01-2016
LX-(Q)-GSM / LX-(Q)-NET Techn. Docum. + Installation
P. 5
CONNECTION CLAMPS
If LX-GSM
and LX-NET
Relay connection:
The LX-GSM and LX-NET devices do have a double output relay. By this relay two separate elec-
tric circuits can be switched simultaneously, e.g. a signalling device on/off and an electric
valve off/on too.
Under initial conditions the relay contacts 7-8 are closed and relay contacts 9-10 are opened.
In case of event the relay operates so both contact pairs switch over. Then contacts 7-8 do open
and 9-10 do close.
At power outage or when the device goes out of order then the relay is under initial condition. in
Inital state
Event state
Relay output
Contact 7 - 8 links
Contact 9 - 10 opened
Contact 7 - 8 opened
Contact 9 - 10 links
Schaltspannung
Max. 250 V AC
Voltage
Max. 3,5 A
Steuerfunktion
For setup see menu item “6. Relay“ and GSM command #S (at LX-GSM)