Place the central fan, letting the distance between centers of the impeller
match the middle sign and fix it to the bar by the piercing screws “
A
” and
“
B
” as shown in the
figures 2 and 4
.
The screws must be tightened using an electric screwer. Measure the
distance between centers of the transformer coils and place on the bar
one by one the side fans, letting the impeller middle (
figure 1
) match the
distance between centers of the coils:
Bar 1200: from 470 to 585 mm
Bar 1800: from 470 to 700 mm
Bar 3600: from 670 to 770 mm
Fix them to the bar by the piercing screws “
A
” and “
B
” as shown in the
figure 4
.
2) COMPONENTS INCLUDED IN THE KIT.
Bar is supplied with disassembled fans.
A complete ventilation kit is composed of:
•
2 wired ventilation bars
•
6 fans:
TG180 (Bar 1200)
TG360 (Bar 1800)
TG500 (Bar 3600)
•
12 piercing screws to fix the fans on the bars