28
Fn_10:
START / STOP Control
This parameter is used to decide if the Start and Stop function will be controlled by the Keypad or
by Remote Operation (
TM2
).
0: Keypad Control
1: Remote Operation (
TM2
)
Note:
The STOP Key on the Keypad can still be used for Emergency Stopping even if the START /
STOP Control is from
TM2
(
Fn_10
= 1). (Refer to
Fn_48
)
Fn_11:
Frequency Command Selection
0: Run by
Fn_25
Master Reference
1: Run by Frequency Setting Potentiometer on Keypad
2: Run by Speed Pot on
TM2
or Remote Signal (Terminals (12 / 13 / 14))
3: Run by Multi-Function Input Frequency Command (Terminals 6 / 7 / 8))
0 - 10VDC Speed Ref. 0 - 5VDC Remote 4 - 20mA Signal 0 - 10VDC Remote
(
Fn_11
) to 2
Use a (10K, 2 Watt)
Pot with the wiper in
Terminal 13. Jumper
(
JP1
) Pins 1 & 2.
(
Fn_11
) to 2
For a Remote 5VDC
Signal, Jumper (
JP1
)
Pins 1 & 2.
(
Fn_11
) to 2
For a Remote
4 - 20mA Signal,
Jumper (
JP1
)
Pins 2 & 3.
(
Fn_11
) to 2
For a Remote
0 - 10VDC Signal,
Jumper (
JP2
)
Pins 2 & 3.
TM2
12
13
14
15
FM- FM+
FCW WIPER FCCW
1
2
3
JP1
TM2
12
13
14
15
1
2
3
JP1
FM- FM+
+
-
TM2
12
13
14
15
1
2
3
JP1
FM- FM+
+
-
TM2
12
13
14
15
JP1
FM- FM+
+
-
1
2
3