Tecson e-litro Start-Up & Operation Download Page 11

V6.x // 06-2016 

Setup and Operation 

P. 11

 

 

 

Example 2

  Buried tank, cylindric horizontal, for 10,000 liters diesel, 

   

 

Inner height 1.59 m, (filling level 54 cm),  LITRO-level probe 0 - 

250 mbar

 

   

 

Device 

e-litro gsm

 with SIM card:   

 

Menu item 

 

1. Measuring probe 
2. Liquid 
3. Tank shape 
4. Tank volume 
5. Tank height 
5b. Filling limit 
6. Display 
7. Relay 
8. ( Exit ) 
. . .  
15. Modem 
. . . 
19. Exit         [Enter] 

Setting / Selection 

 

250 mbar  
Diesel oil 
Cylindric horizontal 
10050 l (exact value from bearing chart) 
159.0 cm (exact value from bearing chart) 
99% (no limit indicator) 
Fil Level 
On:  96%      Off:  94%        (relay energizes at 96%) 
Go forward to next step with [+] 
... 
PIN:  xxxx    - enter the PIN code of the SIM-card 
... 
Displaying mode   => ... 1280 l ... 13 % 

 

Example 3

 

e-litro secu4

 device with 4 battery tanks 4 x 1250 liters, 

  

 

steel tanks with hemicycles at top and bottom, 155cm tank height, 

 

 

display:  Fillspace  +  Level for each single tank 

 

 

disable tank filling at a limit of 94%. 

 

Menu item 

 

1. Number of tanks  
2. Liquid 
3. Tank shape 
4. Tank volume 
5. Tank height 
5b. Filling limit 
6. Display  
7. Unit 
8. Exit         [Enter] 

Setting / Selection 

 

4  
Heating oil 
Steel tanks 
1250 L  (x 4) 
155.0 cm 
94%  =   146cm 
Not available for secu4 (no function) 
Active     =>   

‘on’ at 99% ; ‘off’ at 10% of the filling level 

Back to displaying mode; 
Display 1 (details per tank) switches with  
Display 2 total inventory in L; filling space in L 

 
 
 
 

Tank with interior mantle 

  

In case of a tank with interior mantle (e.g. horz. cyl. or cellar steel tank) correct the input values.  
 
Example:  Mantle thickness:                  ca.  5 

– 10 mm: 

=> Enter 

‘5.Tank height’:  

reduce height by ca. 15 mm  

=> Enter 

‘4.Tank volume’:  

reduce volume by ca. 2 % 

 

 

 

 

Summary of Contents for e-litro

Page 1: ...sm SW Version V6 0x for tank sizes up to max 10 000 liters CONTENT Installation and mounting 4 Control elements and display 4 ALARM and QUIT button for secu4 6 Device setup and programming 7 Programmi...

Page 2: ...e applicable for liquid level measurements of tanks operated unpressurized Maximum display value 10 000 liters per tank in case of secu4 The liquid level is indicated by the LCD display The instrument...

Page 3: ...t the secu4 will sound the ALARM and an output relay will interrupt the current loop of the tanker The displaying device and the sensorbox both contain of an alarm sound Such an alarm can be switched...

Page 4: ...skip to next menu step Language Select the operation language German English French in menu step 18 Select displaying mode for e litro and e litro net gsm After setting menu items 1 to 5b the favored...

Page 5: ...assword The device settings can be protected by activating a password under menu item 8 A forgotten password can be requested by contacting TECSON Resetting the secu4 will cause the device to demote i...

Page 6: ...evel action Status Red LED Quit button Beeper loud Relay break contact Display all levels below limit OK off off closed OK level 93 at refill or reserve warning flashes double beeping closed STOP Quit...

Page 7: ...up the measuring range of the level sensor The LITRO Sensor is preset to 250mbar Measuring range max oil tank height water column 250 mbar 3 00 m 2 50 m If a different level sensor to the LITRO Sensor...

Page 8: ...ank shape With excava tion Plastic tank with large cavity Excavation in the middle of the tank s body No ring bandages Cyl 50m 3 Not applicable with e litro displaying devices Bearing chart Value inpu...

Page 9: ...g limit 95 190cm change of value with If e g a water tank may be filled to capacity the filling limit is to be set to a value of 99 all all 6 Display resp for secu4 without function The upper display...

Page 10: ...for secu4 loss of password Menu item 9 24 see ff Steps 9 24 contain special settings which usually will not be needed all After entering setup of step 1 to 7 the standard programming is completed By...

Page 11: ...Example 3 e litro secu4 device with 4 battery tanks 4 x 1250 liters steel tanks with hemicycles at top and bottom 155cm tank height display Fillspace Level for each single tank disable tank filling a...

Page 12: ...displaying Default values Resets all values back to standard 0 For secu4 Exit all do not execute with e litro 10 Trim height Input option for the reference height for calibration of probe and measurem...

Page 13: ...the registered tank numbers Return only for e litro gsm e litro net 17 Input Output Alarm In Choose the function of the alarm contact input Deactive Defines the alarm input to be not operating Opening...

Page 14: ...Relay 1 Off On Enter Not for e litro 24 Reset Resetting the device software ESC Leaves this sub menu without execution Restart New initialization of the device software but parameter setup is left un...

Page 15: ...Please blow through or replace the measurement line preferably with the blue bubbling through pipe of the e litro set As a TEST the bubbling through pipe can be disconnected from the LITRO Sensor E8 s...

Page 16: ...estination In case of entering an individual dest IP no Error N2 message will be shown Important The destination address must be a fixed IP address Otherwise the device retries sending again and again...

Page 17: ...on the prepaid account Error M 5 No mobile network available for the SIM card an external antenna could help Destination number set correctly please check Error M 6 Network or other failure during se...

Page 18: ...us 2 green signal 3 brown minus Bottom right clamping block Power supply 230V AC N L Clamp contact number 1 LITRO sensor input red or white or blue 2 LITRO sensor input brown or black 3 4 Input for a...

Page 19: ...number 1 LITRO Sensor input red white blue 2 ditto black brown 3 data input for additional e litro device 4 ditto 5 alarming contact input 6 ditto 7 8 relay output opening contact normal status is clo...

Page 20: ...er maintenance This needs to be induced by the operator If the secu4 s tanker switch off function is used the password needs to be activated in menu item 8 The password is predefined Maintenance Manuf...

Reviews: