JN5-CM-PDP User Manual
File No.:R09-PBUS-D20 Version:01
14
4 GSD File and Parameters
A GSD file is a text file used to identify PROFIBUS-DP device (master or slave), which contains
the necessary data for the configuration of DP slaves within a standard DP master. Typical
information in a GSD file are Vendor information, supported Baud rates, Timing information,
supported Options/features and Available I/O signals. The parameters in GSD file are used for the
configuration of the PROFIBUS network. The parameters descriptions are shown as below.
GSD File for
A510
series drive
Appendix A: TECO_A51.GSD
Parameters for
A510
series drive
The parameters description is shown as in the table below:
Item Name
Type
Description
Default
1
Dout1
U16
This is the MODBUS address of STW1.
Other addresses are not allowed.
0x2501
2
Dout2
U16
This is the MODBUS address of HSW.
Other addresses are not allowed.
0x2502
3 Dout3
U16
Not
used
0x0000
4 Dout4
U16
Not
used
0x0000
5
Din1
U16
This is the MODBUS address of ZSW1.
Other addresses are not allowed.
0x2520
6
Din2
U16
This is the MODBUS address of HIW.
Other addresses are not allowed.
0x2524
7
Din3
U16
This is a MODBUS address and should in
range of
0x2520 to 0x252F
.
JN5-CM-PDP
will monitor this address,
and copy the return data to the 3rd word
of cyclic input data PZD if selecting
module”4 PKW, 4 PZD”.
0x2522
8
Din4
U16
This is a MODBUS address and should in
range of
0x2520 to 0x252F
.
JN5-CM-PDP
will monitor this address,
and copy the return data to the 4th word
of cyclic input data PZD if selecting
module”4 PKW, 4 PZD”.
0x2527
9
LossDPComTreat
U16
It is used to decide the method when
communication with PROFIBUS network
is lost. The settings can be:
00 - Ignore event and continue;
01 - Stop according to 07-09 stop method.
0x0001
10
LossSPComTreat
U16
It is used to decide the method when the
SP communication is lost.
The settings can be:
00 - Stop data exchange and alarm;
01 - Continue data exchange and alarm;
02 - Ignore and continue data exchange.
0x0000