Connect wires to terminal blocks 

 

 

 

Name 

Terminal function 

SLC

1  

А, В  

Connecting the data SLC1 

+,  -   

Connecting the power SLC1 

SLC

А, В  

Connecting the data SLC2  

+,  -    

Connecting the power SLC2 

U1, GND 

Input for connecting the main 
power supply 

U2, GND 

Input for connecting a backup 
power supply 

А485В, GND, 

А485В 

RS-485  interface  for  connecting  to  the  control 
panel  and  organizing  a  ring  interface  (terminals 
SLC  for  connecting  incoming  and  outgoing  inter-
faces are chosen arbitrarily) 

 

6

  Register the RPA in the Control Panel  see p. 6.1.

 

7 Test the RPA 
1)

  Check  according  to  the  indication  on  the  RPA,  in the  PKM  Astra 

Pro or on the screen "Astra-812 Pro" the status of the RPA (the sta-
tus "Normal" should be displayed) 

2)

  Run  test  mode  according  to  User  guide.  Control  the  issuance  of 

notifications on the Control Panel

 

 

9.4 

If the length of the radial topology SLC is more than 800 m, it is 

recommended  to  install  a  100  Ohm  terminating  resistor  (from  the  de-
livery  set)  at  the  SLC  point  farthest  from  the  RPA  to  match  the  Data 
line.  

R1, R2

 

– resistor 100Ohm. 

Pic.3 

10  Warranty 

 

The  operation  warranty  period  is  5  years  from  the  date  of  operation 
start-up, but no longer than 5 years 6 months from the date of manu-
facturing subject to the requirements of User guide 
 

 
 

Manufacturer: 

ZAO NTC TEKO 

420108, Russia, Kazan, 

Gafuri str., 71 

Tel.:+7(843) 528-03-69 

[email protected]

  

www.teko.biz

  

 

Made in Russia 

 

More than 800 m 

Not more than 250 addressable devices 

RPA 

Summary of Contents for ASTRA-A RPA

Page 1: ... cable length in a segment should not exceed 200 m 1 7 Recommended wires for SLC cable with two pairs of twisted cores pairs arranged in parallel core cross section from 0 35 to 2 5 sq mm For security systems it is permissible to use a UTP 4 2 0 5 cables Recommended wire type to ensure maximum range for SLC in fire sys tems is FRLS FRHF FRLSLtx 2 2 0 5 1 8 RPA has two independent power inputs main...

Page 2: ...D2 x2 yellow flashes every 3 sec Connection with Control Panel is normal Activity with Control Panel via D1 and D2 Solid green Status Interface LED Control Panel No connection with Control Panel No activity with Con trol Panel via D1 and D2 Solid yellow No connection with Control Panel No activity with Con trol Panel via D1 x1 yellow flash every 1 sec No connection with Control Panel No activity w...

Page 3: ...a the Astra Pro PKM or the Astra 812 Pro menu 6 2 Removing RPA а If the RPA is connected to the Control Panel then the removal of the RPA from the memory of the Control Panel is done through the Configuration Module of the PKM Astra Pro software or from the menu of the Control Panel Astra 812 Pro b If the RPA is not connected to the Control Panel remove the RPA from the memory of the Control Panel...

Page 4: ...a Pro or on the screen Astra 812 Pro the status of the RPA the sta tus Normal should be displayed 2 Run test mode according to User guide Control the issuance of notifications on the Control Panel 9 4 If the length of the radial topology SLC is more than 800 m it is recommended to install a 100 Ohm terminating resistor from the de livery set at the SLC point farthest from the RPA to match the Data...

Reviews: