01-2016
LX-(Q)-GSM / LX-(Q)-NET Techn. Docum. + Installation
P. 9
FUNCTION CHECK
After fueling or once a year please check if the displayed liters are correct.
MAINTANCE
It is recommended to check once year if the displayed liters are correct.
For a simple check lift the level probe by the cable so that the probe is above
the liquid level. In this state the device should display 0 liters (+tolerance).
In case of large deviation we recommend to do an Offset calibration for the
measuring probe again. Refer to the setup step “9.Offset probe” and if appli-
cable to the setup “10.Trim height“.
New level probe:
In case mounting of a new level probe it is necessary reset to “default values”
in step “9. Offset probe“.