Tecnologic THP 98 Operating Instructions Manual Download Page 10

ALARMS HYSTERESIS: The alarms functioning depends furthermore on
the alarms hysteresis ("HALn" parameter), which works in asymmetric
mode. More precisely, in case of minimum alarm, the alarm will be
activated when the process value goes under the alarm set and will be
deactivated when it goes upper than the alarm set + "HALn";  in case of
maximum alarm, the alarm will be activated when the process value goes
upper than the alarm set and will be deactivated when it goes under the
alarm set - "HALn". In case of window alarms, the minimum alarm
example is applicable to the lowest set ("ALnL") while the maximum alarm
example is applicable to the higher set ("ALnH"). 

b - ALARM  LATCH

It's possible to have 2 different alarm output

behaviours, depending on the value of the second figure code. 
0 = ALARM NOT LATCHED: The alarm remains active only in alarm
conditions.
1 = ALARM LATCHED: The alarm is activated when there are alarm
conditions and remains active although these conditions are not existing
anymore, till is not pushed the "LEFT" key.

c- START-UP BEHAVIOUR

It's possible to have 2 different alarm output

behaviours, depending on the value of the third figure code.
0 = NORMAL BEHAVIOUR: The alarm is always activated when there are
alarm conditions.
1 = ALARM NOT ACTIVE AT START-UP: If at start-up the instrument is
in alarm conditions this is not activated.

d - OUTPUT LOGIC MODE

It's possible to have 2 different alarm output

behaviours, depending on the value of the fourth figure code. 
1 = OUTPUT ON IN ALARM CONDITIONS: The output is activated when
the alarm is active, while is deactivated while the alarm is not active. 
0 = OUTPUT OFF IN ALARM CONDITIONS: The output is activated
when the alarm is not active, while is deactivated while the alarm is active.

4.6 - HEATER BREAK ALARM FUNCTION (HB)

The instrument can be furnished with the Heater Break alarm function.
(Alarm in case of broken heating element ), in this case it will have an
input (TAHB) able to measure the load current driven by C1 output. This
kind of input accepts signals coming from current transformers (TA) till a
maximum of 200 mA (at 200 mA the instrument measure a value of 100.0).
Therefore, to obtain the correct Ampere measure it will occur that TA ratio
would be 1/0,002. Tecnologic can supply 2 standard models : TR 03536 :
25A / 0,05 A, TR 03537 : 100 A / 0,2 A . During the functioning it's
possible to visualise on SV display the current measured by TAHB input,
expressed in Ampere (if obviously the TA ratio is 1/0,002) pushing "LEFT"
key. The alarm will be active when, in C1output active conditions, the
current measured by TAHB input will results lower than the value set on
"ALHb" parameter. "ALHb" parameter  has to be programmed with the
value of the current normally taken over by the load driven by C1 output,
considering as well the network tension fluctuations , in order to avoid
undesired alarms. As regard the HB alarm hysteresis it's automatically
calculated by the instrument as 2% of "ALHb" and the behaviour is the
same as a minimum alarm. If it's desired to deactivate the HB alarm, it's
enough to program "ALHb" = 0.0.
It's possible to have 2 different HB alarm output behaviours, depending on
the "rLHb" parameter programmed.
"nO" = NORMALLY OPENED

The output is activated when the alarm is

active, while is deactivated when the alarm is not active.
"nC" = NORMALLY CLOSED: The output is activated when the alarm is
not active, while is deactivated when the alarm is active.

Notes :

 The current measure trough TAHB input needs at least 100 mS.

5 - PROGRAMMING

Push key "P" and keep it pushed for about 2 seconds, the instrument will
show on the higher display PV the code of the first parameter ("SEtP") and
on the lower display SV the programmed value with one figure flashing.
This indicates that it's possible to modify it pushing "UP" key. When it's
desired to modify a different figure it's necessary to select it, by means of
"LEFT" key and then modify it using "UP" key. Once set the desired value
pushing key "P" on the display will be shown the code of the next
parameter. Working on "LEFT" and "UP" keys, as above described, is then
possible to modify it. Once set the desired values push key "P" several
times till the instrument goes out of the parameters programming, going
back to the normal conditions of functioning visualising the process value
on display PV and the Set Point value on display SV.  Otherwise the
instrument goes automatically out from the programming mode after about
50 seconds starting  by the moment of the last push on the keys. The last
parameter of the first level which appears on PV display is "PASS" : this is
the request of the PASSWORD to accede to the second level parameters. To
do this it's necessary to set, on Password request, the number written on
the last page of this manual, and then push "P" key. If it's set the wrong
Password the instrument goes out from the programming. The modality of
programming of the second level parameters and the operations to go out
by them are exactly the same as described for the first level parameters. 

P.A.: 

During the instrument programming the regulation is not activated

and the alarm outputs remain in the original conditions, as before the
programming input. Always go out regularly from the programming phase
because, if the instrument is switched-off during the programming, at the
next switching-on will be signalised a memory error, visualised by the
message "Err EEPr". To re-establish the functioning is needed therefore to
push, at the same time, "P" and "LEFT" keys  and then get into the first
level parameter programming, go out regularly, even if no parameters are
changed. When programming operating parameters some parameters will

TECNOLOGIC - THP 98

 

 USER MANUAL (I - GB) - Vr. 01   - ISTR 00372  - PAG. 10

Summary of Contents for THP 98

Page 1: ...perty of TECNOLOGIC S p A which forbids any reproduction and divulgation although partial if not expressly authorised TECNOLOGIC S p A reserves the right to execute aesthetically and functional modifications at any moment and without any notice INDICE PROBLEMI MANUTENZIONE E GARANZIA 7 TABELLA PARAMETRI 6 1 DESCRIZIONE DEI PARAMETRI 6 PROGRAMMAZIONE 5 FUNZIONE ALLARME DI HEATER BREAK 4 6 FUNZIONAM...

Page 2: ...o tra parti in bassa tensione alimentazione e uscite a relè e frontale Principale tra parti in bassa tensione alimentazione e uscite a relè e parti in bassissima tensione ingressi e uscite statiche Nessun isolamento tra ingressi e uscite statiche CARATTERISTICHE MECCANICHE Contenitore Plastico autoestinguente UL 94 V0 Dimensioni 48 x 96 mm DIN prof 100 mm Peso 290 g circa Installazione Incasso a p...

Page 3: ...e possiedono un elemento che causa un incremento positivo ad es Riscaldante e un elemento che causa un incremento Negativo ad es Raffreddante Il parametro Func stabilisce il funzionamento dell uscita C1 mentre l uscita C2 automaticamente funzionerà in modo opposto Ad esempio se Func HEAt all uscita C1 andrà collegato l elemento che causa incremento positivo ad es Riscaldante mentre all uscita C2 a...

Page 4: ...to quando il valore di processo scende al di sotto del valore SEtP ALn 4 ALLARME RELATIVO DI MASSIMA L allarme viene attivato quando il valore di processo sale al di sopra del valore SEtP ALn 5 ALLARME RELATIVO A FINESTRA L allarme viene attivato quando il valore di processo scende al di sotto del valore SEtP ALnL oppure quando il valore di processo sale al di sopra del valore SEtP ALnH ISTERESI D...

Page 5: ...condi dal momento in cui si è premuto per l ultima volta un tasto Come ultimo parametro nel primo livello viene visualizzato sul display PV PASS questa è la richiesta della PASSWORD per accedere ai parametri di secondo livello Per avere accesso ai parametri di secondo livello dello strumento occorre impostare alla richiesta della Password il numero riportato nell ultima pagina del presente manuale...

Page 6: ...omandato dall uscita C1 es Riscaldante quando lo strumento prevede le uscite di regolazione C1 e C2 tcr2 TEMPO DI CICLO USCITA C2 Tempo di ciclo per l uscita C2 quando interviene la regolazione proporzionale nel modo di regolazione PID espresso in sec rS RESET MANUALE Posizionamento della banda proporzionale rispetto al Set point espresso in valore percentuale Unit UNITA DI MISURA Stabilisce la vi...

Page 7: ...ifettoso quindi accompagnato dalle indicazioni del difetto riscontrato deve pervenire con spedizione in porto franco presso lo stabilimento TECNOLOGIC salvo accordi diversi 1 GENERAL DESCRIPTION THP 98 model is a single loop digital microprocessor based controller with ON OFF PID single action PID double action direct and inverse control mode and with AUTOTUNING function for PID mode The process v...

Page 8: ...as possible from source of electromagnetic disturbances so as motors power relays relays electrovalves etc The instrument is removable from its housing by the front side is recommended to disconnect the power supply from the instrument when is necessary to do this operation ELECTRICAL CONNECTIONS Carry out the electrical wiring connecting only one wire for each terminal according to the following ...

Page 9: ...wo external decimal point on the lower display SV The regulator automatically tunes all the right parameters for a correct PID control mode Before to switch off the instrument always wait for the end of the Autotuning process indicated by the return of the display on the normal functioning During the autotuning execution are activated some ON OFF regulation cycles that consequently make temperatur...

Page 10: ...utput considering as well the network tension fluctuations in order to avoid undesired alarms As regard the HB alarm hysteresis it s automatically calculated by the instrument as 2 of ALHb and the behaviour is the same as a minimum alarm If it s desired to deactivate the HB alarm it s enough to program ALHb 0 0 It s possible to have 2 different HB alarm output behaviours depending on the rLHb para...

Page 11: ... instruments with 2 regulation outputs C1 and C2 because in these models the only possible regulation is PID mode for both outputs Func OUTPUT C1 OPERATING MODE Permits to decide if C1 regulation mode has to control an Heating process HEAt or a Cooling process CooL In the instruments with 2 regulation outputs C1 and C2 this parameter automatically determines the C2 output opposite action to the on...

Page 12: ...ese cases verify the correct connection of the probe with the instrument and afterward proceed to verify the probe itself In case the Autotuning has been interrupted by an anomaly probe interruption etc it s visualised no Auto flashing In case the Autotuning is not ended within 4 hours it s visualised tout Auto flashing If the instrument has been switched off during the programming at the next swi...

Reviews: