Tecson Tank-Spion Digital LX-GSM Installation Instructions Manual Download Page 9

01-2016

 

LX-(Q)-GSM  /  LX-(Q)-NET    Techn. Docum.  +  Installation 

P. 9

 

 

FUNCTION CHECK 

 

After fueling or once a year please check if the displayed liters are correct. 

  

MAINTANCE 

 

It is recommended to check once year if the displayed liters are correct. 
For a simple check lift the level probe by the cable so that the probe is above 
the liquid level. In this state the device should display 0 liters (+tolerance).  
In case of large deviation we recommend to do an Offset calibration for the 
measuring probe again. Refer to the setup step “9.Offset probe” and if appli-
cable to the setup “10.Trim height“. 

 

New level probe:

 

In case mounting of a new level probe it is necessary reset to “default values” 
in step “9. Offset probe“. 

 

 

Summary of Contents for Tank-Spion Digital LX-GSM

Page 1: ...pion Digital LX GSM Tank Spion Quadro LX Q NET Tank Spion Quadro LX Q GSM Content Page GENERAL 2 MOUNTING INSTRUCTIONS 3 MOUNTING OF LEVEL PROBE 3 ELECTRIC INSTALLATION 4 CONNECTION CLAMPS 5 DEVICE ME...

Page 2: ...evel probe can be mounted by standard with a 1 or 1 screw thread For mounting in plas tic tanks a grommet and a PG screwing is provided Electric supply 230V AC A special type of the monitoring device...

Page 3: ...display device is connected to the power supply system and may normally only to be used with box cover closed Type 12V 24V DC As a special model this device type is supplied by a low voltage power sup...

Page 4: ...sion The cable of the probe can be extended up to 100 m e g with NYM or YR damp location or NYY soil Line diameter at least 2 x 0 4 mm In case of cable extension in a manhole pit or out doors it is re...

Page 5: ...conditions the relay contacts 7 8 are closed and relay contacts 9 10 are opened In case of event the relay operates so both contact pairs switch over Then contacts 7 8 do open and 9 10 do close At pow...

Page 6: ...cation details via mobile phone are not relevant The complete parameter setup will be done via the OilView system DEVICE PARAMETERS SMS See additional documention Messages Commands a Parameters ati GS...

Page 7: ...um Installation P 7 For LX NET LX Q NET LX NET connection clamps LX Q NET connection clamps Alarm input Pushbuttons Measuring probes 1 to 4 230V supply Probe Serial Link In Digital In Alarm Pushbutton...

Page 8: ...tep 1 Measur probe You can step through the menu items by pressing PLUS or MINUS Press ENTER to step into a sub menu Press PLUS or MINUS for selection press ENTER to confirm After completing Step 7 yo...

Page 9: ...check lift the level probe by the cable so that the probe is above the liquid level In this state the device should display 0 liters tolerance In case of large deviation we recommend to do an Offset c...

Page 10: ...Devices with network bindung The LX Q NET supports DHCP protocol The device should get a fixed IP The network parameter setup has to be done at menu item 15 Network After that and after parameter set...

Page 11: ...01 2016 LX Q GSM LX Q NET Techn Docum Installation P 11 BROWSER ACCESS Show content in browser Entering the IP address in your browsers address line the device will be called...

Page 12: ...owser Clicking the CONFIG button opens a next page in tzhe browser Here you can setup serveral parameters for the device Password The inital passwort for config access at the device is tank The passwo...

Page 13: ...tup is too large measuring value is too small Execute again 9 Offset probe Otherwise defect of probe Error E 7 Current measuring value too small for set corresponding tank height or tank volume Make s...

Page 14: ...ally Sending will be displayed caused by an unreachable destination IP address The destination should be a fixed IP address IP Port should be setup in correct manner LX Q GSM Error messages of GSM mod...

Page 15: ...ing current max 3 5 A Measuring probe standard Voltage Ub of probe 12 30V DC Measur input of device 20V DC Protection Rating probe IP 68 referring to IEC 529 Materials V4A POM FPM HD PE Length of cabl...

Page 16: ...xtended Note F r die serielle Datenausgabe wird ein LINK Adapter ben tigt Art Nr 12038 Add on set for data transmission to a PC Software for displaying and interpretation incl automatic generating of...

Reviews: