Basic Functions 

The GSM-Messenger is a remote monitoring system for tank filling levels (liter), meter readings and alarm 
events. The device operates with an integrated GSM mobile phone module that registers itself on the respec-
tive mobile network.  
  
The LINK input can be connected to 1-4 TECSON oil level indicators. Additionally the device monitors the two 
event inputs A1 and A2 which are connected to a potential-free break or make contact (Relays / Reed). 
  
In the event of an alarm or in appointed time intervals the GSM-Messenger automatically reports the current 
plant status. Therefore the Messenger generates an SMS with a plant identifier (header), report reason, liter 
inventory, meter readings and plant status. The data is sent to the parameterized destination phone number via 
SMS. Under normal reception conditions the attached antenna is sufficient for the internal GSM radio module. 
For bad reception areas an external mobile radio antenna with a 5m to 10m cable can be connected. Such an 
outdoor antenna is available as an equipment accessory. 
  
The GSM-Messenger indicates the device status via ist 4 LEDs (see page 6). 
After a power or mobile network blackout the device automatically redials into the GSM mobile network.  

 

Counting Functions 

Since software version V3.xx the GSM-Messenger contains an integrated counter function. 
For device versions V2.xx the special variant Messenger C+, 2+ or A+ was necessary for a counter function. 
 
For these counter functions potential-free switching contacts are connected to input A1 or A2. 
These are typically either reed contacts, relay outputs or make/break contacts. 
 
Via inputs A1 and A2 the following counting functions are applicable 

-  Impulse counter (e.g. water meter with reed output) 

-  Event counter (counts how often the contact has been closed, i.e. how often an event has occurred) 

-  Operating hours counter (e.g. time counter that indicates how long a contact state persists) 
  
The counting mode can be activated and parameterized via command #Ai=

… . 

See enclosed description 

Messages, Commands and Parameters  for the GSM-Messenger

“. 

 

SIM Card 

A prepaid or contract SIM card needs to be inserted into the GSM radio module. 
This SIM card has to be operative i.e. it has to be registered and activated. 
After entering the PIN code at the device the GSM-Messenger automatically dials up into the respective mobile 
network. When using a prepaid SIM card the prepaid credit needs to be recharged if empty. This can be done 
e.g. via internet contractor or at an ATM. 
 

 

OilView Connection 

If the device is connected to the www.oilview.de system all device settings can be performed by the OilView 
systems administrator/user. Only exception: The PIN entry is to be performed via the device keys. 
If the OilView system is not desired the whole parameter settings as well as the device communication is to be 
made per SMS via a mobile phone. The parameters will be transmitted and permanently saved to the device 
via SMS commands #... . Accordingly all reports generated by the device will be sent via SMS to the parame-
terized mobile phone numbers. 

 

 

 

Summary of Contents for GSM-Messenger

Page 1: ...Content Page BASIC FUNCTIONS 2 COUNTING FUNCTIONS 2 SIM CARD 2 OILVIEW CONNECTION 2 ELECTRICAL INSTALLATION 4 DISPLAYING LEDS 6 DEVICE REPORTS 7 DEVICE PARAMETERIZATION 7 SMS REPORTS 7 TECHNICAL DATA...

Page 2: ...for a counter function For these counter functions potential free switching contacts are connected to input A1 or A2 These are typically either reed contacts relay outputs or make break contacts Via...

Page 3: ...ing contact possibly interpose a relay oil tank display 1 oil tank display 2 measuring probe tank 1 up to 100 m 2 wired control line GSM Messenger data transmitter mobile network with SIM card digital...

Page 4: ...ctivated Before connecting it to the 230V supply voltage check if the SIM card is inserted and engaged correctly into the designated modem Network connection Remove the mains fuse ensure safety Connec...

Page 5: ...Therefore press both buttons simultaneously and hold them for 5 sec During this process all registers and parameters will be reset Subsequently the PIN code of the SIM card needs to be reentered Afte...

Page 6: ...up trials the device will retry the dial up only once a day This mode operates for 255 days By pushing the Enter button the device does one logon trial to mobile network again In case of success fully...

Page 7: ...evice will also report the low levels at the beginning of a tank filling report text Info tank n Also via P7 1 Check Credit The credit of the SIM card has fallen below 1 Please recharge the credit Par...