4-13
Group 04: External Analog Input and Output Parameters
No.
Description
Range
Factory
Setting
Unit
Note
04-00
Analog Input Signal Type
Select (AI1/AI2)
AI1 AI2
1
-
*7
(0): 0~10V (0~20mA) 0~10V (0~20mA)
(1): 0~10V (0~20mA) 2~10V (4~20mA)
(2): 2~10V (4~20mA) 0~10V (0~20mA)
(3): 2~10V (4~20mA) 2~10V (4~20mA)
04-01
AI1 Signal Verification Scan Rate 1~200
50
2ms
04-02
AI1 Gain
0 ~ 1000
100
%
*1
04-03
AI1 Bias
0 ~ 100
0
%
*1
04-04
AI1 Bias Selection
0: Positive 1: Negative
0
-
*1
04-05
AI1 Slope
0: Positive 1: Negative
0
-
*1
04-06
AI2 Signal Verification Scan
Rate
1~200
50
2ms
04-07
AI2 Gain
0 ~ 1000
100
%
*1
04-08
AI2 Bias
0 ~ 100
0
%
*1
04-09
AI2 Bias Selection
0: Positive 1: Negative
0
-
*1
04-10
AI2 Slope
0: Positive 1: Negative
0
-
*1
04-11
Analog Output (AO) Mode
0: Output Frequency
1: Frequency Command
2: Output Voltage
3: DC Bus Voltage
4: Motor Current (100% rated current)
0
-
*1
04-12
Analog Output (AO) Gain
0 ~ 1000
100
%
*1
04-13
Analog Output (AO) Bias
0 ~ 100
0
%
*1
04-14
AO Bias Selection
0: Positive 1: Negative
0
-
*1
04-15
AO Slope
0: Positive 1: Negative
0
-
*1
04-16
F-Gain Function
0: Invalid 1: Effective
0
-
*1