![TECOMAT FOXTROT CP-1016 Basic Documentation Download Page 17](http://html1.mh-extra.com/html/tecomat-foxtrot/cp-1016/cp-1016_basic-documentation_1072627017.webp)
Basic documentation for CP-1016 module
17
TXV 110 16
Parameters of analog outputs AO0, AO1
Number of outputs
2
Number of outputs in a group
2
Output type
active voltage output
Galvanic isolation from internal circuits
no
Common pole of a group
minus
Converter numerical resolution
10 bits
Conversion time
10 µs
Output voltage / resolution 1 LSB
0 – 10.5 V/10.54 mV
Max. output current
10 mA
Error of analog output
Max. error at 25 °C
±2 % of full range
Temperature coefficient
±0.3 % of full range/K
Linearity
±0.7 % of full range
Repeatability under steady conditions
±0.5 % of full range
Number of outputs
2
Number of outputs in a group
2
Output type
active voltage output
Galvanic isolation from internal circuits
no
Common pole of a group
minus
External power supply
no
Conversion time
10 µs
Protection type
integrated overvoltage protection
Converter numerical resolution
10 bits
Output voltage/resolution 1 LSB
0 to +10 V/10.546 mV
Permitted continuous overload (without damage)
±20 V (each terminal AO against AGND)
Max. output current
10 mA
Error of analog input
max. error at 25 °C
±2 % of full range
temperature coefficient
±0.3 % of full range /K
non-linearity
±0.7 % of full range
repeatability under steady conditions
±0.5 % of full range
2. PACKAGING, TRANSPORTATION, STORAGE
The module is packed according to internal packing instructions into a cardboard box. This
documentation is enclosed in the packaging. The external packaging is done according to the
quantity and way of transportation into a shipping container being labelled and containing all the
necessary data for transportation.
The goods is transported from the manufacturer's facilities as agreed when placing an order.
Transportation of the goods by the customer must be pursued by covered transport means and
in the position as indicated on the packaging. The shipping containers must be fixed in such a
way to avoid accidental spontaneous movement and damage of the external container during
transport.
During transportation and storage, the product must be protected from direct influence of
atmospheric actions. Transportation of the product is permitted within a temperature range of
-25 °C to 70 °C, relative humidity of 10 % to 95 % (without condensation) and minimum
atmospheric pressure higher than 70 kPa.