 Panel hole dimensions 0 8mm tolerance 3 Identification label Fix the unit securely with the blocks supplied 1 2 3 4 1MN0008 REV 0 1 Control unit 3 Fixing screw 2 Fixing block 4 Crosshead screwdriver 1X100mm MOUNTING 8 ...

Page 9: ... line supply 230V 10 50 60 Hz 10 Amp max 2 Remote enabling contact ENABLE 5 FAULT relay fault signal 3 M1 M2 motor line connection 5A max Note with the power to the unit ON the FAULT relay switches contacts 8 9 open NO and 7 9 closed NC FAULT 8 9 NC ALARM FAULT OR POWER OFF FAULT 7 9 NC POWER ON ELECTRICAL CONNECTIONS 7 8 9 7 8 9 9 ...

Page 10: ...r stopped due to over current Under current LED ON motor working under current alarm signal Over and under current LEDs ON overtemp aux stop overtemperature alarm Under current LED flashing motor disconnected while auto tuning Over current LED ON motor consumption 5 5A immediate trip without any delay All LEDs flashing corrupted memory error ech press reset and repeat the programming procedure N B...

Page 11: ......

Page 12: ... the M2 line 8 VRT200 Enabling or disabling PTC inputs LEDS ON PTCs enabled LEDs ON PTC disabled N B if the PTC sensors are not connected the function must be disabled Default disabled 9 Motor start for automatic calibration CAL LED ON To perform the automatic calibration all motors must be connected as per final configuration At the START the motors are switched ON for 60 seconds the CAL LED flas...

Page 13: ...evice M1 or M2 under current yellow LED ON Check the condition of the fans the cables and the supply Re program the device All the LEDs are flashing Memory error press RESET and repeat the programming procedure All the LEDs are ON Likely microcontroller fault return the device to Tecsystem for repair Contact TECSYSTEM Technical Department if the problem persists European directives 2012 19 EC WEEE...

Page 14: ...VRT200 USEFUL CONTACTS TECHNICAL INFORMATION ufficiotecnico tecsystem it SALES INFORMATION info tecsystem it 13 ...

Reviews: