0000 ... 9999
Password request second level
programming parameters
PASS
SECOND LEVEL PARAMETERS TABLE
1
0 ... 20 sec.
Input digital filter costant
FiLt
0
-999 ... 9999
-99.9 ... 999.9
Calibration
OFFt
J
J / CrAl / r / S
/ t Pt1 / Pt2
Input probe
SEnS
C
C / F / AbS
Unit of measurement
Unit
50
-100.0 ... 100.0
%
Manual reset
rS
30
1 ... 255 sec.
Output C2 cycle time
tcr2
10
0.0 ... 999.9
C2 / C1 power ratio
Prat
30
1 ... 255 sec.
Output C1 cycle time
tcr1
30
0 ... 9999 sec.
Derivative time
dEr
500
0 ... 9999 sec.
Integral time
Int
100
1 ... 9999
Proportional band
Pb
no
no / SP / LoSP
Autotuning
Auto
HEAt
HEAt / CooL
Output C1 operating mode
Func
Pid
Pid / OnOF
Control mode
Con1
9999
SPLL ... 9999
SPLL ... 999.9
High/maximum Set point
SPHL
-999
-999 ... SPHL
-99.9 ... SPHL
Low/minimum Set Point
SPLL
no
no / yES
Alarm programming at first or
second level parameters
ALPr
no
no / yES
Disconnection of alarm A2
dAL2
no
no / yES
Disconnection of alarm A1
dAL1
no
rL1 - rL2
rL12 - no
Alarm on for error instrument
FAIL
nO
nO - nC
Output HB logic mode
rLHb
0000
0000 ... 5111
Alarm A2 operation mode
rL2
0000
0000 ... 5111
Alarm A1 operation mode
rL1
Notes
Def.
Range
Description
Par.
7 - PROBLEMS, MAINTENANCE AND WARRANTY
ERRORS SIGNALLING
:
The 2 displays are used as well to visualise
anomaly conditions of instrument functioning :
- In case of probe interruption it's visualised
"- - - -"
flashing.
- In case the measured variable goes under the probe limits it's visualised
"uuuu"
flashing.
- In case the measured variable goes upper under the probe limits it's
visualised
"oooo"
flashing.
In these cases verify the correct connection of the probe with the
instrument and afterward proceed to verify the probe itself.
- In case the Autotuning has been interrupted by an anomaly (probe
interruption, etc.) it's visualised
"no Auto"
flashing.
- In case the Autotuning is not ended within 4 hours, it's visualised
"tout
Auto"
flashing.
- If the instrument has been switched-off during the programming, at the
next switching-on will be signalised the eeprom memory error, appearing
the message
"Err EEPr"
. To re-establish the right functioning it's
necessary to push contemporary the "P" and "LEFT" keys and then get into
parameter programming of the first level, go out regularly, even if no
parameters are changed.
All the anomaly conditions will de-active all the regulation outputs.
HOW TO CLEAN
:
We recommend to avoid abrasive cleaners or
containing solvents which could damage the instrument.
WARRANTY AND REPAIRS
:
The instrument is under warranty against
construction vices or defected material, noticed within 12 months from
delivery date.The warranty is limited to the repairs or to the substitution of
the instrument. The eventual opening of the housing, the violation of the
instrument or the wrong use and installation of the product means the
automatically decay of the warranty. In case of defected instrument,
noticed in warranty period or out of warranty, do contact our sales
department to obtain the shipment authorisation. The defected product
must be shipped to TECNOLOGIC with the detailed description of the
failures found and without any fees or charge for Tecnologic, safe
different agreements.
THP 98 PASSWORD = 0381
TECNOLOGIC - THP 98
USER MANUAL (I - GB) - Vr. 01 - ISTR 00372 - PAG. 12