4-19
Group 08: Protection Parameters
No.
Description
Range
Factory
Setting
Unit
Note
08-00
Trip Prevention Selection
xxxx0: Enable Trip Prevention During
Acceleration
xxxx1: Disable Trip Prevention During
Acceleration
xxx0x: Enable Trip Prevention During
Deceleration
xxx1x: Disable Trip Prevention During
Deceleration
xx0xx: Enable Trip Prevention in Run
Mode
xx1xx: Disable Trip Prevention in Run
Mode
x0xxx: Enable Over Voltage Prevention
in Run Mode
x1xxx: Disable Over Voltage Prevention
in Run Mode
01000
-
*5
08-01
Trip Prevention Level
During Acceleration (%)
50 ~ 200
200
%
1
08-02
Trip Prevention Level
During Deceleration (%)
50 ~ 200
200
08-03
Trip Prevention Level in
Run Mode (%)
50 ~ 200
200
08-04
Over Voltage Prevention
Level in Run Mode
350.0~390.0/700.0~780.0
380.0/7
60.0
VDC
08-05
Electronic Motor Overload
Protection Operation Mode
0: Disable
1: Enable
1
-
*7
08-06
Operation After Overload
Protection is Activated
0: Coast-to-Stop After Overload Protection is Activated
1: Drive Will Not Trip when Overload Protection is
Activated (OL1)
0
-
08-07
Over Heat Protection
( cooling fan control)
0: Auto (Depends on temp.)
1: Operate while in RUN Mode
2: Always Run
3: Disabled
1
-
08-08
AVR Function
(Auto Voltage Regulation)
0: AVR Function is enabled
4
-
*5
1: AVR Function is disabled
2: AVR Function is disabled for Stop
3: AVR Function is disabled for Deceleration.
4: AVR Function is disabled for Stop and Deceleration.
5: When VDC>360V, AVR Function is disabled for Stop
and Deceleration.
08-09
Input Phase Loss
Protection
0: Disable
1: Enable
0
-
08-10
Output Phase Losts
Protection
0: Disable
0
-
1: Enable
08-11
Motor Type Selection
0: Overload protection (Standard Motor)
0
-
1: Overload protection (Inverter Duty Motor)
08-12
Motor Overload Protection
Curve
0: Motor Overload Protection for General loads
(OL=103 %) (150% for 1 Minutes)
0
-
1: Motor Over load Protection for HVAC (Fan & Pump)
(OL=113%) (123% for 1 Minutes).
08-13
Over Torque Detection
Control
0: Over Torque Detection Disabled
0
-
1: Detected After the Setting Frequency
2: Detected When Running
1
Base on the percentage of inverter rated current.