background image

V6.x // 06-2016 

Setup and Operation 

P. 15

 

 

Error code 

Meaning 

Error 

E 1

 

Invalid input value. 

Error 

E 2

 

Signal value of the LITRO-sensor is too small (signal current less than 3.7 mA). 
In case of the secu4 the sensorbox transmits invalid data (probe error). 
Disconnect the current supply and turn the device back on. If the error lasts for at 
least 5 min. the LITRO-sensor or the sensorbox is defective.  

Error 

E 3

 

Measuring value of the LITRO-sensor is too high for offset calibration. The probe 
must not be plunged! A current of 4

.

5 mA or higher indicates a probe problem. 

Error 

E 4

 

Measured value is implausible. Perform menu item 

‘9.Offset probe’. 

Error 

E 5

 

Height input is larger than tank height.  (Wrong input) 

Error 

E 6

 

The measured value is too small for reference. Make sure the probe is plunged.  
The appointed height is too big or the measuring value (resp. the filling level) is too 
small for setting. Perform step 

‘9. Offset probe’. Otherwise probe error. 

Error 

E 7

 

The measured value is too small for the appointed tank height or tank volume. 
Make sure the probe is plunged! 

Error 

E 8

 

For 

secu4:

 

The high test pressure during the maintenance check (s. page 20)  

was fully reached. This was the aim of the test. So no error is present. 

 

For LITRO-sensor: Wait until the loading phase after the initial start is  
completed (max. 5min.). Otherwise the sensor is not connected properly.  
Plus (= blue or white or red) => connect to clamp 1. 

The second display line shows the signal current. A value larger than 22 mA  
(e.g. 25 mA) indicates a clogged or bent measurement line to the buried tank.  
Please blow through or replace the measurement line, preferably with the blue 
bubbling-through pipe of the e-litro set. 
As a TEST the bubbling-through pipe can be disconnected from the LITRO-Sensor. 
E8 should disappear with the next pumping action. Otherwise the LITRO-sensor is 
defective or it has too much pressure. 

Error 

E 9

 

The current value is 0 mA. The probe

’s connection could be broken. 

Check probe connection (polarity) and extension and if necessary reconnect it. 

Error 

E10

 

Calibration error. Switch off and on the 230V supply voltage after waiting for 5 sec 
and retry. Otherwise the LITRO-sensor or the sensorbox is defective. 

Error 

E11

 

Warning: The liquid level of the tank is too low for an exact calibration 
(Press [Enter] to continue anyway). 

Error 

E12

 

No measurement data is received yet from the external tanks 2, 3 or 4. 
In case of 

secu4

 the sensorbox has not sent any data yet. Wait for 3 min. 

Error 

E13

 

No measurable pump pressure. Disconnect the current supply then reconnect it and 
wait for one pumping cycle. If the error E13 remains the micro pump is defective. 
Otherwise send in the LITRO-sensor or the sensorbox! 
The device is not repairable on site. Do not open the device, loss of warranty! 

Error 

E14

 

Charging voltage is too low. Wait for 3 min. If necessary disconnect the power 
supply for 10s. 

Error 

E15

 

No data from the sensorbox. Potential disruption of the signal line to the sensorbox. 

Error 

E16

 

Implausible pressure drop of one of the tank measuring lines (please check!). 
Disconnect the power supply for 10s or cancel E16 with OK.  
Otherwise the sensorbox is defective. 

Error 

E18

 

Device function error. The internal test pressure was not reached! 
The sensorbox of the secu4 or the LITRO-sensor has to be replaced. 

For device type  

e-litro net

 

   

Summary of Contents for e-litro

Page 1: ...sm SW Version V6 0x for tank sizes up to max 10 000 liters CONTENT Installation and mounting 4 Control elements and display 4 ALARM and QUIT button for secu4 6 Device setup and programming 7 Programmi...

Page 2: ...e applicable for liquid level measurements of tanks operated unpressurized Maximum display value 10 000 liters per tank in case of secu4 The liquid level is indicated by the LCD display The instrument...

Page 3: ...t the secu4 will sound the ALARM and an output relay will interrupt the current loop of the tanker The displaying device and the sensorbox both contain of an alarm sound Such an alarm can be switched...

Page 4: ...skip to next menu step Language Select the operation language German English French in menu step 18 Select displaying mode for e litro and e litro net gsm After setting menu items 1 to 5b the favored...

Page 5: ...assword The device settings can be protected by activating a password under menu item 8 A forgotten password can be requested by contacting TECSON Resetting the secu4 will cause the device to demote i...

Page 6: ...evel action Status Red LED Quit button Beeper loud Relay break contact Display all levels below limit OK off off closed OK level 93 at refill or reserve warning flashes double beeping closed STOP Quit...

Page 7: ...up the measuring range of the level sensor The LITRO Sensor is preset to 250mbar Measuring range max oil tank height water column 250 mbar 3 00 m 2 50 m If a different level sensor to the LITRO Sensor...

Page 8: ...ank shape With excava tion Plastic tank with large cavity Excavation in the middle of the tank s body No ring bandages Cyl 50m 3 Not applicable with e litro displaying devices Bearing chart Value inpu...

Page 9: ...g limit 95 190cm change of value with If e g a water tank may be filled to capacity the filling limit is to be set to a value of 99 all all 6 Display resp for secu4 without function The upper display...

Page 10: ...for secu4 loss of password Menu item 9 24 see ff Steps 9 24 contain special settings which usually will not be needed all After entering setup of step 1 to 7 the standard programming is completed By...

Page 11: ...Example 3 e litro secu4 device with 4 battery tanks 4 x 1250 liters steel tanks with hemicycles at top and bottom 155cm tank height display Fillspace Level for each single tank disable tank filling a...

Page 12: ...displaying Default values Resets all values back to standard 0 For secu4 Exit all do not execute with e litro 10 Trim height Input option for the reference height for calibration of probe and measurem...

Page 13: ...the registered tank numbers Return only for e litro gsm e litro net 17 Input Output Alarm In Choose the function of the alarm contact input Deactive Defines the alarm input to be not operating Opening...

Page 14: ...Relay 1 Off On Enter Not for e litro 24 Reset Resetting the device software ESC Leaves this sub menu without execution Restart New initialization of the device software but parameter setup is left un...

Page 15: ...Please blow through or replace the measurement line preferably with the blue bubbling through pipe of the e litro set As a TEST the bubbling through pipe can be disconnected from the LITRO Sensor E8 s...

Page 16: ...estination In case of entering an individual dest IP no Error N2 message will be shown Important The destination address must be a fixed IP address Otherwise the device retries sending again and again...

Page 17: ...on the prepaid account Error M 5 No mobile network available for the SIM card an external antenna could help Destination number set correctly please check Error M 6 Network or other failure during se...

Page 18: ...us 2 green signal 3 brown minus Bottom right clamping block Power supply 230V AC N L Clamp contact number 1 LITRO sensor input red or white or blue 2 LITRO sensor input brown or black 3 4 Input for a...

Page 19: ...number 1 LITRO Sensor input red white blue 2 ditto black brown 3 data input for additional e litro device 4 ditto 5 alarming contact input 6 ditto 7 8 relay output opening contact normal status is clo...

Page 20: ...er maintenance This needs to be induced by the operator If the secu4 s tanker switch off function is used the password needs to be activated in menu item 8 The password is predefined Maintenance Manuf...

Reviews: