JN5-CM-PDP User Manual
File No.:R09-PBUS-D20 Version:01
6
2.3 Connect with Base Unit and Setting Parameters
JN5-CM-PDP
module connected with base unit via a RS485 port with MODBUS RTU protocol.
Setting for RS485 port: Baud Rate 19200kbps, 8 bit data length, 1bit for stop bit, and no parity bit.
Users have to set parameters as shown in the table below.
Function
Description
Setting value
Default value
00-02
Run source
2: communication control
1
00-05
Frequency source
3: communication setting
1
09-00 Communication
address 1:
address=1
1
09-02
Serial Baud Rate
4: 19200bps
3
09-03
Stop Bit
0: 1stop bit
0
09-04
Parity Bit
0: no parity bit
0
More information for setting and wiring refer to see:
A510 User Manual
.