4-15
Group 06: Automatic Program Operation Parameters
Code
Parameter Name
Setting Range
Default
Unit
Notes
~
06-31
06-32
Auto_ Run Mode running direction 2
0: Stop
0
-
06-33
Auto_ Run Mode running direction 3
0
-
06-34
Auto_ Run Mode running direction 4
1: Forward
0
-
06-35
Auto_ Run Mode running direction 5
0
-
06-36
Auto_ Run Mode running direction 6
2: Reverse
0
-
06-37
Auto_ Run Mode running direction 7
0
-
06-38
Auto_ Run Mode running direction 2
0
-
06-39
Auto_ Run Mode running direction 3
0
-
Group 07: Start /Stop Parameters
Code
Parameter Name
Setting Range
Default
Unit
Notes
07-00
Momentary Power Loss and Restart
0: Disabled
0
-
1: Enabled
07-01
Auto Restart Delay Time
0.0 ~ 800.0
0.0
s
07-02
Number of Auto Restart Attempts
0~10
0
-
07-03
Reset Mode Setting
0: Enable Reset Only when Run Command is
Off
0
-
1: Enable Reset when Run Command is On or
Off
07-04
Direct Running After Power Up
0: Enable Direct run on power up
1
-
0: Disable Direct run on power up
07-05
Delay-ON Timer
1.0 ~ 300.0
1.0
s
07-06
DC Injection Brake Start Freq in Stop
Mode
0.10 ~ 10.00
1.5
Hz
07-07
DC Injection Braking Current
0 ~ 20%
5
%
07-08
DC Injection Brake Time in Stop
Mode
0.0 ~ 25.5
0.5
s
07-09
Stopping Method
0: Deceleration to Stop
0
1: Coast to Stop
Group 08: Protection Parameters
Code
Parameter Name
Setting Range
Default
Unit
Notes
08-00
Trip Prevention Selection
xxxx0: Enable Trip Prevention During
Acceleration
xxxx1: Disable Trip Prevention During
Acceleration
xxx0x: Enable Trip Prevention During
Deceleration
xxx1x: Disable Trip Prevention During
Deceleration
xx0xx: Enable Trip Prevention in Run
Mode
xx1xx: Disable Trip Prevention in Run
Mode
x0xxx: Enable over voltage Prevention
in Run Mode
00000
-