background image

"AL1t" – ALARM TYPE :

  the alarm output can behave in six

different ways.

LoAb

 = ABSOLUTE LOW ALARM: The alarm is activated when the

process value goes below the alarm threshold set on parameter

"AL1” and will be deactivated when it goes above the value
[AL1+HAL1]. 

With this mode is possible to program the minimum and the
maximum set  of   “AL1” by “AL1L” and “AL1H” parameters.

HiAb

 = ABSOLUTE HIGH ALARM: The alarm is activated when the

process value goes higher than the alarm threshold  set on
parameter "AL1" and will be deactivated when it goes below the

value [AL1 - HAL1].
With this mode is possible to program the minimum and the

maximum set  of   “AL1” by “AL1L” and “AL1H” parameters.

LoAb

off

ON

AL1

AL1

PV

HiAb

HAL1

time

off

ON

AL1

PV

time

HAL1

off

off

ON

OUT

off

off

ON

OUT

AL1

LodE

 = DEVIATION LOW ALARM: The alarm is activated when the

process value goes below the value [SP + AL1] and will be

deactivated when it goes above the value [SP + AL1 + HAL1].
With this mode is possible to program the minimum and the

maximum set  of   “AL1” by “AL1L” and “AL1H” parameters.

HidE

 = DEVIATION HIGH ALARM: The alarm is activated when the

process value goes above the value [SP + AL1] and will be

deactivated when it goes below the value [SP +  AL1 - HAL1].
With this mode is possible to program the minimum and the

maximum set  of   “AL1” by “AL1L” and “AL1H” parameters.

LodE

ON

off

PV

SP

-AL1

HAL1

time

off

ON

SP

AL1

PV

HidE

time

HAL1

ON

off

off

off

off

ON

OUT

AL1

OUT

AL1

LHAb

 = ABSOLUTE BAND ALARM: The alarm is activated when

the process value goes under the alarm threshold set on parameter
"AL1L" or goes higher than the alarm threshold set on parameter

"AL1H" and will be deactivated when it goes below the value [AL1H
- HAL1] or when it goes above the value [AL1L + HAL1].

LHdE

 = DEVIATION BAND ALARM: The alarm is activated when

the process value goes below the value [SP + AL1L] or goes above
than the value [SP + AL1H] and will be deactivated when it goes

below the value [SP + AL1H - HAL1] or when it goes above the
value [SP + AL1L + HAL1].

LHAb

ON

off

AL1H

AL1L

PV

ON

time

off

HAL1

HAL1

SP

- AL1L

AL1H

PV

time

LHdE

HAL1

HAL1

off

off

ON

ON

off

off

OUT

AL1

OUT

AL1

"

Ab1" - ALARM CONFIGURATION:

 This parameter can assume a

value between 0 and 31.

The number to be set, which will correspond to the function desired,
is obtained by adding the values reported in the following

descriptions :
ALARM BEHAVIOUR AT SWITCH ON: the alarm output may

behave in two different ways, depending on the value added to par.
“Ab1”.

+0 = NORMAL BEHAVIOUR: The alarm is always activated when
there are alarm conditions.

+1 = ALARM NOT ACTIVATED AT SWITCH ON: If, when switched
on, the instrument is in alarm condition, the alarm is not activated. It

will be activated only when the process value is in non-alarm
conditions  and then back in alarm conditions.

P V

+ 1

+ 0

t i m e

A L 1

O N

O N

O N

o f f

o f f

o f f

o f f

A b 1

exemple with absolute low alarm

ALARM DELAY:  the alarm output may behave in two different

ways depending on the value added to par. “Ab1”.
+0 = ALARM NOT DELAYED: The alarm is immediately activated

when the alarm condition occurs.
+2 = ALARM DELAYED: When the alarm condition occurs, delay

counting begins, as programmed on par. “AL1d” (expressed in
sec.) and the alarm will be activated only after the elapsing of that

time.
ALARM LATCH: :  the alarm output may behave in two different

ways depending on the value added to par. “Ab1”.
+ 0 = ALARM NOT LATCHED: The alarm remains active in alarm

conditions only.
+ 4 = ALARM LATCHED: The alarm is active in alarm conditions

and remains active even when these conditions no longer exist,
until  the correctly programmed key “U”, (“USrb”=Aac) has been

pushed.

A L 1

P V

O N

O N

t i m e

+ 0

A b 1

+ 4

o f f

o f f

o f f

exemple with absolute high alarm

ALARM  AKNOWLEDGEMENT: :  the alarm output may behave in
two different ways depending on the value added to par. “Ab1”.

+ 0 = ALARM NOT AKNOWLEDGED: The alarm always remains
active in alarm conditions.

+ 8 = ALARM AKNOWLEDGED: The alarm is active in alarm
conditions and can be deactivated by key “U” if properly

programmed (“USrb”=ASi), and also if alarm conditions still exist.
ALARM BEHAVIOUR AT SET POINT CHANGE (DEVIATION

ALARMS ONLY): the alarm output may behave in two different
ways, depending on the value added to par. “Ab1”.

+0 = NORMAL BEHAVIOUR: The alarm is always activated when
there are alarm conditions.

+16 = ALARM NOT ACTIVATED AT SET POINT CHANGE: If,
when Set Point change, the instrument is in alarm condition, the

alarm is not activated. It will be activated only when the process
value is in non-alarm conditions  and then back in alarm conditions.

"AL1i" - ALARM ACTIVATION IN CASE OF MEASUREMENT
ERROR:

 This allows one to establish how the alarm have behave

in the event of a measurement error (yES=alarm active; no=alarm
deactivated).

TECNOLOGIC spa - TLK 38

 

- OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 8

Summary of Contents for TLK 38

Page 1: ...RING AND VISUALIZATION 4 1 FUNCTIONS 4 ELECTRICAL WIRING DIAGRAM 3 4 ELECTRICAL CONNECTIONS 3 3 MECHANICAL MOUNTING 3 2 PERMITTED USE 3 1 INFORMATION ON INSTALLATION AND USE 3 ACTIVE SET POINT SELECTION 2 5 CONTROL STATES 2 4 PARAMETER PROGRAMMING LEVELS 2 3 SELECTION OF CONTROL STATE AND PARAMETER PROGRAMMING 2 2 FAST PROGRAMMING OF SET POINT 2 1 PROGRAMMING 2 FRONT PANEL DESCRIPTION 1 2 GENERAL ...

Page 2: ...n to normal functioning automatically 2 2 SELECTION OF THE CONTROL STATE AND PARAMETER PROGRAMMING By pushing key P and holding it down for approx 2 sec it is possible to enter into the main selection menu Using the UP or DOWN keys it is then possible to roll over the selections to enter into the operating parameters menu OPEr to swap the regulator to the manual control state and therefore to prog...

Page 3: ...s possible to manually program the power percentage given as output by the controller by deactivating automatic control When the instrument is swapped to manual control the power percentage is the same as the last one supplied and can be modified using the UP and DOWN keys As in the case of automatic control the programmable values range from H100 100 to C100 100 To return to automatic control sel...

Page 4: ... 0 50 mV 0 50 0 60 mV 0 60 12 60 mV 12 60 We recommend to switch on and off the instrument when these parameters are modified in order to obtain a correct measuring For the instruments with input for temperature probes tc rtd it s possible to select through par Unit the unit of measurement C F and through par dP Pt100 PTC and NTC only the desired resolution 0 1 1 0 1 Instead with regards to the in...

Page 5: ...2 rEG All the parameters referring to Neutral Zone ON OFF control are contained in the group rEG This type of control can be obtained when 2 outputs are programmed respectively as 1 rEG and 2 rEG and the par Cont nr The Neutral Zone control is used to control plants in which there is an element which causes a positive increase ex Heater humidifier etc and an element which causes a negative increas...

Page 6: ...al Band tcr1 Cycle time of the output 1rEG Int Integral Time dEr Derivative Time FuOC Fuzzy Overshoot Control and for the Double Action PID control also tcr 2 Cycle time of the output 2rEG Prat Power Ratio P 2 rEG P 1 rEG To activate the AUTO TUNING function proceed as follows 1 Program and activate the desired Set Point 2 Program par Cont Pid 3 Program par Func according to the process to be cont...

Page 7: ...ogram the desired ramp and if it automatic tuning is desired enable the Self tuning function 4 9 SOFT START FUNCTION All the parameters referring to the Soft Start functioning are contained in the group rEG The Soft Start function only works through PID control and allows the limitation of control power when the instrument is switched on for a programmable period of time This is useful when the ac...

Page 8: ...d in the following descriptions ALARM BEHAVIOUR AT SWITCH ON the alarm output may behave in two different ways depending on the value added to par Ab1 0 NORMAL BEHAVIOUR The alarm is always activated when there are alarm conditions 1 ALARM NOT ACTIVATED AT SWITCH ON If when switched on the instrument is in alarm condition the alarm is not activated It will be activated only when the process value ...

Page 9: ...meters through the device TECNOLOGIC KEY01 with 5 poles connector This device it s mainly useable for the serial programming of the instruments which need to have the same parameters configuration or to keep a copy of the programming of an instrument and allow its rapid retransmission To use the device KEY01 it s necessary that the device or instrument are being supplied To transfer the configurat...

Page 10: ...2 Out1 Out2 OFF Output where alarm AL1 is addressed OAL1 22 Note Def Range Description Par no no yES Alarm AL1 activation in case of measuring error AL1i 30 OFF OFF 9999 sec Activation delay of alarm AL1 AL1d 29 1 OFF 9999 Alarm AL1 hysteresis HAL1 28 9999 AL1L 9999 High threshold band alarm AL1 or Maximum set alarm AL1 for high or low alarm AL1H 27 1999 1999 AL1H Low threshold band alarm AL1 or M...

Page 11: ...e measured variable is over the probe s limits over range oooo The measured variable is under the probe s limits under range uuuu Verify the correct connection between probe and instrument and then verify the correct functioning of the probe Probe interrupted Action Reason Error In error conditions the instrument provides an output power as programmed on par OPE and activates the desired alarms if...

Page 12: ... 5 fs tc S 1 fs Sampling rate 130 ms Display 4 Digit Red h 12 mm Compliance ECC directive EMC 2004 108 CE EN 61326 ECC directive LV 2006 95 CE EN 61010 1 Approvals C UL file n E206847 7 5 MEASURING RANGE TABLE 2 10 V SEnS 2 10 0 10 V SEnS 0 10 1 5 V SEnS 1 5 0 5 V SEnS 0 5 0 1 V SEnS 0 1 12 60 mV SEnS 12 60 0 60 mV SEnS 0 60 0 50 mV SEnS 0 50 4 20 mA SEnS 4 20 199 9 999 9 19 99 99 99 1 999 9 999 1...

Reviews: