TROUBLESHOOTING 

CAUSES AND 

SOLUTIONS

 

 

The control unit does not switch on and the 
supply to terminals 40-42 is correct. 

Check  that:  the  connector  is  correctly  inserted  into  its  housing,  the 
wires  are  tightened,  there  is  no  evidence  of  burning  on  the 
connectors.  Disconnect the power supply, carry out the above and 
reconnect. 

 

On startup "ECH" is displayed 

 

Strong disturbance has damaged the data in the memory. See the 
paragraph Programmed data diagnostics on page 15.  

 

The display shows ER0 

Check  the  connecting  cable  between  the  TPL503  sensor  and  the 
NT210  K  control  unit:  the  connector  must  be  fully  pushed  in,  the 
wires must be tightened. 

 
 

The main switch has been tripped unexpectedly. 

 

Check the T.P.L. values recorded in MAX, check the oil level in the 
transformer. 

FCD or FPS warning. 

See the FCD or FPS function on page 19. 

Contact 

TECSYSTEM Technical Department if the problem persists. 

 

 

 

 

 

European  directives  2012/19/EC  (WEEE)  and  2011/65/EC  (RoHS)  have  been  approved  to  reduce  electrical  and 
electronic waste and promote the recycling and reuse of the materials and components of this equipment, cutting down 
on the disposal of the residues and harmful components of electrical and electronic materials 

 

All the electrical and electronic equipment supplied after 13 August 2005 is marked with this symbol, pursuant 
to the European directive 2002/96/EEC on electrical and electronic waste (WEEE). Any electrical or electronic 
equipment marked with this symbol must be disposed of separately from normal domestic waste. 

 

Returning  used  electrical  devices:  contact  TECSYSTEM  or  the  TECSYSTEM  agent  for  information  on  the  correct 
disposal of the devices. 

 

TECSYSTEM is aware of the impact its products have on the environment and asks its customers active support in the 
correct and environmentally-friendly disposal of its devices. 

 

 

 

 

TECHNICAL INFORMATION

[email protected] 

COMMERCIAL INFORMATION

[email protected] 

 

USEFUL CONTACTS 

EQUIPMENT DISPOSAL  

Summary of Contents for NT210 K

Page 1: ...ISO9001 2008 certified quality system http www tecsystem it R 1 5 31 01 18 Translations of the original instructions TECSYSTEM S r l 20094 Corsico MI Tel 39 024581861 Fax 39 0248600783 NT210 K TPL503...

Page 2: ...TY REQUIREMENTS 4 2 ACCESSORIES 5 3 TECHNICAL SPECIFICATIONS 6 4 TPL503 SENSOR INSTALLATION PROCEDURE 8 5 FRONT PANEL 10 DISPLAY 11 CHECKING THE WORK PROGRAM LED TEST ALARM RELAY TEST ALARM RELAY SILE...

Page 3: ...ORK RS485 ELECTRICAL CONNECTIONS DATA FRAME DATA PACKET FUNCTION CODE 21 CODE 3 10 CODE 16 10 NOTES FOR REMOTE PROGRAMMING ERROR CODES exception code POLLING FREQUENCY MODBUS MAPPING TABLE 22 CRC CALC...

Page 4: ...exceeding 90 and never touch with wet or humid hands during storms If any liquid penetrates the control unit disconnect it immediately and contact technical service CLEANING Disconnect the power cabl...

Page 5: ...itch 5 Code 2PL0359 Screws tightening torque 0 5Nm 1 RS485 terminal 3 poles pitch 3 81 Code 2PL0366 Screws tightening torque 0 25Nm 1 TPL503 sensor Tecsybus terminal 4 poles pitch 3 81 Code 2PL0368 Sc...

Page 6: ...h 131mm terminal block included Hole 92 x 92 mm TEST AND PERFORMANCE Construction in compliance with CE regulations Protection from electrical interference EN 61000 4 4 Dielectric strength 1500 Vac fo...

Page 7: ...temperature and pressure memory recorded since the last reset Front alarm reset button Sensor fault diagnostics FLT TPL503 TECHNICAL SPECIFICATIONS TPL503 POWER SUPPLY Direct connection to the Power...

Page 8: ...e from welding or painting residue and perfectly clean The cork rubber gasket TPL base must adhere fully to the support surface note replace the gasket every time it is removed to the TPL base NECESSA...

Page 9: ...air is released Attention bleeding must be carried out taking into consideration the transformer operating conditions with the transformer switched off and a temperature of about 20 C or ambient the i...

Page 10: ...7 FAN warning green LED 6 FAULT warning red LED 18 T P L alarm activation AL1 red LED 7 RS communication TPL503 green LED 19 T P L alarm activation AL2 red LED 8 Scanning mode selection button 20 T ma...

Page 11: ...are tested regularly For this operation press the TEST button briefly all the displays light up for 2 seconds ALARM RELAY TEST This function allows carrying out a test of the relay operation without...

Page 12: ...t 2 1 3 1MN0007 REV 0 1 Control unit 2 Panel hole dimensions 0 8mm tolerance 3 Identification label Fix the unit securely with the blocks supplied 1 2 3 4 1MN0008 REV 0 1 Control unit 3 Fixing screw 2...

Page 13: ...nector connection colours 1 RS white 2 PWL brown 3 PWL black 4 RS Blue Note with the power to the unit ON the FAULT relay switches contacts 8 9 open NO and 7 9 closed NC read paragraph ALARMS AND VENT...

Page 14: ...esholds are exceeded The FAULT relay switches when the unit is powered contacts 7 9 closed NC and 8 9 open NO and holds till one of the following events takes place Data storage fault Ech message TPL5...

Page 15: ...alteration of the programmed data at start up Ech is displayed with the relative warning of the Fault contact In this case for safety reasons the default parameters are loaded automatically see the pr...

Page 16: ...ds until the control unit is reset This operation will allow compensating for any reading tolerances due to differences in altitude or transformer filling pressure For the system to be operating corre...

Page 17: ...old is displayed 6 Set the desired threshold Default 100mbar 7 The pressure TRIP AL2 threshold is displayed 8 Set the desired threshold Default 200mbar 9 The level gas ALARM AL1 threshold is displayed...

Page 18: ...d Modbus transmission speed Default 9 6 Kb s 31 Set the desired speed From 2 4 Kb s to 38 4 Kb s 32 PAR datum is displayed Parity bit selection Default NO 33 Set the desired speed None No Even EVE Odd...

Page 19: ...evented as shown above Corrective actions check the installation of the sensor extension cable is in line with the instructions given in the paragraph on the TPL503 connections on page 15 Identificati...

Page 20: ...emperature reading mode while it is inactive when it is in the following modes display programming and relay test RS485 ELECTRICAL CONNECTIONS As to the signal cable to use in order to guarantee corre...

Page 21: ...00 17 00 18 00 24 The same must be remembered for the Trip thresholds registers 00 25 00 26 00 32 and for each quantity measured Temperature Pressure Level Note the Alarm level thresholds must be prog...

Page 22: ...er 1 2 3 see level indication page 16 00 05 00 TPL503 sensor temperature Holding register Temperature Range 40 120 DATA LO 50 10 00 06 00 Not used Holding register 00 07 00 Oil pressure Holding regist...

Page 23: ...ster 00 14 00 Not used Holding register 00 15 00 Not used Holding register 00 16 00 Not used Holding register 00 17 00 Oil Temperature Set Alarm Holding register C 00 18 00 Oil Pressure HI Set Alarm H...

Page 24: ...bled 00 29 00 Oil pressure Trip Holding register mbar 10 00 30 00 Not used Holding register 00 31 00 Not used Holding register 00 32 00 Not used Holding register 00 33 00 Hfn Holding register See page...

Page 25: ...45 00 Oil Temperature alarm history Holding register See note 2 on page 28 00 46 00 Oil Pressure alarm history Holding register 00 47 00 Oil Level alarm history Holding register 00 48 00 Not used Hold...

Page 26: ...olding register 00 60 00 Not used Holding register 00 61 00 Not used Holding register 00 62 00 Not used Holding register 00 63 00 Not used Holding register 00 64 00 Not used Holding register 00 65 00...

Page 27: ...00 Not used Holding register 00 80 00 Not used Holding register NOTE 1 STATUS REGISTER The status register contains information on the status of the alarms of the channel it refers to Each bit repres...

Page 28: ...NOTE 3 GENERAL FLAG REGISTER The general function register contains information on the enabling of general functions FLG_GEN GENERAL FLAGS B7 B6 B5 B4 B3 B2 B1 B0 FREE PRES DEP FREE SYSTEM FLAG ECH E...

Page 29: ...bytes in the packet excluding the 2 of the CRC G Polynomial 1010 0000 0000 0001 shr shift to the right ALGORHITHM 1 0xFFFF A 2 0 i 3 0 j 4 Di AL AL 5 j 1 j 6 shr A 7 if carry then G A A 8 if NOT j 8...

Page 30: ...roblem persists European directives 2012 19 EC WEEE and 2011 65 EC RoHS have been approved to reduce electrical and electronic waste and promote the recycling and reuse of the materials and components...